Surge arrester 907421 Dehnrapid LSA protection class DRL RE 12
|
48,55 EUR 49,10 EUR |
|||||||||||
|
( 57,77 EUR incl. VAT ) ≈ £40.64 | ≈ $53.36 plus delivery charges: 55,00 € |
|||||||||||
| Made to order · Delivery time approx. 20 workdaysinfo_outline | |||||||||||
| Datasheet: | file_download Download | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Lieske Part No.: | 517450 | ||||||||||
| Mfg Part No: | 907421 | ||||||||||
| UPC/EAN: | 4013364107618 | ||||||||||
| Weight: | 0.0005 kg | ||||||||||
| Type: | DRL RE 12 | ||||||||||
|
Graduated prices net
|
|||||||||||
Product information for DEHN 907421:
Applications
The DRL RE 12 protection plug is particularly suitable for applications in industrial electrical engineering, where signal circuits with common reference potential are operated. This includes, for example, control and regulation systems, communication lines, as well as sensors and actuators in automated production environments. Use in DRL plug magazines enables modular and flexible integration into existing switchgear. The energetic coordination ensures that the protection plug reacts correctly in the event of overvoltage without damaging downstream devices.
Functions and Equipment in Detail
The protection plug features decoupling impedances that enable galvanic isolation between the connected lines and the protection device. This reduces the transmission of interference and increases the stability of signal circuits. The single-stage protection function means that the surge protection is installed directly at the end point of the signal circuit to ensure maximum protection effectiveness. Grounding is achieved via EF 10 DRL, enabling safe and reliable dissipation of overvoltages.
Technology Explained Simply
The DRL RE 12 protection plug operates on the principle of diverting overvoltages through a diverter that activates when a defined voltage threshold is exceeded. The decoupling impedances ensure that signal circuits are electrically separated from each other, minimizing interference. Energetic coordination means that the protection plug is matched in terms of energy absorption and dissipation with other protection components in the system, ensuring cascaded protection. Installation is exclusively in disconnectors or DRL plug magazines, enabling standardized and secure mounting.
Compatibility and Accessories
The protection plug is specifically designed for use in DRL plug magazines and disconnectors. It is energetically coordinated with other components of the DRL system, enabling safe integration into existing switchgear.
Mounting and Installation
Mounting is exclusively in disconnectors or DRL plug magazines. The protection plug is inserted into the designated socket and mechanically secured. No additional mounting aids or tools are required, as installation is simple and quick due to the plug-in technology. Installation is typically performed by qualified specialists as part of electrical installation.
Advantages in Operation
The DRL RE 12 protection plug provides reliable protection of signal circuits against overvoltages, particularly in environments with common reference potential. The decoupling impedances reduce interference and improve signal quality. Energetic coordination ensures safe and efficient protection function throughout the system. The modular design enables flexible expansion and maintenance of the switchgear. Installation in DRL plug magazines or disconnectors ensures standardized and secure mounting, improving the maintainability and expandability of the installation.
| General | |
| Degree of protection | IP 20 (when plugged in) |
| Power throughput | 12 kA |
| Grounding | via EF 10 DRL |
| Compatibility | for disconnecting strips or DRL plug-in magazine |
| Decoupling | with decoupling impedances |
| Energy coordination | electrically coordinated with DRL plug-in module |
| SPD class | O |
| Nominal voltage (UN) | 12 V |
| Max. continuous operating voltage DC (UC) | 14 V |
| Max. continuous operating a.c. voltage (UC) | 9.5 V |
| Nominal current (IN) | 0.4 A |
| D1 Total lightning impulse current (10/350 µs) in combination with DRL 10 B... (Iimp) | 5 kA |
| D1 Lightning impulse current (10/350 µs) per line in combination with DRL 10 B... (Iimp) | 2.5 kA |
| C2 Total nominal discharge current (8/20 µs) in combination with DRL 10 B... (In) | 10 kA |
| C2 Nominal discharge current (8/20 µs) per line in combination with DRL 10 B... (In) | 5 kA |
| C1 Nominal discharge current (8/20 µs) per line without DRL 10 B... (In) | 0.5 kA |
| Voltage protection level line-PG for Iimp D1 in combination with DRL 10 B... (UP) | ≤ 45 V |
| Voltage protection level line-line at 1 kV/µs C3 (UP) | ≤ 36 V |
| Voltage protection level line-PG at 1 kV/µs C3 (Up) | ≤ 19 V |
| Series impedance per line | 4.7 ohms |
| Cut-off frequency line-PG (fG) | 2.7 MHz |
| Capacitance line-line (C) | ≤ 1 nF |
| Capacitance line-PG (C) | ≤ 2 nF |
| Operating temperature range (TU) | -40 °C ... +80 °C |
| Pluggable into | LSA disconnection block 2/10 or DRL 10 B ... plug-in SPD block |
| Earthing via | earthing frame |
| Enclosure material | polyamide PA 6.6 |
| Colour | yellow |
| Test standards | IEC 61643-21 / EN 61643-21 |
Questions & answers
What is the delivery time of Surge arrester 907421 Dehnrapid LSA protection class DRL RE 12?
The article Surge arrester 907421 Dehnrapid LSA protection class DRL RE 12 is currently not in stock and must be ordered on a per-order basis.
According to our experience the article is ready for dispatch within 20 working days. The delivery time usually refers to 1 piece. When ordering larger quantities, we can maybe shorten the delivery time. Just send us an inquiry about the desired quantity of DEHN 907421 to our sales team for an exact delivery time.
How can I buy the item at a lower price?
We offer you Surge arrester 907421 Dehnrapid LSA protection class DRL RE 12 always at the best possible price. We can give you a discount of 2% on Surge arrester 907421 Dehnrapid LSA protection class DRL RE 12 if you choose payment in advance on ordering.
In addition, you can save money with our attractive graduated prizes with every purchase. If you buy a minimum of 10 pieces of Surge arrester 907421 Dehnrapid LSA protection class DRL RE 12 we can offer you a price of 45,64 EUR per piece. The more you buy, the cheaper the article will be.
We also offer individual prices for your needs. You can get an offer by using the form Wholesale Inquiry.