Dold 0065120, EAN: 4030641651206

Dold 0065120 MH9300.12PS/022 3AC24-690V AC12A multifunction measuring relay UH=DC24V

Dold 0065120 MH9300.12PS/022 3AC24-690V AC12A multifunction measuring relay UH=DC24V

Lieske Part No. 1001904
Mfg Part No 0065120
EAN-Code 4030641651206
Manufacturer Dold
Here only 409,46 EUR
487,26 EUR incl. VAT

Further information for Dold 0065120 MH9300.12PS/022 3AC24-690V AC12A multifunction measuring relay UH=DC24V

Technical data
1- / 3-phase1, 3
Enclosure designSwitch cabinet
Measuring range max.690 V
Output contacts2 x 1 C/O contacts
Standard measuring range3 AC 24 - 400 V
Width45 mm
TypeMH 9300
Operate delayYes
Variant
Auxiliary voltageDC 24 V
Contact equipping2 x 1 changeover contact
Measuring currentAC 12 A
Measuring voltage3AC 24 - 690 V
Terminal typepluggable terminal blocks with screw terminals
Approvals and MarkingsDNV
The Dold MH9300.12PS/022 is a multifunctional measuring relay of the VARIMETER PRO series, designed for monitoring electrical parameters in industrial installations. It features an auxiliary voltage of DC 24 V and is designed for use in enclosures. The device monitors up to nine different measurement values simultaneously, including voltage, current, frequency, phase angle cos φ, phase sequence, phase failure, asymmetry, as well as active, reactive, and apparent power. Measurement is performed in both single-phase and three-phase networks, with applications in motor loads being particularly suitable due to symmetrical loading. In single-phase operation, terminals L2 and L3 can be bridged, resulting in the display of U instead of U min / U max.

Applications
This measuring relay is suitable for monitoring single- and three-phase electrical loads, emergency power supplies, voltage-dependent switching operations in cases of over- or under-voltage, and for monitoring mobile equipment. It is particularly used in motor protection for phase faults and in transformer protection for unsymmetrical loading. Frequency monitoring is also intended for applications with frequency converters.

Functions and Equipment in Detail
The device features two independent relay outputs, each with a 1-changeover contact. The monitoring functions can be individually parameterized, with each function assignable to one or both relays. The relay function can be switched between operating and resting current principle. The response delay and start-up bypass time ensure that short-term voltage fluctuations after switching on the auxiliary voltage do not lead to false tripping. The adjustable hysteresis of 0.2 to 50 % of the setpoint value allows precise adjustment of switching thresholds. A fault memory documents the last fault conditions, simplifying fault diagnosis on the device.

Technology Explained Simply
Measurement is performed via terminals L1, L2, and L3, with a minimum measurement voltage of 20 V between L1/L2 required to ensure proper operation. The measurement ranges include voltages from 3 AC 24 to 690 V, with the standard measurement range being 3 AC 24 to 400 V. The maximum measurement current is AC 12 A. Display is via an LCD screen showing current measurement values. Status indication is provided by LEDs: green for present auxiliary voltage, red flashing for overload in the current path, and orange for missing measurement or input mode. The terminal type consists of removable terminal blocks with screw terminals, facilitating replacement and maintenance.

Compatibility and Accessories
The device is designed for use in enclosures and has a width of 45 mm. It is available with plug-in connection blocks, which can be equipped with either screw terminals or spring-cage terminals. The auxiliary voltage is DC 24 V, although the series also offers variants with AC 230 V or AC/DC 110–400 V. The DNV certification is relevant for use in specific industrial environments.

Mounting and Installation
Mounting is performed in standard enclosures. The terminals are designed to allow easy and secure connections. Parameterization is done via an intuitive menu structure on the device, enabling setup and diagnosis without additional equipment. The connection terminals are removable, allowing device replacement without complete rewiring.

Advantages in Operation
Simultaneous monitoring of multiple parameters enables early detection of impending failures, supporting preventive maintenance and avoiding costly damage. Reduced wiring and compact design increase installation efficiency. The clear LCD display and differentiated fault messages simplify operational monitoring and fault resolution. Reliability and availability of the system are enhanced through continuous monitoring and rapid response to deviations.