Further information for Dold 0070015 RN5897.12/011/61 AC/DC100-230V insulation monitor 1K-2M
Technical data
Approvals
DNV, UL
Bus interface
Modbus RTU
Enclosure design
Distribution board
IMD type
AC, AC/DC, DC
Nominal voltage IT system
AC 0 - 230 V, AC 0 - 1000 (Coupling device) V, DC 0 - 230 V, DC 0 - 1500 (Coupling device) V
Response value
1 - 2000 kΩ
Response value type
Adjustable
Width
52,5 mm
Type
RN 5897/011
Earth fault indicator
Variant
Alarm value
1 kOhm - 2 MOhm
Auxiliary voltage
AC/DC 100 - 230 V
Contact equipping
2 x 1 changeover contact
Prewarning value
1 kOhm - 2 MOhm
Approvals and Markings
UL-listed C/US, DNV
The insulation monitor RN5897.12/011/61 AC/DC100-230V from Dold is a device for monitoring insulation in IT systems, particularly in ungrounded AC, DC, and mixed AC/DC networks. The device belongs to the VARIMETER IMD family and is used for continuous monitoring of the insulation resistance between the line conductors L(+) and L(-) as well as the protective conductor PE1/PE2. It is suitable for use in industrial plants, UPS systems, networks with frequency converters, battery networks, DC drives, hybrid and battery-powered vehicles, as well as mobile power generators. The function is based on insulation monitoring according to IEC/EN 61557-8, with the trip threshold adjustable in the range of 1 to 2000 kΩ. Adjustment is performed via two rotary switches on the device front, allowing two independent trip thresholds for pre-alarm and alarm to be defined. The adjustment range for both values is between 1 kΩ and 2 MΩ.
Applications
The device is universally applicable in IT systems with nominal voltages up to AC 250 V or DC 300 V. When used with an external pre-stage device (e.g. RL 5898, RP 5898 or RR 5898), the nominal voltage can be extended to AC 1000 V or DC 1500 V. Monitoring also occurs when the network is de-energized, ensuring continuous safety function. The maximum network capacitance is 1000 μF, with optimized response time at high capacitances. Measurement takes place in the measuring circuit between L(+) / L(-) and PE1/PE2, with integrated wire break monitoring for the measuring circuit (switchable) and for the protective conductor PE1/PE2 (non-switchable).
Functions and Equipment in Detail
The insulation monitor features two galvanically isolated 1-changeover contacts, each used for pre-alarm and alarm. Indication is provided via a multi-coloured illuminated display, showing the current insulation resistance, device status and parameter settings. Operation is performed via the rotary switches and menu navigation on the display. Additionally, an external control input is available for a combined test/reset button. Alarm memory is selectable, and an automatic and manual device self-test is integrated. The tamper-proof transparent cover protects the device against unauthorized manipulation.
Technology Explained Simply
Monitoring is performed via a measuring circuit that measures the insulation resistance between the network conductors and the protective conductor. The trip thresholds are adjustable, enabling early warning (pre-alarm) when insulation resistance decreases and an alarm at critical values. Galvanic isolation of the contacts ensures safe signal transmission. The Modbus RTU interface enables remote reading and parameterization of all measured values, device states and parameters. The auxiliary voltage is supplied via terminals A1(+) / A2 with AC/DC 100–230 V. The width is 52.5 mm, allowing installation in standard installation distributors.
Compatibility and Accessories
The device is compatible with external pre-stage devices of types RL 5898, RP 5898 and RR 5898, which extend the system’s nominal voltage. The Modbus RTU interface enables integration into higher-level control and monitoring systems. A trigger output for insulation fault detection systems is also available to support fault localization.
Mounting and Installation
Mounting is performed in an installation distributor. The width of 52.5 mm corresponds to the standard for DIN rail mounting. The auxiliary voltage is connected via terminals A1(+) / A2. Network connections are made via terminals L(+) / L(-) and PE1/PE2. The device front is equipped with rotary switches and a display for parameterization and indication. The tamper-proof cover is sealed after commissioning to prevent manipulation.
Operational Advantages
The insulation monitor provides preventive fire and plant protection through early detection of insulation faults. Selective earth fault detection according to L+ and L- enables quick fault localization. Galvanically isolated contacts and the Modbus interface increase reliability and integration into existing systems. Adjustable trip thresholds and monitoring even when the network is de-energized ensure flexible and safe use in various application scenarios. The certifications UL-listed C/US and DNV confirm suitability for use in respective markets.
Approvals and Markings
The device is certified with UL-listed C/US and DNV, confirming compliance with respective safety and quality requirements. Monitoring is performed according to IEC/EN 61557-8, ensuring application in industrial and technical installations.