Dold 0070013 RN5897.12/010/61 DC12-24V insulation monitor 1k-250k

Dold 0070013 RN5897.12/010/61 DC12-24V insulation monitor 1k-250k

Lieske Part No. 1001693
Mfg Part No 0070013
EAN-Code 4030641700133
Manufacturer Dold
Here only 632,67 EUR
752,88 EUR incl. VAT

Further information for Dold 0070013 RN5897.12/010/61 DC12-24V insulation monitor 1k-250k

Technical data
ApprovalsDNV, UL
Enclosure designDistribution board
IMD typeAC, AC/DC, DC
Nominal voltage IT systemAC 0 - 230 V, AC 0 - 1000 (Coupling device) V, DC 0 - 230 V, DC 0 - 1500 (Coupling device) V
Response value1 - 250 kΩ
Response value typeAdjustable
Width52,5 mm
TypeRN 5897/010
Earth fault indicatorYes
Variant
Alarm value1 - 250 kOhm
Auxiliary voltageDC 12 - 24 V
Contact equipping2 x 1 changeover contact
Prewarning value20 kOhm - 2 MOhm
Approvals and MarkingsUL-listed C/US, CCC
The insulation monitor RN5897.12/010/61 DC12-24V from Dold is a device of the VARIMETER IMD family for monitoring insulation in IT systems. It is designed for continuous monitoring of ungrounded AC, DC, and mixed AC/DC networks, particularly in installations with high network capacitance. The device is intended for use in industrial, medical, and mobile applications, where early detection of insulation faults is critical to prevent fires and system outages. The auxiliary voltage is supplied via DC 12–24 V, and the device is mounted in installation distributors with a module width of 52.5 mm.

Applications

The insulation monitor is universally applicable in various systems, including UPS systems, networks with frequency converters, battery networks, DC drives, hybrid and battery-powered vehicles, as well as mobile power generators. It monitors both AC and DC networks up to a maximum of 250 V AC or 300 V DC. The use of an external pre-stage device (e.g. RL 5898, RP 5898 or RR 5898) can extend the maximum rated voltages to AC 1000 V or DC 1500 V. Monitoring also occurs when the network is de-energized, increasing reliability in critical operating conditions.

Functions and Equipment in Detail

The device features two independently adjustable threshold settings: a pre-alarm level ranging from 20 kΩ to 2 MΩ and an alarm level from 1 kΩ to 250 kΩ. These values can be easily and user-friendly adjusted via two rotary switches on the front of the device. Display is provided by a multi-colored illuminated screen showing the current insulation resistance, device status, and parameterization options. Selective earth fault detection for L+ and L– enables quick fault localization. Additionally, an integrated trigger output is available for insulation fault detection systems.

Technology Explained Simply

Insulation monitoring is performed according to the standard IEC/EN 61557-8. The device detects both symmetrical and asymmetrical insulation faults. Measurement takes place in the measuring circuit between terminals L(+) / L(–) and PE1 / PE2. The response time is optimized by setting the maximum network capacitance (up to 1000 μF), which is particularly important for systems with high capacitance. Wire break monitoring in the measuring circuit is switchable off, while monitoring of the protective conductor connections PE1/PE2 is not switchable off. The operating mode of the alarm relay (active or rest current principle) is adjustable.

Compatibility and Accessories

The insulation monitor can be operated both with and without an external pre-stage device. Combining it with pre-stage devices RL 5898, RP 5898 or RR 5898 extends the maximum rated voltages. The auxiliary voltage is supplied via terminals A1(+) / A2. An external control input allows the use of a combined test/reset button. The tamper-proof transparent cover protects the device against unauthorized manipulation.

Mounting and Installation

The device is mounted in installation distributors and requires a module width of 52.5 mm. The connection terminals are clearly labeled, with terminals L(+) and L(–) connected directly to the network to be monitored. When using a pre-stage device, the connection is made via the corresponding terminals. After switching on the auxiliary voltage, the device performs an internal self-test lasting approximately 12 seconds, which is displayed on the screen.

Advantages in Operation

The insulation monitor provides preventive fire and system protection through early detection of insulation faults. The two-stage alarm function (pre-alarm and alarm) allows for differentiated response to decreasing insulation values. Alarm memory is selectable, and automatic and manual device self-tests ensure operational reliability. The clear display and simple parameterization reduce maintenance time and increase operational safety. Certifications UL-listed C/US, CCC, DNV, and UL confirm suitability for use in various markets.