| Technical data |
| Approvals | UL |
| Load current up to | 50 A |
| Load voltage up to | AC 480 V |
| Number of poles | 1-pole, 2-pole, 3-pole |
| On/Off Input Control | DC |
| Width | 22,5 mm, 45 mm, 90 mm |
| Type | BF 9250/_ _8 |
| Variant |
| Auxiliary voltage | DC 7 - 32 V |
| Contact equipping | without signal contact |
| Load current | 2 x AC 25 A |
| Load voltage | AC 24 - 480 V |
| Semiconductor output | 2-pole |
| Approvals and Markings | UL-listed C/US |
| Variant | Switching at zero crossing. With high I2t value |
The Dold solid-state contactor BF9250.92/108 is a
2-pole electronic switching device for
frequent and noiseless control of AC loads in industrial and technical applications. It is operated via
DC control voltage in the range of 7 to 32 V and switches loads with a voltage of
AC 24 to 480 V and a load current of
2 x AC 25 A. The switching is
zero-voltage switching, meaning the switching operation occurs at the moment of zero crossing of the alternating voltage to minimize electrical interference and sparking. This feature makes the device particularly suitable for applications requiring high switching quality and low electromagnetic interference.
Applications
The device is designed for use in industrial control systems, automation systems, and plants for
heating, motor, valve, and lighting control. Due to its high switching frequency and noiseless operation, it is especially suitable for installations where mechanical relays or contactors would cause disturbance noises due to their mechanical movements. The
load voltage up to 480 V and the
load current up to 50 A (at 40 °C ambient temperature) enable use in medium to high power requirements.
Functions and equipment in detail
The solid-state contactor features
protection circuitry using varistors, which protects against transient overvoltages and increases the device's lifespan. The
control is digital via DC voltage, allowing integration into modern control systems such as PLCs or SPS systems. The
on and off delay is each ≤ 1 ms plus 1/2 cycle of the mains voltage, with the 1/2 cycle being omitted in the instant-switching variant. The
minimum load current is AC 40 mA, ensuring reliable switching even at low loads.
Technology explained simply
The device operates as a
solid-state contactor, where no moving contacts are present, but electronic semiconductors (usually thyristors or triacs) close and open the current circuit. This eliminates mechanical wear, resulting in high lifespan and reliability. The
zero-voltage switching function reduces electromagnetic compatibility (EMC) and prevents sparking. The
peak blocking voltage is ± 1200 Vp, ensuring high insulation strength against transient voltage peaks. The
power loss is calculated using the formula P = 1,2 [V] x Ieff. [A] / k [W], where k is the form factor (for sinusoidal current, k = 1,11).
Compatibility and accessories
The device is compliant with
IEC/EN 60947-4-2 and IEC/EN 60947-4-3 and carries the
UL-listed C/US approval, enabling use in the USA and Canada. It is available in various
widths (22.5 mm, 45 mm, 90 mm) and can be
clipped onto a DIN rail, enabling easy installation in enclosures. The
load voltage ranges include AC 24–240 V and AC 24–480 V, with a frequency of 50/60 Hz. For protection of the semiconductors,
semiconductor fuses (e.g. cylindrical fuse 10 x 38) are required, which are dimensioned differently depending on the configuration (1-, 2- or 3-pole). The
limit load integral values (I²t) are specified for the 2-pole variant as 1800 A²s at 2 s, enabling high surge current resistance for connection to inductive loads such as motors or transformers.
Mounting and installation
Mounting is done by clipping onto a
DIN rail, with the installation position required to be horizontal. The
ambient temperature is 0 to 40 °C, with current derating required at 40 °C. The maximum device temperature is 60 °C, with current derating varying depending on width and heatsink design. The
storage temperature is between -20 and +80 °C. The
clearance and creepage distances correspond to pollution degree 3 and a rated impulse voltage of 4 kV according to IEC 60664-1.
Advantages in operation
Due to
noiseless switching and
high lifespan without mechanical wear, the device is particularly suitable for applications requiring high operational reliability and low maintenance. The
EMC compliance according to IEC/EN 61000-6-4 and -6-1, as well as protection circuitry using varistors, increases reliability in electrically disturbed environments. The
DIN rail mounting enables quick and flexible installation in existing enclosures. The
zero-voltage switching function reduces load stress and extends the lifespan of motors and heating elements.