VDE-Kabel H07V-U2,5GNGE-R100 H07V-U 2.5 mm² green/yellow 100m-reel Eca PVC-insulated single-core cable
|
41,05 EUR |
|||||||||||
|
incl. 27,88 EUR copper surcharge ( 48,85 EUR incl. VAT ) ≈ £34.32 | ≈ $45.36 plus delivery charges: 55,00 € |
|||||||||||
| Delivery time from supplier's stock (ca.) 5 workdaysinfo_outline | |||||||||||
| Sales unit: 100 meters | |||||||||||
| In Stock: >100 meters | |||||||||||
| Lieske Part No.: | 522084 | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Mfg Part No: | H07V-U2,5GNGE-R100 | ||||||||||
| Weight: | 3.2 kg | ||||||||||
| Type: | H07V-U 2,5 GN/GE | ||||||||||
|
Graduated prices net
|
|||||||||||
Product information for VDE-Kabel H07V-U2,5GNGE-R100:
Applications
This cable is intended for use in dry, protected indoor environments, where it functions as a protective earth conductor in electrical installations. It is not suitable for direct installation on trays, gutters, or troughs, as this may compromise the mechanical and electrical integrity of the cable. It is used in permanently installed systems, where the cable is protected by conduits or channels.
Functions and Features in Detail
The cable consists of a bare, single-strand copper conductor, ensuring stable electrical conduction. The insulation is made of PVC, specified according to VDE 0207, providing sufficient electrical insulation and mechanical strength. The green-yellow sheath color is standard for protective earth conductors and supports clear identification within the installation network. The cable is rigid, allowing for fixed installation in conduits or channels, but not permitting flexible movement.
Technical Explanation
The rated voltage of 450/750 V makes the cable suitable for use in power systems typically operating at 230 V or 400 V. The test voltage of 2500 V ensures sufficient electrical strength to meet safety-critical requirements. The maximum operating temperature is +70 °C, allowing use under normal indoor conditions. During installation, the temperature must be between +5 °C and +70 °C; after installation, operation is possible from -30 °C to +70 °C. The minimum bending radius is 15 times the cable diameter to prevent damage to the insulation or conductor. Flame retardancy according to VDE 0472 Part 804, Test Method B (equivalent to IEC 332-1), ensures limited flame spread in case of fire, which is important for safety in electrical installations.
Compatibility and Accessories
The cable is designed for use in electrical installations executed in accordance with VDE and IEC standards. It is compatible with standard installation systems such as conduits, installation rails, and distributors designed for PVC-insulated cables. The green-yellow color coding enables clear identification as a protective earth conductor, which is beneficial during installation and maintenance. The cable can be combined with other cables of the same type to create complete installation sets.
Installation and Mounting
Installation is carried out by routing in conduits, channels, or under plaster. The cable is not intended for open installation on trays or gutters. The installation must ensure the minimum bending radius of 15 times the cable diameter to avoid mechanical damage. Connections are made using suitable connectors, terminals, or solder joints designed for a conductor cross-section of 2.5 mm². Installation is performed in closed systems to ensure mechanical and electrical integrity.
Operational Advantages
The cable offers high electrical insulation and mechanical stability, ensuring reliable performance in electrical installations. The green-yellow marking facilitates identification as a protective earth conductor, enhancing safety during installation and maintenance. Flame retardancy according to VDE 0472 Part 804, Test Method B, reduces the risk of flame spread in case of fire. Temperature resistance from -30 °C to +70 °C allows broad application in indoor environments with varying conditions. Use in closed installation systems protects the cable from mechanical stress and environmental influences.
The item price shown refers to 100 meters VDE-Kabel H07V-U2,5GNGE-R100
| General | |
| Conductor material | bare copper |
| Circuit board construction | solid |
| Insulating material | PVC |
| Insulation standard | VDE 0207 |
| Sheath colour | Green/yellow |
| Sheath colour standard | VDE 0293-308 |
| Nominal voltage | 450/750 V |
| Test voltage | 2500 V |
| Installation temperature range | +5 °C - +70 °C |
| Temperature range after installation | -30 °C - +70 °C |
| Maximum operating temperature | +70 °C |
| Minimum bending radius | 15 x cable diameter |
| Flame retardancy | VDE 0472 Part 804, test type B |
| Flame retardancy standard | IEC 332-1 |
Questions & answers
What is the delivery time of VDE-Kabel H07V-U2,5GNGE-R100 H07V-U 2.5 mm² green/yellow 100m-reel Eca PVC-insulated single-core cable?
The article VDE-Kabel H07V-U2,5GNGE-R100 H07V-U 2.5 mm² green/yellow 100m-reel Eca PVC-insulated single-core cable is currently in stock
According to our experience the article is ready for dispatch within 5 working days. The delivery time usually refers to 1 piece. When ordering larger quantities, we can maybe shorten the delivery time. Just send us an inquiry about the desired quantity of VDE-Kabel H07V-U2,5GNGE-R100 to our sales team for an exact delivery time.
How can I buy the item at a lower price?
We offer you VDE-Kabel H07V-U2,5GNGE-R100 H07V-U 2.5 mm² green/yellow 100m-reel Eca PVC-insulated single-core cable always at the best possible price. We can give you a discount of 2% on VDE-Kabel H07V-U2,5GNGE-R100 H07V-U 2.5 mm² green/yellow 100m-reel Eca PVC-insulated single-core cable if you choose payment in advance on ordering.
In addition, you can save money with our attractive graduated prizes with every purchase. If you buy a minimum of 15 meters of VDE-Kabel H07V-U2,5GNGE-R100 H07V-U 2.5 mm² green/yellow 100m-reel Eca PVC-insulated single-core cable we can offer you a price of 40,85 EUR per piece. The more you buy, the cheaper the article will be.
We also offer individual prices for your needs. You can get an offer by using the form Wholesale Inquiry.
How many units does the article contain?
VDE-Kabel H07V-U2,5GNGE-R100 H07V-U 2.5 mm² green/yellow 100m-reel Eca PVC-insulated single-core cable is offered by us in a sales unit of 100 meters If you need a larger quantity, you can contact us at any time. We will make a special offer for you