Dold 0063869, EAN: 4030641638696

Dold 0063869 current relay BA9053/010 AC1,5-15A

Industrial Material > Industrial relays and contactors > Switching units / measuring, control relay

Dold 0063869 current relay BA9053/010 AC1,5-15A

Lieske Part No. 593079
Mfg Part No 0063869
EAN-Code 4030641638696
Manufacturer Dold
Here only 335,41 EUR
399,14 EUR incl. VAT

Further information for Dold 0063869 current relay BA9053/010 AC1,5-15A

Technical data
1- / 3-phase1
Enclosure designSwitch cabinet
Output contacts2 C/O contacts
Width45 mm
TypeBA 9053
Operate delayYes
Variant
Auxiliary voltageAC/DC 24 - 80 V
Contact equipping2 changeover contacts
Measuring rangeAC 1,5 - 15 A
Start up delayWithout
Switching delay0 - 100 s
Approvals and MarkingsUKCA, CCC
VariantOvercurrent relay. Energized on trip. Time delay at response value
The Dold current relay BA9053/010 AC1,5-15A AC/DC24-80V is an overcurrent relay of the VARIMETER series, designed for monitoring single-phase DC and AC power networks. It is used for continuous monitoring of the current consumption of electrical loads, enabling early detection of deviations from the setpoint and thus preventing failures in industrial plants or railway applications. The device setting is adjusted via rotary switches on the front panel, ensuring simple and user-friendly configuration. The relay operates on the operating current principle and switches when the set threshold value is exceeded, with an integrated switching delay of 0 to 100 seconds. This delay activates after exceeding the setpoint and allows for differentiated response to short-term current peaks, such as those during motor start-up, without triggering a false trip signal.

Applications

The relay is suitable for use in industrial plants and railway applications where reliable current monitoring is required. It monitors the arithmetic mean of the rectified measured current and is calibrated for sinusoidal AC currents in RMS value. The galvanic isolation between auxiliary circuit and measuring circuit ensures safe and interference-free signal transmission. The measuring ranges cover AC 1.5 to 15 A, and the devices are equally usable for DC and AC. The maximum measuring frequency is 5 kHz, enabling accurate detection even during rapid signal changes.

Functions and Equipment in Detail

The device features 2 changeover contacts as output contacts, which can be used to control additional switching devices or alarms. The auxiliary voltage is AC/DC 24 to 80 V, allowing flexible integration into existing control systems. Indication is provided via two LEDs: a green LED indicates operational readiness, while a yellow LED signals activation of the output relay. The setting of the pickup and dropout values is done via rotary switches, with the hysteresis depending on the setpoint. The pickup delay is also integrated and ensures stable response to current changes.

Technology Explained Simply

The relay measures the current via an internal measuring resistor (shunt) and compares the measured value with the set threshold. When the setpoint is exceeded, the output contact switches after the switching delay has elapsed. The switching delay can be adjusted between 0 and 100 seconds, allowing adaptation to different requirements. The galvanic isolation between measuring and auxiliary circuit prevents interference and increases safety. The width is 45 mm, enabling compact mounting in enclosures.

Compatibility and Accessories

The relay is designed for use in enclosures and complies with standards IEC/EN 60255-1 and IEC/EN 60947-1. The UKCA and CCC certifications are valid for the respective variant. It can be used both as an overcurrent relay and as an undercurrent relay, with the hysteresis adjusted accordingly for undercurrent applications. The devices are designed for high overload capacity, with maximum permissible currents varying according to the measuring range. The terminal markings include auxiliary voltage (A1, A2), current input (i, k), and the two changeover contacts (11-14, 21-24).

Mounting and Installation

Mounting is done in an enclosure, with the width of 45 mm enabling standard installation. The connection terminals are clearly labeled, ensuring error-free wiring. The threshold values are adjusted via the rotary switches on the front panel, requiring no additional tools. The operating voltage is connected via terminals A1 and A2, while the measured current is supplied via terminals i and k.

Advantages in Operation

Early detection of current anomalies enables preventive maintenance and prevents costly failures. The LED indicators provide quick visual feedback on the operating status. The switching delay reduces false trips caused by short-term current peaks, increasing reliability. Galvanic isolation and high overload capacity ensure robust and safe operation in demanding environments. Compliance with standards IEC/EN 60255-1 and IEC/EN 60947-1 guarantees high quality and compatibility with other devices in the system.