VDE-Kabel G338096 NHXH-J E30 5x6 mm² orange halogen-free sheathed cable
|
7,25 EUR |
|
|
incl. 3,79 EUR copper surcharge ( 8,63 EUR incl. VAT ) ≈ £6.06 | ≈ $8.01 plus delivery charges: 55,00 € |
|
| Delivery time from supplier's stock (ca.) 3 workdaysinfo_outline | |
| In Stock: >1000 meters | |
| Lieske Part No.: | 268002 |
|---|---|
| Mfg Part No: | G338096 |
| Weight: | 0.526 kg |
| Type: | NHXH 5X6 E30 |
Product information for VDE-Kabel G338096:
Applications
This cable is suitable for areas with increased fire protection requirements, such as hospitals, administrative buildings, schools, or public facilities. It is used where continuous power supply is necessary even during a fire to ensure rescue and evacuation measures. The E30 functional integrity approval means that the cable can maintain its electrical function for at least 30 minutes under fire conditions. This is crucial for the reliability of safety systems.
Functions and Features in Detail
The cable consists of bare copper conductors, which are either single-strand or multi-strand. The insulation of the conductors is a cross-linked, halogen-free, ceramizing two-layer insulation (HXI2), which forms a protective ceramic layer when heated. The conductor identification follows VDE 0293-308. A common sheath protects the individual conductors, and the outer jacket is made of a halogen-free polymer mixture in orange. This color serves as a visual identifier and is commonly used in the electrical trade for such safety cables.
Technical Explanation
The halogen-free composition of the insulation and jacket prevents the release of toxic and corrosive gases during a fire. The minimal smoke development improves visibility and rescue chances. The flame retardancy according to EN 50266-2-4 and IEC 60332-3 Cat.C ensures that the cable is not self-igniting and does not propagate flames. The insulation integrity test FE 180 according to VDE 0472 T. 814 confirms that the insulation retains its electrical insulating capability even at high temperatures. The E30 functional integrity test according to DIN 4102-12 guarantees that the cable remains electrically functional under fire conditions.
Compatibility and Accessories
The cable is suitable for standard cable support systems such as cable trays, cable ladders, and ceiling installations. It can be installed indoors, provided mechanical damage and external influences are excluded by appropriate protective measures. Installation in conduits is permitted, provided no water accumulation occurs. The cable is intended for connecting devices of protection class II, meaning it is suitable for devices without a protective earth conductor.
Installation and Mounting
During installation, a minimum temperature of +5 °C must be observed. After installation, the cable can be operated at temperatures from -30 °C to +70 °C. The bending radius is 15 times the cable diameter for single-conductor cables and 12 times for multi-conductor cables. Installation is carried out indoors, and the cables must be protected against mechanical stress. Direct installation in earth or water is not permitted.
Operational Advantages
The cable offers high safety in case of fire due to its halogen-free composition, minimal smoke development, and the ability to maintain its function under fire conditions for at least 30 minutes. The ceramizing insulation protects the conductors and prevents short circuits. The approval for safety systems according to VDE 108 makes the cable a reliable choice for critical applications. The orange jacket color facilitates identification in the installation network.
Functional Integrity E30
The test according to DIN 4102-12 (E30) ensures that the cable maintains its electrical function even at a fire temperature of 800 °C. This is crucial for the reliability of safety systems that must be activated in emergencies. Test certificates from an official material testing institute can be provided upon request.
Temperature Range and Flexibility
The cable can be installed at ambient temperatures from +5 °C to +70 °C. After installation, it is suitable for operating temperatures from -30 °C to +70 °C. The bending radius is 15 times the cable diameter for single-conductor and 12 times for multi-conductor cables, enabling flexible installation.
Rated Voltage and Test Voltage
The rated voltage is 300/500 V, which is sufficient for most indoor installations. The test voltage of 2000 V ensures the electrical strength of the insulation. The cable is therefore suitable for use in power installations.
Flame Retardancy and Insulation Integrity
The flame retardancy according to EN 50266-2-4 and IEC 60332-3 Cat.C prevents the spread of flames along the cable. The insulation integrity test FE 180 according to VDE 0472 T. 814 confirms that the insulation retains its electrical insulating capability even at high temperatures. These properties are essential for safety in case of fire.
