VDE-Kabel G330096 NHXH-J E30 4x1.5 mm² orange halogen-free sheathed cable
|
2,15 EUR |
|
|
incl. 0,76 EUR copper surcharge ( 2,56 EUR incl. VAT ) ≈ £1.80 | ≈ $2.38 plus delivery charges: 55,00 € |
|
| Made to order · Delivery time approx. 20 workdaysinfo_outline | |
| Lieske Part No.: | 752765 |
|---|---|
| Mfg Part No: | G330096 |
| Weight: | 0.165 kg |
| Type: | NHXH 4X1,5 E30 |
Product information for VDE-Kabel G330096:
Applications
This cable is used in areas where special protection against fire and fire damage for people and assets is required. It is intended for installations that must continue to function during a fire, such as fire alarm systems, emergency lighting systems, and warning systems. The test for functional integrity according to DIN 4102 Part 12 (E30) has been successfully passed for all standard cable support systems such as cable trays, cable ladders, and ceiling installations. The cable is therefore suitable for use in critical safety installations that must operate reliably even under fire conditions.
Functions and Equipment in Detail
The cable consists of bare copper conductors, which are either single-strand or multi-strand. The conductor insulation is made of a cross-linked, halogen-free, ceramizing two-layer insulation (HXI2), providing high heat resistance and optimized fire behavior. The conductor identification follows VDE 0293-308. The common outer sheath protects the individual conductors and ensures a stable overall structure. The sheath color is orange and made of a halogen-free polymer blend, which is crucial for the fire behavior properties.
Technical Explanation
The cable is halogen-free, meaning that no toxic or corrosive gases are released during a fire. The fire behavior properties are enhanced by the ceramizing insulation, which forms a protective ceramic layer at high temperatures. The flame retardancy complies with standards EN 50266-2-4 and IEC 60332-3 Cat.C. The insulation integrity (FE 180) is tested according to VDE 0472 Part 814, describing the insulation’s ability to maintain its electrical properties even under fire conditions. The functional integrity (E30) according to DIN 4102-12 guarantees that the cable remains electrically functional even after 30 minutes of fire exposure.
Compatibility and Accessories
The cable is designed for use in electrical installations intended for safety and emergency lighting systems, fire alarm systems, and warning systems according to VDE 108. It is suitable for connecting devices of protection class II. Installation is carried out indoors, in air, concrete, or conduit, with the requirement to avoid water accumulation in conduit installations. The cable is not intended for direct installation in soil or water.
Installation and Mounting
During installation, care must be taken to protect the cable from external influences and mechanical damage. The minimum bending radii are 15 times the cable diameter for single-conductor cables and 12 times for multi-conductor cables. The temperature range during installation is +5 °C to +70 °C, and after installation, it is -30 °C to +70 °C. The rated voltage is 300/500 V, and the test voltage is 2000 V.
Operational Advantages
The cable offers high safety in the event of fire due to its halogen-free composition, minimal smoke development, and the ability to remain electrically functional even under fire conditions. The ceramizing insulation provides a stable protective layer at high temperatures. Testing according to DIN 4102-12 (E30) and VDE 0472 Part 814 (FE 180) ensures reliability in critical applications. The orange sheath color facilitates identification within the installation network.
Functional Integrity E30
The functional integrity test according to DIN 4102 Part 12 (E30) ensures that the cable remains electrically functional even after 30 minutes of fire exposure. This is crucial for the reliability of safety systems such as fire alarm systems and emergency lighting systems.
Halogen-Free
The cable is halogen-free, meaning that no toxic or corrosive gases are released during a fire. This protects people and technical systems from additional damage.
Ceramizing Insulation
The cross-linked, halogen-free, ceramizing two-layer insulation (HXI2) forms a protective ceramic layer at high temperatures, maintaining electrical insulation even under fire conditions.
Flame Retardancy
The flame retardancy complies with standards EN 50266-2-4 and IEC 60332-3 Cat.C, describing the cable’s ability to not propagate flame and prevent flame spread.
Insulation Integrity FE 180
The insulation integrity (FE 180) according to VDE 0472 Part 814 guarantees that the insulation retains its electrical properties even under fire conditions, which is critical for the safety of the installation.
| General | |
| Nominal voltage | 300/500 V |
| Test voltage | 2000 V |
| Installation temperature range | +5 °C |
| Temperature range after installation | -30 °C |
| Bend radius single-core | 15 x cable diameter |
| Bending radius multi-core | 12 x cable diameter |
| Circuit integrity | E30 according to DIN 4102-12 |
| Insulation integrity | FE 180 according to VDE 0472 Part 814 |
| Flame retardancy | EN 50266-2-4, IEC 60332-3 Cat.C |
| Conductor marking | VDE 0293-308 |
| Sheath colour | Orange |
| Conductor material | Copper |
| Insulation type | Networked, halogen-free, ceramizing 2-layer insulation HXI2 |
| Degree of protection | halogen-free, flame-retardant, minimal smoke emission, no corrosive gases |
The final cable weight will be determined before invoicing. The calculation is based on the copper content and any additional weight due to drums, pallets, or outer packaging. Prices are subject to this subsequent calculation.
Please note that for cables, that are not in stock and must be produced, the manufacturer may need an order of a minimum length that can be 5-10km depending on cable type!
Questions & answers
What is the delivery time of VDE-Kabel G330096 NHXH-J E30 4x1.5 mm² orange halogen-free sheathed cable?
The article VDE-Kabel G330096 NHXH-J E30 4x1.5 mm² orange halogen-free sheathed cable is currently not in stock and must be ordered on a per-order basis.
According to our experience the article is ready for dispatch within 20 working days. The delivery time usually refers to 1 piece. When ordering larger quantities, we can maybe shorten the delivery time. Just send us an inquiry about the desired quantity of VDE-Kabel G330096 to our sales team for an exact delivery time.
How can I buy the item at a lower price?
We offer you VDE-Kabel G330096 NHXH-J E30 4x1.5 mm² orange halogen-free sheathed cable always at the best possible price. We can give you a discount of 2% on VDE-Kabel G330096 NHXH-J E30 4x1.5 mm² orange halogen-free sheathed cable if you choose payment in advance on ordering.
We also offer individual prices for your needs. You can get an offer by using the form Wholesale Inquiry.