Dold 0070016, EAN: 4030641700164

Dold 0070016 RN5897.12/060/61 AC/DC24-60V insulation monitor 1k-250k

Dold 0070016 RN5897.12/060/61 AC/DC24-60V insulation monitor 1k-250k

Lieske Part No. 1001695
Mfg Part No 0070016
EAN-Code 4030641700164
Manufacturer Dold
Here only 632,67 EUR
752,88 EUR incl. VAT

Further information for Dold 0070016 RN5897.12/060/61 AC/DC24-60V insulation monitor 1k-250k

Technical data
ApprovalsDNV, UL
Enclosure designDistribution board
IMD typeAC, AC/DC, DC
Nominal voltage IT systemAC 0 - 230 V, AC 0 - 1000 (Coupling device) V, DC 0 - 230 V, DC 0 - 1500 (Coupling device) V
Response value1 - 250 kΩ
Response value typeAdjustable
Width52,5 mm
TypeRN 5897/010
Earth fault indicatorYes
Variant
Alarm value1 - 250 kOhm
Auxiliary voltageAC/DC 24 - 60 V
Contact equipping2 x 1 changeover contact
Prewarning value20 kOhm - 2 MOhm
Approvals and MarkingsUL-listed C/US, CCC
VariantWith measuring stop function
The insulation monitor RN5897.12/060/61 AC/DC24-60V from Dold is a device of the VARIMETER IMD family for monitoring insulation in IT systems. It is designed for continuous measurement of insulation resistance between the network conductors L(+) and L(-) as well as the protective conductor PE1/PE2, in order to detect earth faults early. The device is designed for use in ungrounded AC, DC, and mixed AC/DC networks, with maximum rated voltages of AC 230 V and DC 230 V. When used with an external pre-stage device, higher voltages can be monitored, with pre-stage devices RL 5898, RP 5898, and RR 5898 intended for different voltage ranges. The auxiliary voltage is AC/DC 24 to 60 V, and the device can also monitor when the network is de-energized.

Applications

The insulation monitor is universally applicable in various application areas, including UPS systems, networks with frequency converters, battery networks, DC drives, hybrid and battery-powered vehicles, as well as mobile power generators. It is designed for network capacitances up to 1000 μF and offers an optimized response time at high capacitances. Monitoring is carried out in accordance with IEC/EN 61557-8, ensuring a standardized and reliable measurement method.

Functions and Equipment in Detail

The device features two independently adjustable threshold settings: a warning threshold in the range of 20 kΩ to 2 MΩ and an alarm threshold from 1 kΩ to 250 kΩ. These settings are adjusted via two rotary switches on the front of the device. The display is a multi-colored illuminated screen showing the current insulation resistance, device status, and parameterization options. Monitoring of the measurement circuit L(+)/L(-) for wire break is switchable off, while monitoring of the protective conductor connection PE1/PE2 for wire break is not switchable off. A trigger output enables connection to an insulation fault detection system.

Technology Explained Simply

Insulation monitoring is performed by continuously measuring the resistance between the network conductors and the protective conductor. When the set thresholds are undershot, an alarm is triggered. Measurement can also be performed when the network is de-energized, enabling continuous monitoring even when idle. Monitoring of the measurement circuit for wire break ensures that a broken measurement circuit is detected to avoid false alarms. The tamper-proof transparent cover protects the device against unauthorized manipulation.

Compatibility and Accessories

The device can be combined with external pre-stage devices RL 5898, RP 5898, and RR 5898 to monitor higher rated voltages. RL 5898 is suitable for voltages up to AC 400 V / DC 500 V, RP 5898 for AC 690 V / DC 1000 V, and RR 5898 for AC 1000 V / DC 1500 V. Combining with these pre-stage devices extends the application range of the insulation monitor.

Mounting and Installation

The insulation monitor is designed as an installation distributor with a width of 52.5 mm. Power supply is via terminals A1(+) / A2 with auxiliary voltage AC/DC 24 to 60 V. After switching on the auxiliary voltage, an internal self-test runs, lasting approximately 12 seconds. Afterward, insulation resistance measurement begins. Connection examples and maximum voltages are described in the data sheet.

Operational Advantages

The insulation monitor provides preventive fire and system protection through early detection of insulation faults. Selective earth fault detection according to L+ and L- enables quick fault localization. Simple adjustment of thresholds and parameters via rotary switches and menu navigation facilitates commissioning. Alarm storage is selectable, and an external control input allows connection of a combined test/reset button. The measurement stop function is integrated to interrupt the measurement selectively.

Approvals and Markings

The device is UL-listed C/US and CCC-certified. Additionally, it has approvals according to DNV and UL, confirming its suitability for use in various industries and regions. Compliance with standards IEC/EN 61557-8 and the approvals ensure safe and reliable operation.

Enclosure Design and Mounting

The device is designed as an installation distributor with a width of 52.5 mm. The tamper-proof transparent cover protects the device against manipulation. Mounting is in standard distributor boxes, with connection terminals for auxiliary voltage and measurement circuits clearly labeled.

Functions for Safety and Reliability

The insulation monitor features an automatic and manual device self-test to check functionality. Monitoring of the measurement circuit for wire break ensures detection of a broken measurement circuit. Monitoring of the protective conductor connection PE1/PE2 for wire break is not switchable off to ensure continuous monitoring of the protective conductor. Alarm storage is selectable to document alarm history.

Application-Specific Features

The device is suitable for use in IT systems with high network capacitances. Setting the maximum network capacitance allows for shortening the response time. The operating or standby current principle for alarm relays is adjustable to adapt the alarm function to requirements. The multi-colored display facilitates interpretation of the device status.