Halogen-Free Composition and Environmental Compatibility
The halogen-free composition of the insulation and jacket prevents the release of toxic and corrosive gases during a fire. The minimal smoke development improves visibility and rescue chances. The cable is therefore environmentally compatible and safe in use.
Approvals and Standards
The cable meets the requirements for functional integrity E30 according to DIN 4102-12, flame retardancy according to EN 50266-2-4 and IEC 60332-3 Cat.C, as well as the insulation integrity test FE 180 according to VDE 0472 T. 814. These approvals make it suitable for use in safety systems according to VDE 108.
Application in Safety Systems
The cable is suitable for use in fire alarm systems, alarm and instruction systems, as well as safety and emergency lighting according to VDE 108. The E30 functional integrity test guarantees that the cable maintains its electrical function even during a fire. Test certificates from an official material testing institute can be provided upon request.
Cable Installation and Protective Measures
Installation is carried out indoors, and the cables must be protected against external influences and mechanical damage. Direct installation in earth or water is not permitted. Installation in conduits is permitted, provided no water accumulation occurs. Installation in air or concrete is allowed.
Approvals and Standards
The cable meets the requirements for functional integrity E30 according to DIN 4102-12, flame retardancy according to EN 50266-2-4 and IEC 60332-3 Cat.C, as well as the insulation integrity test FE 180 according to VDE 0472 T. 814. These approvals make it suitable for use in safety systems according to VDE 108.
Application in Safety Systems
The cable is suitable for use in fire alarm systems, alarm and instruction systems, as well as safety and emergency lighting according to VDE 108. The E30 functional integrity test guarantees that the cable maintains its electrical function even during a fire. Test certificates from an official material testing institute can be provided upon request.
Cable Installation and Protective Measures
Installation is carried out indoors, and the cables must be protected against external influences and mechanical damage. Direct installation in earth or water is not permitted. Installation in conduits is permitted, provided no water accumulation occurs. Installation in air or concrete is allowed.
| General | |
| Nominal voltage | 300/500 V |
| Test voltage | 2000 V |
| Installation temperature range | +5 °C - +70 °C |
| Temperature range after installation | -30 °C - +70 °C |
| Bend radius single-core | 15 x cable diameter |
| Bending radius multi-core | 12 x cable diameter |
| Conductor material | Copper |
| Wire insulation | networked halogen-free ceramising 2-layer insulation HXI2 |
| Conductor marking | according to VDE 0293-308 |
| Sheath colour | Orange |
| Material outer sheath | halogen-free polymer blend |
| Flame retardancy | according to EN 50266-2-4, IEC 60332-3 Cat.C |
| Insulation integrity | FE 180 according to VDE 0472 T. 814 |
| Circuit integrity | E30 according to DIN 4102-12 |
| Features | halogen-free, flame-retardant, minimal smoke emission, no corrosive gases |
The final cable weight will be determined before invoicing. The calculation is based on the copper content and any additional weight due to drums, pallets, or outer packaging. Prices are subject to this subsequent calculation.
Please note that for cables, that are not in stock and must be produced, the manufacturer may need an order of a minimum length that can be 5-10km depending on cable type!
Questions & answers
What is the delivery time of VDE-Kabel G338096 NHXH-J E30 5x6 mm² orange halogen-free sheathed cable?
The article VDE-Kabel G338096 NHXH-J E30 5x6 mm² orange halogen-free sheathed cable is currently in stock
According to our experience the article is ready for dispatch within 3 working days. The delivery time usually refers to 1 piece. When ordering larger quantities, we can maybe shorten the delivery time. Just send us an inquiry about the desired quantity of VDE-Kabel G338096 to our sales team for an exact delivery time.
How can I buy the item at a lower price?
We offer you VDE-Kabel G338096 NHXH-J E30 5x6 mm² orange halogen-free sheathed cable always at the best possible price. We can give you a discount of 2% on VDE-Kabel G338096 NHXH-J E30 5x6 mm² orange halogen-free sheathed cable if you choose payment in advance on ordering.
We also offer individual prices for your needs. You can get an offer by using the form Wholesale Inquiry.