Dold 0067692 RR5887.12/011 AC/DC85-230V insulation fault detector

Dold 0067692 RR5887.12/011 AC/DC85-230V insulation fault detector

Lieske Part No. 100165
Mfg Part No 0067692
EAN-Code 4030641676926
Manufacturer Dold
Here only 827,77 EUR
985,05 EUR incl. VAT

Further information for Dold 0067692 RR5887.12/011 AC/DC85-230V insulation fault detector

Technical data
Bus interfaceModbus RTU, RS-485
Nominal voltage IT systemDC, AC, 3AC 24 - 455 V
Operating modeSlave
Width105 mm
TypeRR 5887
Failure storageYes
Variant
Auxiliary voltageAC/DC 85 - 230 V
Contact equipping2 changeover contacts
VariantFor rooms for medical purposes. 8 measuring channels
The insulation fault detection device RR5887.12/011 AC/DC85-230V from Dold is a specialized device for monitoring and locating insulation faults in complex, isolated AC/DC networks, i.e. in IT systems. It is used in conjunction with the test current generator RR 5886 and serves for continuous monitoring of insulation quality, particularly in installations used for medical purposes. The RR 5887 device family enables precise fault location by evaluating test currents injected into the network via external current transformers. These current transformers operate independently and are directly connected to the measurement channels of the device, with calibration being automatically performed by the RR 5887.

Applications

The device is intended for use in industrial plants, shipbuilding, plant engineering, and photovoltaic installations. Special emphasis is placed on its use in areas used for medical purposes, where high operational safety and availability of power supply are required. The ability to detect insulation faults early contributes to avoiding failures and ensuring the functionality of critical systems.

Functions and Equipment in Detail

The RR5887.12/011 features 8 measurement channels, each of which can connect an external current transformer. The number of measurement channels can be increased by connecting multiple devices via an RS-485 bus connection, thereby enabling more precise fault location in extensive networks. The device operates in slave mode, meaning it functions within a network of multiple devices under the control of a master. Communication takes place via the RS-485 bus interface, which can optionally also be used for Modbus RTU. This allows integration into existing fieldbus systems and central evaluation of measurement data.

Technology Explained Simply

The operation is based on injecting a test current into the network via the RR 5886, while the RR 5887 evaluates this current. The external current transformers detect the test current at various points in the network and transmit the signals to the measurement channels of the RR 5887. The device recognizes two alarm levels: a pre-alarm when the insulation fault current exceeds 1 mA, and an alarm when the current exceeds 5 mA. These levels enable a step-by-step response to deteriorating insulation conditions. Indication is provided via LEDs – green for operating voltage, yellow for pre-alarm, and red for alarm. A yellow LED labeled BUS indicates activity on the RS-485 connection.

Compatibility and Accessories

The device is specifically designed for use with the test current generator RR 5886 and complies with standards DIN EN 61557-9 (VDE 0413-9):2009 and DIN EN 61557-1 (VDE 0413-1). Insulation coordination is performed according to IEC 60664-1. The nominal voltage of the IT system can be DC, AC, or 3AC in the range of 24 to 455 V. The auxiliary voltage for the device itself is in the range of AC/DC 85 to 230 V. The width is 105 mm, enabling installation in standard control panels.

Mounting and Installation

Installation is carried out via terminal connections. The terminals are designated for auxiliary voltage (A1, A2), current transformers (K1–K4/I1–I4), RS-485 bus (SH, GND, Rb, B, A, Ra), switching output (G, H), and alarm relays (11–14, 21–24). A switching input (X1, X2) allows setting the memory behavior for alarm states, which can be activated via a wire bridge or an external control input with a maximum of 24 V DC. The function is active-low, meaning alarm memory is activated when a low level is applied.

Advantages in Operation

Early detection and localization of insulation faults enable targeted and rapid correction, increasing operational safety. Simple operation via clear adjustment elements and automatic calibration reduces maintenance effort. Fault memory allows documentation of alarm states, which is helpful for tracing malfunctions. The integrated alarm relays (two changeover contacts each for pre-alarm and alarm) enable control of external signaling devices or control systems. Galvanic isolation of the RS-485 bus connection increases system immunity to interference and safety.