Dold 0069519, EAN: 4030641695194

Dold 0069519 RL9405/100 3/N AC80-230V 50Hz energy meter

Dold 0069519 RL9405/100 3/N AC80-230V 50Hz energy meter

Lieske Part No. 1000977
Mfg Part No 0069519
EAN-Code 4030641695194
Manufacturer Dold
Here only 360,52 EUR
429,02 EUR incl. VAT

Further information for Dold 0069519 RL9405/100 3/N AC80-230V 50Hz energy meter

Technical data
1- / 3-phase3
Auxiliary voltageWithout
Bus interfaceModbus RTU
Enclosure designDistribution board
Measuring range max.230 V
Standard measuring range3/N AC 80 - 230 V
Width35 mm
TypeRL 9405
Variant
Nominal voltage3/N AC 80 - 230 V / 140 - 400 V 50 Hz
VariantSecondary rated current of the current transformers 1 A
The energy meter RL9405/100 from the VARIMETER PRO series by Dold is a 3-phase measuring device for networks with neutral conductor (3/N), designed for operating voltages of AC 80–230 V and 140–400 V at a nominal frequency of 50 Hz. It is used for continuous acquisition and evaluation of electrical parameters as well as for measuring energy consumption in low-voltage networks. The measured values are read out via a galvanically isolated Modbus RTU interface, enabling integration into higher-level control and monitoring systems. The device is designed for use in enclosures and installation small distributors and features a compact width of 35 mm, making it suitable even in confined spaces.

Applications

The energy meter RL9405/100 is intended for measurement in 3-phase networks with neutral conductor, regardless of whether it is an IT-, TN- or TT-system. It is used in industrial and commercial facilities where accurate measurement of voltage, current, power, and energy consumption is required. Measurement is continuous, capturing effective and peak values of phase voltage and phase current, network frequency, power factor, active power, reactive power, apparent power, active energy, reactive energy, and apparent energy. Measurement accuracy is ±0.5 %, sufficient for reliable data acquisition in monitoring and control systems.

Functions and equipment in detail

The device features an integrated memory that stores energy consumption even after power supply is switched off. Current transformer ratios can be set via Modbus, allowing adaptation to market-standard current transformers with secondary rated currents of 100 mA, 1 A, or 5 A, and a secondary rated voltage of 333 mV. Measurement ranges extend up to 1000 A when using external current transformers. The Modbus RTU interface supports baud rates of 9600, 19200, and 38400 bit/s and allows setting the slave address from 1 to 99 directly on the device.

Technology explained simply

The voltage inputs (L1, L2, L3, N) serve both as power supply source and as measurement channels. Current measurement is performed via external current transformers connected to terminals i1, k1, i2, k2, i3, k3. The RS485 interface (terminals GND, A, B) enables communication via Modbus RTU. Galvanic isolation of the interface protects the device and connected equipment from voltage surges. The operating voltage is generated from the measurement voltage of all three phases, allowing the device to operate independently of a separate power supply. The minimum current is 0.05 % of the rated output current multiplied by the current transformer ratio.

Compatibility and accessories

The energy meter RL9405/100 is designed for use with current transformers having a secondary rated current of 1 A. It can be connected to market-standard current transformers, whose winding ratio can be set via Modbus. The Modbus RTU interface enables connection to systems supporting the Modbus protocol. Device indicators consist of a green LED (ON, indicating applied operating voltage) and a yellow LED (BUS, indicating RS485 bus activity).

Mounting and installation

The device is installed in enclosures or installation small distributors. Mounting is done in standard 35 mm width, fitting into typical enclosure modules. Connection terminals are clearly labeled (L1, L2, L3, N for voltage, i1–i3, k1–k3 for current, GND, A, B for RS485). Current transformers must be connected externally, with terminals i1–i3 and k1–k3 assigned to respective phases. The Modbus address and baud rate can be set directly on the device.

Advantages in operation

The compact design with 35 mm width frees up more space in the enclosure. Permanent storage of energy measurement values enables continuous documentation even during power failure. Power supply from the measurement voltage reduces the number of required supply lines. The Modbus RTU interface provides a standardized interface for integration into existing monitoring and control systems. Measurement accuracy of ±0.5 % ensures reliable data for operational monitoring. The device is not intended for billing purposes according to EU Directive 2004/22/EC (MID) and therefore must not be used as an electricity meter for active energy consumption.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/1000977
qrcode für Dold 0069519 RL9405/100 3/N AC80-230V 50Hz energy meter