Product information for DEHN 952017:
Applications
The protection module DG MOD 750 is intended for use in electrical installations in the low-voltage range, particularly in buildings equipped with an electrical distribution system serving multiple consumers. It is generally used in the second protection level (Type 2) to further reduce overvoltages not fully absorbed by a Type 1 arrester (e.g., in the main distribution board). The application typically occurs at the distribution level, for example, before devices or in substations, where high protection quality is required. The standard EN 61643-11 defines the requirements for performance and electrical characteristics for such arresters.
Functions and Equipment in Detail
The module is based on varistor technology, which exhibits a nonlinear current-voltage characteristic. Under normal operating voltage, the varistor remains in a high-resistance state and conducts almost no current. As soon as an overvoltage occurs, the resistance drops suddenly, allowing the overvoltage current to be diverted. This process takes place within nanoseconds, thereby protecting connected devices from damage. The module is designed as a replacement or addition to the DEHNguard system, with installation into designated module inserts. The construction allows for easy integration into existing switchgear installations.
Technology Explained Simply
The varistor technology used in the DG MOD 750 is a proven method for overvoltage protection. Varistors are made of semiconductor material that becomes conductive under overvoltage conditions. The protection function is achieved by diverting the overvoltage current through the varistor to earth. The standard EN 61643-11 defines the requirements for impulse voltage withstand, including impulse voltage withstand at 1.2/50 µs and at 8/20 µs, which the module must meet. The exact impulse voltage withstand and maximum permissible impulse voltage are specified in the product's technical data. The protection function operates without mechanical movement, ensuring high reliability and long service life.
Compatibility and Accessories
The DG MOD 750 is specifically developed for the DEHNguard modular system and can only be used in conjunction with the designated housings and mounting units. It is not a universal module, but is adapted to the construction and mounting geometry of the DEHNguard system. Compatibility is limited to DEHNguard module systems, particularly those designed for mounting Type 2 modules.
Mounting and Installation
Installation is carried out in the designated module inserts of the DEHNguard system. The installation must comply with VDE regulations and relevant installation guidelines. The module is inserted into the appropriate rail or module housing and connected to the lines. Earthing must be secure and executed in accordance with applicable standards to ensure the protection function. Installation is typically performed by qualified specialists familiar with regulations for electrical installations.
Advantages in Operation
The DG MOD 750 provides reliable protection for electrical installations. The use of varistors ensures a rapid response to overvoltages, thereby protecting sensitive devices from damage. Integration into the DEHNguard system enables modular expansion of the protection function without requiring extensive modifications. The construction is robust and suitable for use in industrial and commercial installations. The protection function remains effective throughout the module's service life, provided no mechanical damage or overloads occur.
| General | |
| Degree of protection | Type 2 in accordance with EN 61643-11 |
| Technology | Varistor (voltage-sensitive resistor) |
| System compatibility | DEHNguard modular |
| Norm | EN 61643-11 |
| Nominal discharge current (8/20 µs) (In) | 15 kA |
| Max. discharge current (8/20 µs) (Imax) | 25 kA |
| Max. continuous operating a.c. voltage (UC) | 600 V |
| Rated varistor voltage (Umov) | 750 V |
Questions & answers
What is the delivery time of DEHN 952017 DG MOD 750 surge arrester Type2 varistor protection module for guard M + S?
The article DEHN 952017 DG MOD 750 surge arrester Type2 varistor protection module for guard M + S is currently not in stock and must be ordered on a per-order basis.
According to our experience the article is ready for dispatch within 20 working days. The delivery time usually refers to 1 piece. When ordering larger quantities, we can maybe shorten the delivery time. Just send us an inquiry about the desired quantity of DEHN 952017 to our sales team for an exact delivery time.
How can I buy the item at a lower price?
We offer you DEHN 952017 DG MOD 750 surge arrester Type2 varistor protection module for guard M + S always at the best possible price. We can give you a discount of 2% on DEHN 952017 DG MOD 750 surge arrester Type2 varistor protection module for guard M + S if you choose payment in advance on ordering.
In addition, you can save money with our attractive graduated prizes with every purchase. If you buy a minimum of 5 pieces of DEHN 952017 DG MOD 750 surge arrester Type2 varistor protection module for guard M + S we can offer you a price of 108,67 EUR per piece. The more you buy, the cheaper the article will be.
We also offer individual prices for your needs. You can get an offer by using the form Wholesale Inquiry.