Further information for Dold 0068220 RR5886 AC/DC85-230V test current generator

Technical data
Bus interfaceModbus RTU, RS-485
Nominal voltage IT systemDC, AC, 3AC 24 - 455 V
Operating modeMaster / Slave
Width105 mm
TypeRR 5886
Variant
Auxiliary voltageAC/DC 85 - 230 V
VariantFor industrial plants
The RR 5886 test current generator from Dold is a device for insulation fault detection in complex, isolated AC/DC networks (IT systems). It is used in conjunction with the insulation fault detector RR 5887 to monitor and locate insulation faults. The device is designed for use in industrial plants and supports a wide voltage range for auxiliary supply of AC/DC 85 to 230 V. The width is 105 mm, enabling integration into standard control panels.

Applications

The RR 5886 is used in installations where high operational reliability and availability of power supply are required. These include industrial plants, shipbuilding, plant engineering, and photovoltaic systems. Insulation fault detection is performed in IT systems with nominal voltages of DC, AC, and 3AC in the range of 24 to 455 V. The application is particularly suited for networks where both alternating and direct current components are present simultaneously.

Functions and Equipment in Detail

The device generates positive and negative test currents used for monitoring DC networks and mixed AC/DC networks. The external current transformers operate independently and are connected to the measurement channels of the insulation fault detector RR 5887, where they are calibrated. The test current output can be manually initiated via a button or externally controlled via terminal connections (Y1, Y2). Shorting terminals Y1-Y2 disables the start/stop button. The test current output depends on the bus mode, which is controlled via the RS-485 bus connection.

Technology Explained Simply

The RR 5886 operates in master/slave mode and enables synchronization of test current evaluation via an RS-485 bus connection. Multiple insulation fault detectors can be connected via this bus, increasing the number of measurement channels. This allows for more precise localization of insulation faults in extensive networks. The Modbus RTU interface is used for controlling insulation fault detection and reading measured insulation fault currents. Status output is provided via an external switching output (terminals G, H). Device indicators include a green LED ON" (when operating voltage is applied), a yellow LED "BUS (RS-485 bus activity), and yellow LEDs for positive and negative test current pulse output.

Compatibility and Accessories

The test current generator RR 5886 is specifically designed for use with the insulation fault detector RR 5887. The interaction between both devices follows DIN EN 61557-9 (VDE 0413-9):2009 and DIN EN 61557-1 (VDE 0413-1). Insulation coordination is performed according to IEC 60664-1. External control via an insulation monitor is possible, facilitating integration into existing monitoring systems.

Mounting and Installation

Mounting is performed in standard control panels with a width of 105 mm. Connections are made via terminals: A1(+), A2 for auxiliary supply (AC/DC), L1(+), L2(-), L3, PE for IT network voltage connections, SH, GND, Rb, B, A, Ra for RS-485 bus connection (galvanically isolated), Y1, Y2 for switching input to control test current, and G, H for switching output for status indication.

Operational Advantages

By enabling early detection and localization of insulation faults, the RR 5886 allows for quick and targeted troubleshooting. The two alarm levels support timely recognition of dangerous insulation conditions. Intuitive operation through automatic calibration and clear adjustment elements reduces operator effort. The universal auxiliary voltage range of AC/DC 85 to 230 V increases flexibility during installation in various plant environments. Network operational safety and high availability are ensured through continuous monitoring and rapid fault localization.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/1002094
qrcode für Dold 0068220 RR5886 AC/DC85-230V test current generator