Further information for Dold 0069632 insulation monitor 1k-250k DC24V
Technical data
Approvals
UL
Classification
For photovoltaic systems
Enclosure design
Switch cabinet
IMD type
AC, AC/DC, DC
Nominal voltage IT system
AC 0 - 1000 V, DC 0 - 1000 V
Response value
1 - 250 kΩ
Response value type
Adjustable
Width
90 mm
Type
LK 5895
Earth fault indicator
Variant
Alarm value
1 - 250 kOhm
Auxiliary voltage
DC 24 V
Contact equipping
2 x 1 changeover contact
Prewarning value
1 - 250 kOhm
Approvals and Markings
UL-listed C/US, UKCA
Variant
With wire-break detection at L(+)/L(-). Without analog output. With adapted measurement algorithm
The insulation monitor LK 5895 of the VARIMETER IMD family from Dold is a device for monitoring insulation quality in IT systems, particularly in ungrounded AC, DC, and mixed AC/DC networks with a nominal voltage up to 1000 V. It is designed for early detection of insulation faults to ensure preventive fire and system protection. The device is specifically designed for use in photovoltaic systems, including those with thin-film technology, as well as in battery networks, UPS systems, and networks with frequency converters. Insulation monitoring is performed in accordance with the standard IEC/EN 61557-8, ensuring the reliability and safety of the measurement.
Applications
The LK 5895 is universally applicable in various applications, including photovoltaic systems, hybrid and battery vehicles, networks with DC drives, and systems with high network capacitance up to 3000 μF. Monitoring is also possible in de-energized networks, making it particularly suitable for installations with intermittent power supply. Selective earth fault detection on L+ and L– enables rapid fault localization, reducing maintenance and downtime.
Functions and Equipment in Detail
The device features two adjustable threshold values: the alarm threshold in the range of 1 kΩ to 250 kΩ and the pre-alarm threshold, which can also be set in the range of 1 kΩ to 250 kΩ. Adjustment is performed via two ratchet rotary switches on the front of the device, which can be operated with a screwdriver. This ensures simple and clear operation. Measured values and device status are displayed via an LED bar, visually indicating the current insulation resistance. Additionally, a green LED labeled PWR lights up when supplied with DC auxiliary voltage.
Technology Explained Simply
The monitoring technology is based on an adapted measurement algorithm that reduces response time in networks with high capacitance. The measurement circuits can be deactivated via control terminals, for example, during network coupling. Measurement circuit monitoring includes wire break detection on L(+) and L(–), enabling detection of interruptions in the measurement circuit. The output relays operate on either the energized or de-energized principle, with selection possible depending on the application. An automatic and manual device self-test ensures functional verification of the device.
Compatibility and Accessories
The device is designed for IT systems with AC and DC voltages up to 1000 V. It detects both symmetrical and asymmetrical insulation faults. The contact configuration includes one changeover contact each for pre-alarm and alarm. External test and reset buttons can be connected to allow external verification of functionality or to reset the alarm state. Alarm memory is selectable, so an alarm can be retained even after the fault has disappeared.
Mounting and Installation
The device is designed for installation in enclosures and has a width of 90 mm. Connections are clearly labeled: A1+ and A2 for DC auxiliary voltage (24 V), L(+) and L(–) for the measurement circuit, KE and PE for the protective conductor, and control terminals G, R, T, and HM for configuring the operating behavior. Installation is done via screw terminals, ensuring a secure connection.
Operational Advantages
The LK 5895 offers an optimized measurement time, typically shorter than with conventional methods. Measurement is performed without an additional pre-stage device, simplifying installation. The visual display of insulation resistance via the LED bar enables quick visual inspection of the system status. The combination of simple operation, high reliability, and universal applicability makes the device a robust solution for insulation monitoring in modern electrical systems.
Approvals and Markings
The device is UL-listed C/US and UKCA-certified, confirming compliance with relevant safety and quality standards in the USA and the United Kingdom. These approvals ensure suitability for use in corresponding markets and applications.
Core Functions at a Glance
Insulation monitoring according to IEC/EN 61557-8
Adjustable thresholds for alarm and pre-alarm
LED display for insulation resistance and device status
Wire break detection on L(+) and L(–)
Universal applicability in AC, DC, and AC/DC networks up to 1000 V
Approvals UL-listed C/US, UKCA
The technical features such as auxiliary voltage (DC 24 V), contact configuration (2 x 1 changeover contact), and adjustment ranges for pre-alarm and alarm thresholds (20 kΩ to 2 MΩ and 1 kΩ to 250 kΩ respectively) are integrated into the device and correspond to the manufacturer’s specifications. The device class is specified for photovoltaic systems, although use in other IT systems is also possible.