Technical data
ApprovalsUL-Recognized
Bus interfaceModbus RTU
ClassificationFor DC charging stations
Enclosure designDistribution board
IMD typeAC, AC/DC, DC
Nominal voltage IT systemAC 0 - 230 V, AC 0 - 690 (Coupling device) V, DC 0 - 230 V, DC 0 - 1000 (Coupling device) V
Response value1 - 500 kΩ
Response value typeAdjustable
Width52,5 mm
TypeRN 5893/100
Earth fault indicatorYes
Variant
Alarm value1 - 500 kOhm
Auxiliary voltageAC/DC 100 - 240 V
Contact equipping2 x 1 changeover contact
Prewarning value1 - 500 kOhm
Approvals and MarkingsUL-rec. C/US
VariantFür Netzableitkapazitäten bis 5 µF
The insulation monitor RN5893.12/100/61 from Dold is a device for monitoring insulation quality in IT systems, particularly in ungrounded AC, DC, and mixed AC/DC networks. It belongs to the VARIMETER IMD family and is specifically designed for use in DC charging stations for electric vehicles operating according to IEC/EN 61851-23:2014/AC:2016-06. The device monitors insulation in accordance with IEC/EN 61557-8 and is designed for network capacitances up to 5 µF. The auxiliary voltage is supplied via AC/DC 100–240 V, making it flexible for use in various power supply networks.

Applications

The insulation monitor is primarily intended for DC charging stations with voltages up to DC 1000 V. The use of an external pre-stage device RP 5898 enables monitoring of nominal voltages up to AC 690 V or DC 1000 V. It is also suitable for UPS systems, networks with frequency converters, battery networks, DC drives, hybrid and battery-powered vehicles, as well as mobile power generators. The application is in ungrounded systems, with a maximum operating voltage of AC 250 V or DC 300 V if no pre-stage device is used.

Functions and Equipment in Detail

The device features two independently adjustable trip thresholds, which can be used as a pre-alarm value and an alarm value. The adjustment range for both values is between 1 kΩ and 500 kΩ. Monitoring is performed via two configurable changeover contacts, each electrically isolated. These can be configured for various functions such as insulation fault alarm, pre-alarm, fault on DC+/DC−, or device fault. The operating mode of the alarm relays (active or passive current principle) is also adjustable.

Technology Explained Simply

Insulation monitoring is performed by an optimized measurement of insulation resistance, which functions reliably even with voltage fluctuations in the network. The measurement is based on evaluation of the network voltage. The response time of the device is a maximum of 1 second. A multicolored device status LED provides user-friendly visualization of the operating state. A manual self-test is available, and an automatic self-test can also be activated. Alarm storage is selectable, and the measurement circuits L(+) and L(−) as well as the protective earth connections PE1/PE2 are monitored for wire breakage (PE monitoring cannot be disabled). Monitoring also occurs when the network is de-energized.

Compatibility and Accessories

The device is equipped with a galvanically isolated Modbus RTU interface, via which all measured values, device states, and parameters can be read and configured. Configuration via Modbus enables remote control and monitoring. The connection option for an external pre-stage device RP 5898 extends the application range to higher voltages. The width is 52.5 mm, allowing installation in standard installation distributors.

Mounting and Installation

Power supply is via terminals A1(+) and A2 with auxiliary voltage AC/DC 100–240 V. After switching on the auxiliary voltage, the device performs an internal self-test. Mounting is in an installation distributor, where the tamper-proof transparent cover protects against unauthorized manipulation. An external control input allows connection of a combined test/reset button, with the additional option to pause the measurement function.

Advantages in Operation

The insulation monitor provides preventive fire and system protection through early detection of symmetrical and asymmetrical insulation faults. The adjustment of trip thresholds is simple via Modbus, facilitating integration into higher-level control systems. The extended operating temperature range of −40 °C to +70 °C makes the device suitable for demanding environments. The UL-Recognized (C/US) certification ensures use in corresponding markets.