Dold 0069399, EAN: 4030641693992

Dold 0069399 RN5897.12/321/61 AC/DC24-60V insulation monitor 1k-500k

Dold 0069399 RN5897.12/321/61 AC/DC24-60V insulation monitor 1k-500k

Lieske Part No. 1001703
Mfg Part No 0069399
EAN-Code 4030641693992
Manufacturer Dold
Here only 684,28 EUR
814,29 EUR incl. VAT

Further information for Dold 0069399 RN5897.12/321/61 AC/DC24-60V insulation monitor 1k-500k

Technical data
ApprovalsUL
Bus interfaceModbus RTU
ClassificationFor DC charging stations
Enclosure designDistribution board
IMD typeAC, AC/DC, DC
Nominal voltage IT systemAC 0 - 230 V, AC 0 - 690 (Coupling device) V, DC 0 - 230 V, DC 0 - 1000 (Coupling device) V
Response value1 - 500 kΩ
Response value typeAdjustable
Width52,5 mm
TypeRN 5897/321
Earth fault indicatorYes
Variant
Alarm value1 - 500 kOhm
Auxiliary voltageAC/DC 24 - 60 V
Contact equipping2 x 1 changeover contact
Prewarning value1 - 500 kOhm
Approvals and MarkingsUL-listed C/US
The insulation monitor RN5897.12/321/61 AC/DC24-60V from Dold is a device of the VARIMETER IMD family for monitoring insulation in IT systems. It is designed for use in ungrounded AC, DC, and mixed AC/DC networks and is particularly suitable for DC charging stations for electric vehicles specified according to IEC/EN 61851-23:2014/AC:2016-06. The device monitors insulation even when the network is de-energized and detects both symmetrical and asymmetrical insulation faults. Parameterization is performed via a galvanically isolated Modbus RTU interface, through which all measured values, device statuses, and settings can be read and controlled.

Applications

The insulation monitor is universally applicable in IT systems with rated voltages up to AC 230 V and DC 230 V. With external pre-stage devices RL 5898 or RP 5898, it can be used for higher voltages up to AC 690 V or DC 1000 V. Main application areas include DC charging stations for electric vehicles, UPS systems, networks with frequency converters, battery networks, DC drives, hybrid and battery-powered vehicles, as well as mobile power generators. The devices are designed for network leakage capacitances up to 5 μF.

Functions and Equipment in Detail

The device features two independently adjustable trip thresholds, which can be used for pre-alarm and alarm functions. The adjustment range for both thresholds is between 1 kΩ and 500 kΩ. For each trip threshold, there is a dedicated changeover contact serving as a signaling relay. The relay operation mode (active or rest current principle) is selectable. A multicolored device status LED visually indicates the operating state in a user-friendly manner. An automatic self-test is performed after each full hour of operation, and a manual self-test is also possible. Alarm memory storage is selectable, and the measurement circuits L(+) and L(-) are monitored for wire break (can be disabled). The protective earth connections PE1/PE2 are also monitored for wire break, which cannot be disabled.

Technology Explained Simply

Insulation monitoring is performed according to IEC/EN 61557-8. The device measures the insulation resistance and responds when the set thresholds are undershot. The response time is maximum 1 second. The measurement is optimized even during network voltage fluctuations, as the network voltage is evaluated. The auxiliary voltage can range from AC/DC 24 to 60 V. The device is designed for an extended operating temperature range of -40 °C to +70 °C. The width is 52.5 mm, enabling installation in standard installation distributors. An external control input (X1, X2) allows connection of a combined test/reset button, with the additional option to pause the measurement function. The Modbus RTU interface is galvanically isolated, ensuring secure communication even in electrically noisy environments.

Compatibility and Accessories

The device is compatible with external pre-stage devices RL 5898 (for voltages up to AC 400 V / DC 500 V) and RP 5898 (for voltages up to AC 690 V / DC 1000 V). These extend the application range of the insulation monitor to higher voltages. Connections for the pre-stage device are made via terminals L(+), L(-), VSG1, VSG2. The devices are UL-listed C/US, confirming approval for use in North America.

Mounting and Installation

The insulation monitor is mounted in installation distributors. The width of 52.5 mm corresponds to the standard for DIN rail mounting. Connections are made via terminals: A1(+) and A2 for auxiliary voltage, L(+) and L(-) for the measurement circuit, PE1 and PE2 for protective earth, X1 and X2 for the external control input. Modbus signals are connected via terminals A and B. The tamper-proof transparent cover protects the device against unauthorized manipulation.

Operational Advantages

The device provides preventive fire and system protection through early detection of insulation faults. Setting trip thresholds and parameters is simple via Modbus, enabling centralized control and monitoring. The display of operating states via the multicolored LED simplifies diagnosis. The high operating temperature of up to +70 °C makes the device suitable for demanding environments. The galvanic isolation of the Modbus interface increases safety and immunity to interference. The combination of two adjustable trip thresholds enables a differentiated alarm strategy, e.g., pre-alarm for slight insulation degradation and alarm for critical values.