DEHN 943110 DG MD TT 2P surge protector type 2+3 275
|
113,02 EUR |
|
|
( 134,49 EUR incl. VAT ) ≈ £94.60 | ≈ $124.21 plus delivery charges: 55,00 € |
|
| Made to order · Delivery time approx. 20 workdaysinfo_outline | |
| Datasheet: | file_download Download |
|---|---|
| Lieske Part No.: | 2492476 |
| Mfg Part No: | 943110 |
| UPC/EAN: | 4013364554030 |
| Weight: | 0.25 kg |
| Type: | DG MD TT 2P 275 |
| Arrester use at 16.7 Hz – traction power supply systems | |
| Test voltage AC (UC) | 275 V |
| Nominal AC voltage (UN) | 230 / 400 V |
| Nominal frequency AC (fN) | 16.7 Hz |
| Technical data | |
| Energy coordination with terminal equipment (≤ 10 m) | type 2 + type 3 |
| Nominal voltage (a.c.) (UN) | 230 / 400 V (50 / 60 Hz) |
| Max. continuous operating voltage (a.c.) [L-N] (UC) | 275 V (50 / 60 Hz) |
| Max. continuous operating voltage (a.c.) [N-PE] (UC) | 255 V (50 / 60 Hz) |
| Nominal discharge current (8/20 µs) (In) | 20 kA |
| Max. discharge current (8/20 µs) (Imax) | 40 kA |
| Combination wave [L-N] (UOC) | 20 kV |
| Combination wave [N-PE] (UOC) | 6 kV |
| Nominal load current for “V-connection” (IL) | 63 A |
| Voltage protection level [L-N]/[N-PE] (UP) | ≤ 1.5 / ≤ 1.5 kV |
| Voltage protection level [L-N]/[N-PE] at 5 kA (UP) | ≤ 1 / ≤ 1.5 kV |
| Response time [L-N] (tA) | ≤ 25 ns |
| Response time [N-PE] (tA) | ≤ 100 ns |
| Max. mains-side overcurrent protection | 125 A gG |
| Max. mains-side overcurrent protection with “V-connection” | 63 A gG |
| Short-circuit withstand capability for max. mains-side overcurrent protection (ISCCR) | 50 kArms |
| Temporary overvoltage (TOV) [L-N] (UT) – Characteristic | 335 V / 5 sec. – Festigkeit, 440 V / 120 min. – sicherer Ausfall |
| Temporary overvoltage (TOV) [N-PE] (UT) - Characteristic | 1200 V / 200 ms – withstand |
| Operating temperature range (TU) | -40 °C ... +80 °C |
| Operating state / fault indication | green / red |
| Number of ports | 1 |
| Cross-sectional area (min.) | 1.5 mm2 solid / flexible |
| For mounting on | 35 mm DIN rails acc. to EN 60715 |
| Enclosure material | thermoplastic, red, UL 94 V-0 |
| Place of installation | indoor installation |
| Degree of protection | IP 20 (integrated) |
| Capacity | 2 Standard DIN module, DIN 43880 |
| Approvals | DEKRA |
Questions & answers
What is the delivery time of DEHN 943110 DG MD TT 2P surge protector type 2+3 275?
The article DEHN 943110 DG MD TT 2P surge protector type 2+3 275 is currently not in stock and must be ordered on a per-order basis.
According to our experience the article is ready for dispatch within 20 working days. The delivery time usually refers to 1 piece. When ordering larger quantities, we can maybe shorten the delivery time. Just send us an inquiry about the desired quantity of DEHN 943110 to our sales team for an exact delivery time.
How can I buy the item at a lower price?
We offer you DEHN 943110 DG MD TT 2P surge protector type 2+3 275 always at the best possible price. We can give you a discount of 2% on DEHN 943110 DG MD TT 2P surge protector type 2+3 275 if you choose payment in advance on ordering.
We also offer individual prices for your needs. You can get an offer by using the form Wholesale Inquiry.