| Technical data |
| 1- / 2-channel | 1, 2 |
| Approvals | UL |
| Cat. / PL acc. to EN ISO 13849-1 | 4/e |
| Connection | Pluggable cage clamp terminals, Pluggable screw terminals, Screw terminals |
| Output contacts max. | 1 NC contact, 5 NO contacts |
| SIL CL acc. to IEC/EN 62061 | 3 |
| SIL acc. to IEC/EN 62061 | 3 |
| Thermal current Ith max. | 5 A |
| Width | 22,5 mm |
| Type | LG 5929 |
| Variant |
| Contact equipping | 5 NO contacts, 1 NC contact for feedback circuit |
| Nominal voltage | AC/DC 24 V |
| Terminal type | pluggable terminal blocks with screw terminals |
| Approvals and Markings | UL-listed C/US, TÜV, CCC |
| Variant | For 1-channel connections |
The Dold expansion module LG5929.60PS/61 AC/DC24V is a safety-oriented relay module for use in industrial control systems. It is designed for safe contact multiplication and amplification of safety modules, particularly when multiple safety circuits are required beyond what a single module can provide. The device is designed for operation with a nominal voltage of AC/DC 24 V and features forced-guided contacts, ensuring reliable signal transmission even under critical conditions. The module width is 22.5 mm, enabling compact installation in standard control panels.
Applications
This module is intended for use in safety-critical applications, particularly in automation technology, machine control systems, and combustion systems. It complies with the requirements of EN 50156-1, legitimizing its use in combustion control systems. The certifications UL-listed C/US, TÜV, and CCC confirm compliance with international safety and quality standards. It can be operated in conjunction with safety-oriented semiconductor outputs such as BWS or emergency stop switches, facilitating its integration into existing safety architectures.
Functions and Equipment in Detail
The device provides a contact configuration with five normally open contacts (NO) and one normally closed contact (NC) for the feedback circuit. This configuration enables safe monitoring of signal transmission, as the feedback circuit verifies the integrity of the connection. The maximum thermal current rating is 5 A, allowing use with solid conductors up to 2.5 mm² or stranded conductors up to 1.5 mm² with ferrules and plastic collars. The operating status indicator visually signals the current state of the module, simplifying fault diagnosis.
Technology Explained Simply
The forced-guided contacts ensure that the contacts are mechanically synchronized, regardless of electrical or mechanical disturbances. This prevents unintended signal loss and increases system reliability. The connection technology includes removable terminal blocks with screw terminals, enabling quick replacement of the module without tools. Alternatively, spring-cage terminals are available, providing fast and secure connections. The module width of 22.5 mm corresponds to the standard for DIN rail mounting, ensuring universal installation compatibility.
Compatibility and Accessories
The module is suitable for single-channel and dual-channel wiring, allowing flexible use in various safety configurations. It is available with different connection technologies, including removable spring-cage terminals, removable screw terminals, and screw terminals, facilitating adaptation to existing installations. The certifications according to EN ISO 13849-1 (Category 4, PL e) and IEC/EN 62061 (SIL 3) confirm suitability for high-safety applications. Additionally, the module is certified according to EN 61508 (SIL 3), enabling its use in critical industrial environments.
Mounting and Installation
Mounting is performed on a DIN rail, with the module width of 22.5 mm enabling standard installation. The removable terminal blocks can be removed and replaced without tools, simplifying maintenance and module replacement. The connection terminals are designed for solid conductors up to 2.5 mm² or stranded conductors up to 1.5 mm² with ferrules and plastic collars, enabling flexible wiring. The operating status indicator facilitates visual inspection of the operating state during installation and maintenance.
Operational Advantages
The module provides safe and reliable contact multiplication, increasing the number of available safety outputs without compromising safety integrity. The forced-guided contacts and feedback circuit monitoring enhance system reliability. The modular design with removable terminal blocks enables quick replacement, minimizing downtime during maintenance. The certifications according to international standards ensure usability in various markets and application areas.