| General |
| Housing plastic, glass | plastic, glass |
| Colours (similar) | RAL 9010 (white), RAL 9005 (black) |
| Dimensions (Ø × H) | 80mm × 36mm |
| Degree of protection | IP30 |
| Weight total | ≈ 50 g |
| Ambient temperature | 5…+45°C |
| Ambient air humidity (rH) (non-condensing) | 5...95% |
| Storage temperature | 25...+70°C |
| Over voltage category | III |
| Pollution degree | 2 |
| KNX bus |
| Medium | TP1-256 |
| Configuration mode | S-Mode |
| Maximum group addresses | 254 |
| Maximum assignments | 254 |
| Communication objects | 252 / 122 |
| Nominal voltage | 30V DC SELV |
| Electricity consumption | ≤ 10mA |
| Connection KNX plug-in terminal conductor diameter | 0.8mm s |
| Connection KNX plug-in terminal stripping length | 5mm |
| Time until data reception after bus voltage recovery | ≈ 5 s |
| Sensors |
| Detection method presence passive infrared technique | PIR |
| Presence detection angle | ≈ 94° × 82° |
| Presence detection range | ≈ 5 m |
| Brightness measurement range | 0 Lux … 2000 Lux |
| Temperature measurement range | 5…+60 °C |
| Humidity measurement range (rH) | 0...100 % |
The Elsner Intra-Sewi KNX TH-L-Pr is an in-wall presence, light, and room climate sensor for the KNX building bus system. It is used to detect presence, light intensity, room temperature, and relative humidity, enabling intelligent control of lighting, heating, cooling, and ventilation in indoor spaces. The device is designed for installation in hollow ceilings or in recessed mounting and features integrated logic functions for linking sensor data and control commands.
Applications
The sensor is suitable for use in residential and office buildings where automated, energy-saving room climate control is required. It detects the presence of people in the room using a passive infrared (PIR) method with a range of approximately 5 meters and a detection angle of approximately 94° × 82°. Light intensity is measured in the range of 0 to 2000 Lux, allowing rooms with varying lighting conditions to be monitored. Temperature measurement is performed in the range of 5 to +60 °C, and relative humidity is measured in the range of 0 to 100 %. These values are used to calculate the dew point and to check whether the comfort zone according to DIN 1946 is exceeded.
Functions and Equipment in Detail
The sensor features integrated PI controllers that can control heating or cooling based on temperature and ventilation based on humidity. Control can be performed either according to separate setpoints or a base setpoint. Additionally, two control value comparators are integrated, which can calculate minimum, maximum, or average values from five received values. The logic functions include four AND and four OR gates, each with four inputs, which can process both switching events and communication objects. The outputs of the gates can be configured as either 1 bit or 2 x 8 bits. Configuration is performed via the KNX software ETS.
Technology Explained Simply
The sensor operates in the TP1-256 bus medium and is configurable in S-Mode. The nominal voltage is 30 V DC SELV, and the current consumption is up to 10 mA. Communication objects include 252 inputs and 122 outputs, with support for up to 254 group addresses and assignments. The connection terminal for the KNX bus is designed for conductors with a diameter of 0.8 mm, and the stripping length is 5 mm. After restoring bus voltage, it takes approximately 5 seconds before data can be received. The housing is made of plastic and glass, available in RAL 9010 (white) and RAL 9005 (black), with dimensions of 80 mm Ø × 36 mm height. The protection rating is IP30, providing protection against solid objects larger than 2.5 mm and against splashing water from any direction. The ambient temperature ranges from 5 to +45 °C, and the humidity (non-condensing) ranges from 5 to 95 %. The storage temperature is 25 to +70 °C. The overvoltage category is III, and the pollution degree is 2.
Compatibility and Accessories
The sensor is designed for the KNX system and can communicate with other KNX devices. The integrated functions allow processing of external temperature and humidity values received via the bus and combining them with internal measurements to create mixed values, for example, for room average.
Installation and Mounting
The sensor is installed in hollow ceilings or in a recessed mounting opening. The delivery includes pre-mounted terminals for hollow ceiling installation, a mounting ring for recessed installation, and a KNX plug terminal. Installation is carried out according to the installation instructions included in the delivery, available in German, English, French, Italian, and Spanish. Additionally, a manual is available for download.
Operational Advantages
By combining presence, light, and room climate sensors in a single device, the number of required individual components is reduced. The integrated logic functions enable flexible control of room climate and lighting, resulting in energy savings and a more comfortable indoor climate. The calculation of the dew point and monitoring of the comfort zone according to DIN 1946 support healthy and pleasant indoor air quality. Communication objects and configuration via ETS allow individual adaptation to the specific requirements of the building.
Scope of Delivery
- Sensor
- Pre-mounted terminals for hollow ceiling installation
- Mounting ring for recessed installation
- KNX plug terminal
- Datasheet with installation instructions (German, English, French, Italian, Spanish)
- Manual (German, English, French, Italian, Spanish) as download
- Product file (German, English, French, Italian, Spanish) as download