Applications
This cable is designed for use in indoor environments where a dry condition is guaranteed. It is commonly used in electrical installations in building and industrial applications, particularly in conjunction with control panels, distributors, and lighting systems. Installation takes place in closed channels or conduits to protect the cable from mechanical stress and environmental influences. Use in damp or wet areas is not intended.
Functions and Features in Detail
The cable consists of a bare, fine-stranded copper conductor, providing high flexibility and good electrical conductivity. Insulation is made of PVC according to VDE 0207, ensuring high mechanical strength and chemical resistance. The sheath color complies with VDE 0293 standards, with blue (BLAUTR) used for identification of the cable. The color serves for clear identification within the installation network, especially when used in electrical systems.
Technical Explanation
The rated voltage of 450/750 V means the cable is designed for electrical systems operating up to 750 V DC or 450 V AC (at 50 Hz). The test voltage of 2500 V ensures quality control and guarantees that the insulation remains stable even under increased voltage. The maximum operating temperature is +70 °C, making the cable suitable for use under normal indoor conditions. During installation, the temperature must be between +5 °C and +70 °C; after installation, the ambient temperature can drop to -30 °C without damaging the cable. The minimum bending radius is 15 times the cable diameter, allowing flexible installation without damaging the insulation. Flame retardancy according to VDE 0472 T. 804, test method B (equivalent to IEC 332-1), limits flame spread in case of fire, enhancing safety in buildings.
Compatibility and Accessories
The cable is compatible with standard installation systems for electrical installations in buildings and industrial facilities. It can be combined with other cables of type H07V-K, especially in control panels and distributors. Use in conjunction with luminaires requires protected installation to ensure mechanical and electrical integrity. The cable is not intended for use in open or damp areas, so it should not be combined with products designed for such environments.
Installation and Mounting
Installation must take place in closed conduits or channels, and the cable must not be laid directly on trays, gutters, or troughs. Installation must occur at temperatures between +5 °C and +70 °C to ensure optimal processing. The minimum bending radius of 15 times the cable diameter must be observed to avoid damaging the insulation. The cable is flexible and can therefore be used in complex installation scenarios, although mechanical stress from bending and tensile forces should be limited.
Operational Advantages
The cable offers high electrical conductivity due to the fine-stranded copper conductor, resulting in low voltage drops. The PVC insulation ensures high mechanical strength and chemical resistance, extending the cable’s service life. Flame retardancy according to VDE 0472 T. 804, test method B, enhances safety in case of fire by limiting flame spread. The clear color marking (blue) simplifies identification within the installation network, making maintenance and fault diagnosis easier. The cable is designed for use in dry indoor environments, ensuring reliable performance in typical building installations.
| General | |
| Nominal voltage | 450/750 V |
| Test voltage | 2500 V |
| Installation temperature range | +5 °C - +70 °C |
| Temperature range after installation | -30 °C - +70 °C |
| Operation temperature | +70 °C |
| Bending radius | 15 x cable diameter |
| Flame retardancy | in accordance with VDE 0472 Part 804, test type B |
| Insulation | PVC according to VDE 0207 |
| Conductor | bare copper, fine-stranded |
| Sheath colour | blue (BLAUTR) |
| Application | installation in dry rooms, switching and distribution installations, in conduits above and below plaster, as well as in closed installation channels |
The final cable weight will be determined before invoicing. The calculation is based on the copper content and any additional weight due to drums, pallets, or outer packaging. Prices are subject to this subsequent calculation.
Please note that for cables, that are not in stock and must be produced, the manufacturer may need an order of a minimum length that can be 5-10km depending on cable type!
Questions & answers
What is the delivery time of Kabelwerk Eupen AG N050046 H07V-K 70.0 mm² blue Eca PVC-insulated single-core cable?
The article Kabelwerk Eupen AG N050046 H07V-K 70.0 mm² blue Eca PVC-insulated single-core cable is currently in stock
According to our experience the article is ready for dispatch within 5 working days. The delivery time usually refers to 1 piece. When ordering larger quantities, we can maybe shorten the delivery time. Just send us an inquiry about the desired quantity of Kabelwerk Eupen AG N050046 to our sales team for an exact delivery time.
How can I buy the item at a lower price?
We offer you Kabelwerk Eupen AG N050046 H07V-K 70.0 mm² blue Eca PVC-insulated single-core cable always at the best possible price. We can give you a discount of 2% on Kabelwerk Eupen AG N050046 H07V-K 70.0 mm² blue Eca PVC-insulated single-core cable if you choose payment in advance on ordering.
We also offer individual prices for your needs. You can get an offer by using the form Wholesale Inquiry.