Product information for Dold 0001034:
Applications
The insulation monitor AI 897 is used in industrial plants, medical facilities, shipboard networks, and other applications where high electrical safety and continuous monitoring of insulation condition are required. It is particularly suitable for IT systems, where the network voltage is not directly grounded, to trigger an early warning in case of earth fault. Monitoring is performed via the measurement circuit, and in three-phase networks, connection to a single phase is sufficient, as the phases are low-ohmic (approximately 3–5 Ω) coupled via the supplying transformer, enabling faults on non-connected phases to be detected.
Functions and Equipment in Detail
The device features an adjustable trip value RAN in the range of 10 to 80 kΩ, which can be continuously adjusted using a screwdriver. The measurement voltage is DC 18 V, and the maximum measurement current is less than 0.1 mA. The response delay is less than 4.2 seconds when the insulation resistance drops from infinite to 90 % of the trip value, with a trip value of 50 kΩ and a capacitance of 1 μF. When dropping to 0 kΩ, the delay is approximately 2 seconds. The hysteresis is approximately 50 % of the trip value, meaning the alarm is only reset when the insulation resistance rises above a certain threshold again. The response uncertainty is ±15 % at a trip value of 50 kΩ.
Technology Explained Simply
The insulation monitor operates on the idle current principle, where the output relay is not activated in the event of a fault, but instead a signal is triggered via the measurement circuit in case of an insulation fault. Programming is done via terminals LT1 and LT2: if these are bridged, a memory behavior is activated, where the alarm can only be reset by an external reset button or a reset switch. If no bridge is present, the device operates in hysteresis mode, where the alarm automatically resets as soon as the insulation resistance rises above the trip value again. A test button PT allows functional testing of the device, and an external test button can be connected to PT1–PT2.
Compatibility and Accessories
The device is designed for IT systems with rated voltages from AC 24 to 500 V and can be used in networks with frequencies from 45 to 400 Hz. It is designed for use in enclosures and features a protection rating of IP 40, providing protection against contact with tools and against splashing water to a limited extent. Terminal designations include A1/A2 for supply, PE for protective conductor, PT1/PT2 for external test buttons, LT1/LT2 for external reset buttons, and contacts 11, 12, 14 for the alarm indicator relay. The maximum switching voltage is AC 400 V, and the relay has a thermal current of 6 A. The electrical service life is at least 300,000 switching operations at 10 A and AC 250 V, and the mechanical service life is at least 30 million switching operations.
Mounting and Installation
Mounting is done in an enclosure with a width of 45 mm. The connection terminals are clearly labeled, and wiring is done according to the circuit diagram in the datasheet. The operating temperature range is from -20 °C to +60 °C, and the storage temperature range is from -25 °C to +70 °C. The operating altitude is limited to below 2000 m. The creepage and clearance distances correspond to pollution degree 2 with a rated impulse withstand voltage of 4 kV. The insulation test voltage is AC 2.5 kV for 1 second.
Advantages in Operation
The AI 897 offers reliable and low-maintenance monitoring of insulation resistance without auxiliary voltage. The adjustable trip threshold allows adaptation to specific requirements, and the programmability for memory or hysteresis behavior provides flexibility in alarm processing. The integrated test button and the possibility to connect external reset buttons increase operational safety. The high electrical and mechanical service life, as well as EMC testing according to IEC/EN 61000-4-2 to -4-6, ensure stable operation in industrial environments. The protection rating IP 40 protects against mechanical influences and limited splashing water, which is sufficient for use in enclosures.
| Technical data | |
| Auxiliary voltage | Without |
| Enclosure design | Switch cabinet |
| IMD type | AC |
| Nominal voltage IT system | AC 24 - 500 V |
| Response value | 10 - 80 kΩ |
| Response value type | Adjustable |
| Width | 45 mm |
| Type | AI 897 |
| Variant | |
| Alarm value | 10 - 80 kOhm |
| Contact equipping | 1 changeover contact |
| Nominal voltage | AC 42 V 45 - 400 Hz |
| Variant | Settable response value |
Questions & answers
What is the delivery time of Dold 0001034 AI 897 AC45-400Hz 42V 10-80kΩ insulation monitor?
The article Dold 0001034 AI 897 AC45-400Hz 42V 10-80kΩ insulation monitor is currently not in stock but has been backordered.
According to our experience the article is ready for dispatch within 20 working days. The delivery time usually refers to 1 piece. When ordering larger quantities, we can maybe shorten the delivery time. Just send us an inquiry about the desired quantity of Dold 0001034 to our sales team for an exact delivery time.
How can I buy the item at a lower price?
We offer you Dold 0001034 AI 897 AC45-400Hz 42V 10-80kΩ insulation monitor always at the best possible price. We can give you a discount of 2% on Dold 0001034 AI 897 AC45-400Hz 42V 10-80kΩ insulation monitor if you choose payment in advance on ordering.
In addition, you can save money with our attractive graduated prizes with every purchase. If you buy a minimum of 4 pieces of Dold 0001034 AI 897 AC45-400Hz 42V 10-80kΩ insulation monitor we can offer you a price of 256,06 EUR per piece. The more you buy, the cheaper the article will be.
We also offer individual prices for your needs. You can get an offer by using the form Wholesale Inquiry.