The Dold emergency stop module LG5925.48PS/61 AC/DC24V is a safety-relevant switching component for use in industrial plants, particularly for safeguarding machines and protective grilles. It serves for hazard disconnection in emergency stop situations and is suitable for use in heating systems in continuous operation according to EN 50156-1. The device has a width of 22.5 mm and is designed for a nominal voltage of AC/DC 24 V. It is equipped with removable terminal blocks that support both screw terminals and spring-cage terminals, enabling flexible and quick mounting on standard DIN rails.
Applications
This module is used in plants where safe disconnection of machines or fuel supply is required. Examples include monitoring of sliding protective grilles, protective functions of personnel safety devices, and integration into emergency stop circuits. It is also suitable as a protective door monitor, enabling use in machines with movable protective grilles. Application in heating systems is in accordance with EN 50156-1, particularly for disconnection of the entire fuel supply as specified in section 10.5.5.2.
Functions and Equipment in Detail
The device provides contact configuration with 3 NO contacts and 1 NC contact, where up to 4 NO contacts can be used as output contacts. The switching functions can be operated in 1- or 2-channel wiring, enabling redundant safety functions. An integrated cross-connection detection recognizes faults in the emergency stop control circuit, preventing malfunction. Activation is via a single-button or an automatic activation function, which can be set via switch S2. Operating states are visually indicated by LED displays for channel 1, channel 2, and supply voltage.
Technology Explained Simply
The module is designed for use in safety-critical applications and meets requirements for safety integrity. It complies with Performance Level (PL) e and Category 4 according to EN ISO 13849-1, ensuring high safety performance in hazard avoidance. Additionally, it meets the Safety Integrity Level (SIL CL) 3 according to IEC/EN 62061, as well as SIL 3 according to IEC/EN 61508 and IEC/EN 61511, confirming reliability in safety-critical systems. The maximum thermal current is 8 A, defining the contact load capacity. The connection technology allows the use of stranded conductors with 2 x 1.5 mm² with ferrule and plastic sleeve, or solid conductors with 2 x 2.5 mm² in accordance with DIN 46228-1/-2/-3/-4.
Compatibility and Accessories
The module is compatible with various connection technologies, including removable spring-cage terminals, removable screw terminals, and screw terminals. The use of plug-in connection blocks enables quick replacement of the device, simplifying maintenance and repair. It is designed for use in systems with emergency stop functions and can be combined with other components that also meet safety integrity requirements.
Mounting and Installation
Mounting is done on a standard DIN rail. The removable terminal blocks facilitate connection and maintenance. The connection terminals are designed for use with stranded and solid conductors, with exact cross-sections specified in the datasheet. Installation requires adherence to safety instructions and intended use as described in the manufacturer’s datasheet.
Operational Advantages
The integrated cross-connection detection and redundant 2-channel wiring increase system reliability. The LED displays allow for quick visual inspection of operating status. The width of 22.5 mm optimizes space requirements in enclosures. Certifications UL-listed C/US, TÜV, UKCA, and CCC confirm compliance with international safety standards.
Certifications and Markings
The device is certified UL-listed C/US, TÜV, UKCA, and CCC. These certifications confirm compliance with respective safety and quality requirements for use in industrial plants. The certifications are relevant for use in various markets, particularly in Europe and the USA.
Safety Functions
The safety functions include cross-connection detection, redundant 2-channel wiring, and visual indication of operating states via LEDs. These functions ensure that faults in the control circuit are detected and disconnection in case of danger is reliably guaranteed. Compliance with standards EN ISO 13849-1 and IEC/EN 62061 ensures reliability and safety of the module in critical applications.