| General | |
| SPD as per EN 61673-11 / IEC 61643-11 | type 1 + type 2 + type 3 / class I + class II + class III |
| Energy coordination with terminal equipment (≤ 10 m) | Type 1 + Type 2 + Type 3 |
| Nominal voltage (a.c.) (UN) | 230 / 400 V (50 / 60 Hz) |
| Max. continuous operating voltage (AC) (UC) | 264 V (50 / 60 Hz) |
| Lightning impulse current (10/350 µs) [L1+L2+L3+N-PE] (Itotal) | 100 kA |
| Specific energy [L1+L2+L3+N-PE] (W/R) | 2.50 MJ/ohms |
| Lightning impulse current (10/350 µs) [L, N-PE] (Iimp) | 25 kA |
| Specific energy [L,N-PE] (W/R) | 156.25 kJ/ohms |
| Nominal discharge current (8/20 µs) [L/N-PE] (In) | 25 kA |
| Voltage protection level [L-PE]/[N-PE] (UP) | ≤ 1.5 kV |
| Open-circuit voltage of the combination wave generator (UOC) | 20 kV |
| Follow current extinguishing capability (a.c.) (Ifi) | 50 kArms |
| Integrated overcurrent protection | Yes, ACI technology |
| Integrated ACI technology is selective to upstream fuse | ≥ 100 A gG |
| Short-circuit strength [L-PE]/[N-PE] (ISCCR) | 50 kAeff |
| Response time (tA) | ≤ 100 ns |
| Temporary overvoltage (UT) – characteristic | 440 V / 120 min. – withstand |
| Operating temperature range (TU) | -40°C to +80°C |
| Operating state / fault indication | Green / red (inspection window) |
| Module disconnection indication | Green (side view) |
| Number of ports | 1 |
| Cross-sectional area (L1, L2, L3, N, PE, ) (min.) | 16 mm² |
| Cross-sectional area (L1, L2, L3, N, PE, ) (max.) | 16 mm² solid / 35 mm² stranded / 25 mm² fine-stranded |
| For mounting on | 35-mm DIN rail as per EN 60715 / busbar |
| Place of installation | Indoor |
| Degree of protection | IP 20 |
| Capacity | 11 Standard DIN module, DIN 43880 |
| When used in switchgear with prospective short-circuit currents exceeding 50 kArms (tested by VDE) | |
| Max. prospective short-circuit current | 100 kArms (220 kApeak) |
| Limitation / Extinction of mains follow currents | Up to 100 kArms (220 kApeak) |
Questions & answers
What is the delivery time of DEHN 961405 DV ACI M TNS 264 FM combination surge arrester Type 1+2+3?
The article DEHN 961405 DV ACI M TNS 264 FM combination surge arrester Type 1+2+3 is currently not in stock and must be ordered on a per-order basis.
According to our experience the article is ready for dispatch within 20 working days. The delivery time usually refers to 1 piece. When ordering larger quantities, we can maybe shorten the delivery time. Just send us an inquiry about the desired quantity of DEHN 961405 to our sales team for an exact delivery time.
How can I buy the item at a lower price?
We offer you DEHN 961405 DV ACI M TNS 264 FM combination surge arrester Type 1+2+3 always at the best possible price. We can give you a discount of 2% on DEHN 961405 DV ACI M TNS 264 FM combination surge arrester Type 1+2+3 if you choose payment in advance on ordering.
We also offer individual prices for your needs. You can get an offer by using the form Wholesale Inquiry.