| General |
| Housing plastic, glass | plastic, glass |
| Colours (similar) | RAL 9010 (white), RAL 9005 (black) |
| Dimensions (Ø × H) | 80mm × 36mm |
| Degree of protection | IP30 |
| Weight total | ≈ 50 g |
| Ambient temperature | 5…+45°C |
| Ambient air humidity (rH) (non-condensing) | 5...95% |
| Storage temperature | 25...+70°C |
| Over voltage category | III |
| Pollution degree | 2 |
| KNX bus |
| Medium | TP1-256 |
| Configuration mode | S-Mode |
| Maximum group addresses | 254 |
| Maximum assignments | 254 |
| Communication objects | 252 / 122 |
| Nominal voltage | 30V DC SELV |
| Electricity consumption | ≤ 10mA |
| Connection KNX plug-in terminal conductor diameter | 0.8mm s |
| Connection KNX plug-in terminal stripping length | 5mm |
| Time until data reception after bus voltage recovery | ≈ 5 s |
| Sensors |
| Detection method presence passive infrared technique | PIR |
| Presence detection angle | ≈ 94° × 82° |
| Presence detection range | ≈ 5 m |
| Brightness measurement range | 0 Lux … 2000 Lux |
| Temperature measurement range | 5…+60 °C |
| Humidity measurement range (rH) | 0...100 % |
The Elsner Intra-Sewi KNX L-Pr is an in-wall presence detector with integrated light sensor, specifically designed for use in the KNX bus system. The device detects the presence of persons using passive infrared technology (PIR) and simultaneously monitors ambient lighting, enabling intelligent lighting control in indoor spaces. The combination of presence detection and light measurement makes the sensor particularly suitable for office and administrative rooms, where automatic, energy-saving lighting control is required. The housing is made of plastic and glass, available in RAL 9010 (white) and RAL 9005 (black), and features a compact design with a diameter of 80 mm and a height of 36 mm. The IP30 protection rating safeguards against access to moving parts and against solid foreign objects larger than 2.5 mm, making it suitable for use in enclosed indoor environments.
Applications
The sensor is intended for installation in hollow ceilings or into recessed mounting boxes. It is particularly suitable for rooms with constant usage, such as offices, conference rooms, or corridors, where automatic lighting control based on occupancy and sufficient daylight is beneficial. The detection angles of approximately 94° × 82° and a range of approximately 5 m enable comprehensive coverage of the room. The light measurement range of 0 to 2000 Lux allows precise adjustment of lighting according to daylight conditions. Additionally, the sensor detects ambient temperature in the range of 5 to +60 °C and relative humidity from 0 to 100 %, which is useful for comprehensive room monitoring systems.
Functions and Equipment in Detail
The Intra-Sewi KNX L-Pr features integrated logic gates that enable flexible control. There are 4 AND and 4 OR gates, each with 4 inputs available. Inputs can be used for both switching events and 16 logic inputs in the form of communication objects. The gate outputs can be configured as either 1 bit or 2 x 8 bits, enabling versatile control of loads within the KNX system. The threshold values for presence and light measurement can be set via parameters or communication objects, allowing individual adaptation to specific room conditions. Configuration is performed using the KNX software ETS, which is standard for programming KNX devices.
Technology Explained Simply
The sensor operates in S-Mode, a configuration mode of the KNX system that enables simple and secure parameterization. Communication takes place via the TP1-256 medium, used for data transmission in the KNX bus. The nominal voltage is 30 V DC SELV, ensuring a safe, low-voltage supply. The current consumption is ≤ 10 mA, which is very low and underscores the energy efficiency of the device. The plug terminals for the KNX connection are designed for conductors with a diameter of 0.8 mm, requiring a stripping length of 5 mm. After a bus voltage recovery, it takes approximately 5 seconds for data reception to resume, enabling quick communication restoration.
Compatibility and Accessories
The sensor is developed for the KNX bus system and can be integrated with other KNX devices within a building automation system. The maximum number of group addresses and assignments is 254 each, allowing flexible integration into larger systems. The communication objects are equipped with 252/122, enabling extensive data processing and transmission. For recessed installation, a mounting ring is included in the delivery scope, as well as pre-mounted terminals for hollow ceiling installation. The installation manual is available in multiple languages (German, English, French, Italian, Spanish), as is the handbook and product file for download.
Installation and Mounting
Installation is carried out either in hollow ceilings or into a recessed mounting box. In hollow ceilings, the sensor is installed directly into the ceiling, with pre-mounted terminals facilitating the connection. For recessed installation, the mounting ring is used and inserted into the box. Installation requires connecting to the KNX bus via the plug terminals. Configuration is performed using the ETS software, where parameters such as light thresholds, logic functions, and group addresses are set. The ambient temperature should be between 5 and +45 °C, and the humidity (non-condensing) between 5 and 95 %. The storage temperature is 25 to +70 °C.
Operational Advantages
The Intra-Sewi KNX L-Pr enables automated, energy-saving lighting control that adapts to actual room usage. The combination of presence detection and light measurement reduces unnecessary energy consumption, as lighting is switched off only when no one is present and sufficient daylight is available. The integrated logic gates allow for complex control logic beyond standard functions. The low current consumption and safe low-voltage supply enhance operational safety. The flexible configuration via ETS allows adaptation to different requirements and system environments. The measurement of temperature and humidity extends the sensor’s functionality beyond basic lighting control, making it suitable for comprehensive building automation systems.