Hager CDA263D residual current circuit breaker 2-pole 6kA 63A 30mA type A
|
334,11 EUR 348,18 EUR |
|||||||||||
|
( 397,59 EUR incl. VAT ) ≈ £279.98 | ≈ $375.21 plus delivery charges: 53,00 € |
|||||||||||
| Delivery time from supplier's stock (ca.) 5 workdaysinfo_outline | |||||||||||
| In Stock: 3 pieces | |||||||||||
| Datasheet: | file_download Download | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Lieske Part No.: | 388354 | ||||||||||
| Mfg Part No: | CDA263D | ||||||||||
| UPC/EAN: | 3250611610052 | ||||||||||
| Weight: | 0.202 kg | ||||||||||
| Type: | CDA263D | ||||||||||
|
Graduated prices net
|
|||||||||||
Product information for Hager CDA263D:
- Standards: EN 61008-1, EN 61008-2-1, VDE 0664 Part 10 + 11
- Rated voltage 230/400 VAC 50/60 Hz
- Sensitive to pulsating currents and surge currents up to 250 A
- Short-circuit protection fuse 6 kA at 63 A / gL
- Suitable for retro-fitting of additional equipment
- Single phase extraction from the composite rail possible
- With installer-friendly bi-connect terminal
- Electric shock protection to DIN VDE 0106 part 100
RCD 2-pole
IU Rated current: 63 A
Type: CDA263D
Quantity: 1 unit.
| General | |
| Number of poles | 2 |
| Rated voltage | 230 V |
| Rated current | 63 A |
| Rated fault current | 0.03 A |
| Rated insulation voltage Ui | 500 V |
| Rated impulse withstand voltage Uimp | 4 kV |
| Mounting method | DIN rail |
| Leakage current type | A |
| Short-circuit breaking capacity (Icw) | 6 kA |
| Surge current capacity | 0.25 kA |
| Frequency | 50 Hz |
| Degree of protection (IP) | IP20 |
| Width in number of modular spacings | 2 |
| Built-in depth | 70 mm |
| Ambient temperature during operating | 40 °C |
| Pollution degree | 2 |
| Connectable conductor cross section multi-wired | 16 mm² |
| Connectable conductor cross section solid-core | 25 mm² |
| Power loss | 8.10 W |
| RAL-number (akin) | 7005 |
| Voltage type | AC |
| Selective protection | |
| Short-time delayed tripping | |
| Additional equipment possible | |
| With interlocking device | |
| Explosion-proof | |
Questions & answers
What is the delivery time of Hager CDA263D residual current circuit breaker 2-pole 6kA 63A 30mA type A?
The article Hager CDA263D residual current circuit breaker 2-pole 6kA 63A 30mA type A is currently in stock
According to our experience the article is ready for dispatch within 5 working days. The delivery time usually refers to 1 piece. When ordering larger quantities, we can maybe shorten the delivery time. Just send us an inquiry about the desired quantity of Hager CDA263D to our sales team for an exact delivery time.
How can I buy the item at a lower price?
We offer you Hager CDA263D residual current circuit breaker 2-pole 6kA 63A 30mA type A always at the best possible price. We can give you a discount of 2% on Hager CDA263D residual current circuit breaker 2-pole 6kA 63A 30mA type A if you choose payment in advance on ordering.
In addition, you can save money with our attractive graduated prizes with every purchase. If you buy a minimum of 4 pieces of Hager CDA263D residual current circuit breaker 2-pole 6kA 63A 30mA type A we can offer you a price of 306,55 EUR per piece. The more you buy, the cheaper the article will be.
We also offer individual prices for your needs. You can get an offer by using the form Wholesale Inquiry.