Further information for Dold 0070148 RN5897.12/300/61 AC/DC24-60V insulation monitor 10k-250k
Technical data
Approvals
UL
Classification
For mobile power generators
Enclosure design
Distribution board
IMD type
AC, AC/DC, DC
Nominal voltage IT system
AC 0 - 230 V, DC 0 - 230 V
Response value
10 - 250 kΩ
Response value type
Adjustable
Width
52,5 mm
Type
RN 5897/300
Earth fault indicator
Variant
Alarm value
10 - 250 kOhm
Auxiliary voltage
AC/DC 24 - 60 V
Contact equipping
2 x 1 changeover contact
Prewarning value
20 kOhm - 1 MOhm
Approvals and Markings
UL-listed C/US, CCC
The insulation monitor RN5897.12/300/61 AC/DC24-60V from Dold is a device of the VARIMETER IMD family for monitoring insulation quality in IT systems. It is designed for use in ungrounded AC, DC, and mixed AC/DC networks up to a maximum of 300 V and serves for early detection of insulation faults to ensure preventive fire and system protection. The device is specifically designed for mobile power generators in accordance with DIN VDE 0100-551 and meets the requirements of standard IEC/EN 61557-8 for insulation monitoring devices.
Applications
The insulation monitor is suitable for monitoring networks in various application areas, including UPS systems, networks with frequency converters, battery networks, DC drives, hybrid and battery-powered vehicles, as well as mobile power generators. It is universally applicable in systems that do not have direct earthing and enables continuous monitoring of insulation resistances, even when the network is de-energized.
Functions and equipment in detail
The device features two independently adjustable trip thresholds, which can be used for pre-alarm and alarm functions. The adjustment range for the pre-alarm value is between 20 kΩ and 1 MΩ, and for the alarm value between 10 kΩ and 250 kΩ. Adjustment is performed via three rotary switches on the front of the device, enabling user-friendly parameterization. The operating states are visualized via a multicolored device status LED, which indicates the current state of the device.
Technology explained simply
The insulation monitor measures the insulation resistance between the test terminals L(+) and L(-) as well as the protective earth terminals PE1 and PE2. An active measurement process with alternating polarity is carried out to detect symmetrical and asymmetrical insulation faults. The measurement is also performed when the network is de-energized, enabling continuous monitoring. The auxiliary voltage is supplied via terminals A1(+) and A2 and can be in the range AC/DC 24–60 V. The device features an automatic and manual self-test, which takes approximately 12 seconds after switching on the auxiliary voltage.
Compatibility and accessories
The device is designed for network leakage capacitances up to 30 μF and does not require an additional pre-stage device. The connection monitoring for the test circuit L(+) / L(-) is switchable off, while monitoring of the protective earth terminals PE1 / PE2 cannot be deactivated. An external control input (X1, X2) allows connection of a combined test/reset button. The contact configuration includes two 1-changeover contacts, used for the pre-alarm and alarm signals.
Mounting and installation
The insulation monitor is designed as an installation distributor and has a width of 52.5 mm, making it suitable for standard control panels. The terminals L(+) and L(-) are connected directly to the network to be monitored, while PE1 and PE2 must be connected to the protective earth system via separate conductors. The network type (AC, DC, 3NAC) is set via a rotary switch. The tamper-proof transparent cover protects the device against unauthorized manipulation.
Advantages in operation
With separate trip thresholds for pre-alarm and alarm, the operator can respond early to developing insulation degradation before a critical condition is reached. Alarm memory is selectable, so that an alarm remains stored even after the fault has cleared. Simple operation via rotary switches and visual indication via the LED facilitate maintenance and diagnosis. The device is designed for mobile applications and meets the requirements for use in mobile power generators.
Approvals and markings
The device is UL-listed C/US and carries the CCC mark. It complies with the requirements of standard IEC/EN 61557-8 and is suitable for use in IT systems with nominal voltages up to AC 230 V and DC 230 V. The auxiliary voltage can be in the range AC/DC 24–60 V, enabling flexible integration into various power supply systems. The device class is defined for mobile power generators, ensuring specific application safety.