Dold 0065075, EAN: 4030641650759

Dold 0065075 RK9872.11 phase monitor 3/N AC400/230V

Industrial Material > Industrial relays and contactors > Switching units / measuring, control relay

Dold 0065075 RK9872.11 phase monitor 3/N AC400/230V

Lieske Part No. 1338901
Mfg Part No 0065075
EAN-Code 4030641650759
Manufacturer Dold
Here only 120,84 EUR
143,80 EUR incl. VAT

Further information for Dold 0065075 RK9872.11 phase monitor 3/N AC400/230V

Technical data
1- / 3-phase3
Enclosure designDistribution board
Measuring range max.400 V
Output contacts1 C/O contact
Standard measuring range3/N AC 400/230 V
Width17,5 mm
TypeRK 9872
Variant
Contact equipping1 changeover contact
Nominal voltage3/N AC 400 / 230 V
Approvals and MarkingsUKCA
VariantDe-energized on trip. Without time delay. Monitoring of undervoltage, overvoltage and phase sequence
The phase monitor RK9872.11 from Dold is a compact monitoring device for three-phase networks with nominal voltage 3/N AC 400/230 V. It is used for continuous monitoring of undervoltage, overvoltage, and phase sequence in electrical installations, particularly in applications with three-phase motors, overhead cranes, elevators, escalators, pumps, or filling and emptying systems. The device operates on the zero-current principle, in which the output relay is not activated in the event of a fault, ensuring a safe disconnection. The trigger values for undervoltage and overvoltage are fixed and measured against the neutral conductor (N).

Applications

The phase monitor is designed for use in industrial and commercial installations where reliable network monitoring is required. It is particularly suitable for installations where incorrect phase sequence or voltage fluctuations could cause damage to motors or machinery. The width of 17.5 mm allows for space-saving installation in installation distributors.

Functions and equipment in detail

The device monitors the arithmetic mean of the three phase voltages against the neutral conductor. In a fault-free network with correct clockwise phase sequence, the relay switches to the good state. If an incorrect phase sequence (counterclockwise rotation field) is detected, the yellow LED blinks three times, and the output relay remains deactivated. In the event of undervoltage (below 195.5 V) or overvoltage (above 253 V) lasting longer than 50 ms, the relay drops out. The yellow LED blinks once for undervoltage and twice for overvoltage to indicate the type of fault. The green LED lights up when supply voltage is present.

Technology explained simply

The switching thresholds are fixed: undervoltage is detected at 195.5 V, overvoltage at 253 V. The hysteresis is 2.5 %, ensuring stable switching behavior even with minor voltage fluctuations. The response time is under 50 ms, enabling fast fault detection. The measurement frequency is in the range of 45 to 65 Hz, ensuring compatibility with networks with nominal frequencies of 50 and 60 Hz. The device is designed for continuous operation and consumes approximately 6 VA.

Compatibility and accessories

The phase monitor is designed for 3-phase networks with nominal voltage 3/N AC 400/230 V. It can also be used in 1-phase installations with 400 V or 110 V, with corresponding adjusted trigger values (360 V/99 V for undervoltage, 440 V/121 V for overvoltage). The contact configuration includes a changeover contact rated for AC 15 circuits: make contact up to 2 A/AC 230 V, break contact up to 1 A/AC 230 V. The electrical life expectancy is at least 100,000 switching operations at 1 A/AC 230 V, and the mechanical life expectancy is 1,000,000 switching operations.

Mounting and installation

The device is mounted in installation distributors and is designed for mounting in switchboards. Connections are made via inputs L1, L2, L3, and N. Mounting must only be carried out when de-energized. The device display with green and yellow LEDs enables visual monitoring of the operating status. Safety instructions emphasize that faults must only be rectified when the device is switched off and adjustment work must only be carried out by trained personnel.

Advantages in operation

By simultaneously monitoring undervoltage, overvoltage, and phase sequence, the RK9872.11 enables rapid fault localization and preventive maintenance. The space-saving design and integrated LED display reduce installation effort and improve operational monitoring. The device complies with standard IEC/EN 60255-1 and is marked with the UKCA symbol. The overvoltage category III (according to IEC 60664-1) ensures robust operational safety in industrial environments. The operating temperature range is between -25 °C and +60 °C, and the storage temperature up to +70 °C.