Further information for Dold 0066451 residual current device type B 0-10s
Technical data
Adjustable measuring ranges
0,01 - 3 A
Approvals
UL
Classification
Type B (AC, DC even and pulsating)
Enclosure design
Distribution board
Type of voltage
AC, DC
Width
52,5 mm
Type
RN 5883
Broken conductor detection
Clear key
Operate delay
Relay contact / output
Test key
Variant
Auxiliary voltage
AC/DC 80 - 230 V
Contact equipping
1 changeover contact for prewarning, 1 changeover contact for alarm
Measuring range
10 - 3000 mA
Time delay
0 - 10 s
Approvals and Markings
UL-listed C/US, CCC
Variant
For current transformer ND5015/024, ND5015/035. Without analogue output
The Dold differential current monitor RN5883.12/61 is a sensitive monitoring protection for earthed networks, designed to detect insulation faults at an early stage. It is rated for operating voltages in the range AC/DC 80–230 V and operates with external current transformers of type ND5015/024 or ND5015/035. The device detects differential currents with both DC and AC components and is therefore classified as Type B, enabling detection of DC currents, both smooth and pulsating. Unlike residual current circuit breakers, the RN5883 does not automatically switch off upon fault detection, but instead signals the fault via optical indicators and relay contacts, allowing for targeted maintenance.
Applications
This differential current monitor is intended for use in industrial and technical installations, particularly in systems with mixed AC/DC networks. It serves to detect insulation faults early, which could otherwise lead to fire or equipment damage. The device is used in installation distributors, with a width of 52.5 mm allowing integration into standard control panels. The devices are specified according to IEC/EN 62020 and VDE 0663, ensuring compliance with international safety and functional standards.
Functions and Equipment in Detail
The device features four adjustable measurement ranges from 10 mA to 3 A (0.01–3 A), set via rotary switches. The settings are protected against unauthorized changes by a tamper-proof transparent cover. Upon fault detection, a pre-alarm is triggered, signaled via a separate changeover contact and an LED indicator. A second changeover contact is used for alarm notification, also with LED indication. The LED bar displays the current differential current value, enabling visual monitoring of the operating status. A test button allows functional testing, while a reset button is used to clear the indicators after fault resolution.
Technology Explained Simply
The RN5883 detects differential currents indicating insulation faults via an external current transformer. Measurement is performed using either the residual current or operating current principle, with selection depending on the application. The response delay (0–10 s) prevents false alarms caused by short-term disturbances. Wire break detection ensures that a broken measurement circuit is recognized, avoiding misinterpretations. The relay contacts are configured as changeover contacts, allowing them to be used for various control and signaling tasks.
Compatibility and Accessories
The device is specifically designed for use with current transformers ND5015/024 and ND5015/035. It is available without an analog output, enabling use in pure signaling applications. Certifications UL-listed C/US and CCC confirm compliance with respective safety standards in the USA and China. The devices are designed for use in installation distributors, with a width of 52.5 mm enabling standard mounting in control panels.
Mounting and Installation
Mounting is performed in installation distributors. The connection terminals are designed for connection to external current transformers and auxiliary power supply. Settings for measurement range, time delay, and threshold values are adjusted via mechanical rotary switches. The tamper-proof transparent cover protects the settings from unauthorized changes. The devices are designed for use in earthed networks, with auxiliary voltage required in the range AC/DC 80–230 V.
Operational Advantages
The RN5883 enables early fault detection, increasing system availability and avoiding costly downtimes. Visual indication via LED bar and status LEDs provides a quick overview of the operating status. Separate relay contacts for pre-alarm and alarm allow differentiated responses to fault conditions. Wire break detection and test function enhance system reliability. Use in AC/DC networks expands the application range compared to pure AC systems.