VDE-Kabel 246212 NYY-J 4x35 mm² SM Eca PVC-insulated earth cable drum
|
20,59 EUR |
|
|
incl. 17,99 EUR copper surcharge ( 24,50 EUR incl. VAT ) ≈ £17.21 | ≈ $22.81 plus delivery charges: 55,00 € |
|
| Delivery time from supplier's stock (ca.) 3 workdaysinfo_outline | |
| In Stock: >1000 meters | |
| Lieske Part No.: | 686232 |
|---|---|
| Mfg Part No: | 246212 |
| UPC/EAN: | 4018730150205 |
| Weight: | 1.697 kg |
| Type: | NYY-J 4X35 SM |
Product information for VDE-Kabel 246212:
Applications
This cable is suitable for use in various environments, including underground installations, outdoor applications, indoor spaces, and cable ducts. It is commonly used in industry, construction, and public infrastructure, where reliable and durable power supply is required. Installation must consider the specified temperature range, which during installation lies between -5 °C and +70 °C. After installation, the cable can withstand temperatures from -30 °C to +70 °C.
Functions and Features in Detail
The conductor is made of bare copper, manufactured according to VDE 0295, and has a sector-shaped multi-strand (SM) construction. This design ensures optimal current conduction and good flexibility. The cores are insulated with PVC, with core identification according to VDE 0293-308. The designation J indicates that the cable includes a green-yellow protective conductor, which is essential for electrical safety. A filler layer ensures even distribution of the cores within the cable cross-section.
Technical Explanation
The rated voltage is 0.6/1 kV, meaning the cable is suitable for transmitting electrical energy in medium-voltage installations. The test voltage of 4 kV serves quality assurance and ensures the cable remains stable even under increased electrical stress. The maximum operating temperature of +70 °C guarantees safe operation under normal conditions. The bending radius is 15 times the cable diameter for single-core conductors and 12 times for multi-core conductors, enabling flexible installation. Flame retardancy according to VDE 0472 Part 804, test method B (equivalent to IEC 332-1), ensures limited flame spread in case of fire.
Compatibility and Accessories
The cable is designed for use with standard installation techniques and materials. It can be installed in cable ducts, underground, or outdoors. Connections are made using appropriate cable lugs, cable glands, or other electrical connection components suitable for the specific application. The use of appropriate tools such as cable cutters, wire strippers, or cable knives is required to ensure clean and safe processing.
Installation and Mounting
Installation requires adherence to the specified temperature ranges and bending radii. The cable should not be excessively bent or stretched to avoid damage to the conductors. Underground installation requires sufficient depth and protective measures against mechanical damage, such as protective conduits or concrete slabs. Electrical connections are made using suitable connection components designed for the respective voltage and current rating.
Operational Advantages
The cable offers high mechanical strength, good resistance to environmental influences, and reliable electrical conductivity. The PVC insulation and outer sheath protect the cable against moisture, mechanical stress, and chemical influences. Flame retardancy increases safety in case of fire. The use of a green-yellow protective conductor ensures compliance with safety regulations and protects people from electrical hazards.
| General | |
| Nominal voltage | 0,6/1 kV |
| Test voltage | 4 kV |
| Installation temperature range | -5 to +70 °C |
| Temperature range after installation | -30 to +70 °C |
| Operation temperature | +70 °C |
| Bend radius single-core | 15 x cable diameter |
| Bending radius multi-core | 12 x cable diameter |
| Flame retardancy | VDE 0472 Teil 804, Prüfart B (IEC 332-1) |
| Circuit board construction | sector-shaped stranded (SM) |
| Wire insulation | PVC |
| Outer sheath | PVC black |
| Conductor marking | according to VDE 0293-308 |
The final cable weight will be determined before invoicing. The calculation is based on the copper content and any additional weight due to drums, pallets, or outer packaging. Prices are subject to this subsequent calculation.
Please note that for cables, that are not in stock and must be produced, the manufacturer may need an order of a minimum length that can be 5-10km depending on cable type!
Questions & answers
What is the delivery time of VDE-Kabel 246212 NYY-J 4x35 mm² SM Eca PVC-insulated earth cable drum?
The article VDE-Kabel 246212 NYY-J 4x35 mm² SM Eca PVC-insulated earth cable drum is currently in stock
According to our experience the article is ready for dispatch within 3 working days. The delivery time usually refers to 1 piece. When ordering larger quantities, we can maybe shorten the delivery time. Just send us an inquiry about the desired quantity of VDE-Kabel 246212 to our sales team for an exact delivery time.
How can I buy the item at a lower price?
We offer you VDE-Kabel 246212 NYY-J 4x35 mm² SM Eca PVC-insulated earth cable drum always at the best possible price. We can give you a discount of 2% on VDE-Kabel 246212 NYY-J 4x35 mm² SM Eca PVC-insulated earth cable drum if you choose payment in advance on ordering.
We also offer individual prices for your needs. You can get an offer by using the form Wholesale Inquiry.