Further information for Dold 0067691 RR5887.12/010 AC/DC85-230V insulation fault detector
Technical data
Bus interface
Modbus RTU, RS-485
Nominal voltage IT system
DC, AC, 3AC 24 - 455 V
Operating mode
Slave
Width
105 mm
Type
RR 5887
Failure storage
Variant
Auxiliary voltage
AC/DC 85 - 230 V
Contact equipping
2 changeover contacts
Variant
For rooms for medical purposes. 4 measuring channels
The insulation fault detection device RR 5887.12/010 AC/DC85-230V from Dold is a specialized device for monitoring and locating insulation faults in complex, isolated AC/DC networks, so-called IT systems. It is used in conjunction with the test current generator RR 5886 and is particularly suited for applications where high operational safety and availability of power supply are required, such as in medical rooms. The device features 4 measurement channels, each connected to external current transformers to detect insulation faults in the network. The current transformers operate independently and are calibrated by the device, enabling precise evaluation of fault currents.
Applications
This device is designed for use in industrial plants, shipbuilding, plant engineering, and photovoltaic installations. It is especially relevant in medical facilities, where interruption of power supply can be critical. The ability to detect and locate insulation faults early contributes to avoiding failures and increasing system availability. The application is in IT systems with nominal voltages of DC, AC, and 3AC in the range of 24 to 455 V.
Functions and Equipment in Detail
The device supports two alarm levels: a pre-alarm for insulation fault currents above 1 mA and an alarm for currents above 5 mA. These levels allow for a step-by-step response to deteriorating insulation conditions. Status indication is provided via LED indicators: green LED for operating voltage, yellow LEDs for pre-alarm per channel, red LEDs for alarm per channel, and a yellow BUS-LED for RS-485 bus activity. A summary alarm relay with 2 changeover contacts enables output of pre-alarm and alarm states. A push-button is used for manual reset of alarms as well as for testing and calibration of the current transformers.
Technology Explained Simply
The device operates as a slave, meaning it communicates within a network via an RS-485 bus connection with other devices. The bus interface supports Modbus RTU, enabling integration into existing fieldbus systems. The auxiliary voltage is AC/DC 85 to 230 V, allowing universal adaptation to various power supply networks. The width of 105 mm allows mounting in standard control panels. Fault memory can be activated via a switching input (terminals X1, X2), which can be controlled either by a wire bridge or by an external device with a maximum of 24 V DC. When fault memory is activated, alarm states are retained after an insulation fault detection cycle.
Compatibility and Accessories
The device is specifically designed for use with the test current generator RR 5886, which injects the necessary test currents into the network. The cooperation follows DIN EN 61557-9 (VDE 0413-9):2009 and DIN EN 61557-1 (VDE 0413-1). Insulation coordination is performed according to IEC 60664-1. The number of measurement channels can be extended by linking multiple RR 5887 devices via RS-485, thereby improving fault localization in extensive networks.
Mounting and Installation
Mounting is done in standard control panels with a width of 105 mm. The connection terminals are clearly labeled: A1/A2 for auxiliary voltage, K1 to K4/I1 to I4 for current transformers, SH, GND, Rb, B, A, Ra for RS-485 bus connection, X1/X2 for switching input, G/H for status output, and 11/12/14 as well as 21/22/24 for the alarm relay. Wiring is done according to the circuit diagram in the datasheet.
Advantages in Operation
The combination of automatic balancing function, clear operation, and the ability to store alarm states enables quick and targeted fault correction. Integration into Modbus networks and the scalability of measurement channels through additional devices increase the flexibility and scalability of the system. Operational safety is enhanced by early detection of insulation faults and clear visual indication of fault states.