| Technical data |
| Load current up to | 125 A |
| Load voltage up to | AC 600 V |
| Number of poles | 1-pole |
| On/Off Input Control | AC/DC, DC |
| Width | 45 mm |
| Type | PH 9260 |
| Variant |
| Control voltage | DC 4 - 32 V |
| Load current | AC 50 A |
| Load voltage | AC 100 - 240 V |
| Semiconductor output | 1-pole |
| Variant | Switching at voltage maximum. Without heat sink |
The Dold semiconductor relay PH9260.91/020 AC100-240V AC50A is an
AC semiconductor relay / contactor designed for use in industrial applications. It is used for wear-free and noiseless switching of loads such as heaters, motors, valves or lighting systems. The device operates according to the standard
IEC/EN 60947-4-3 and is configured as
peak voltage switching, making it particularly suitable for switching transformers, as it avoids the high inrush current during switching. The control voltage is
DC 4–32 V, while the load voltage is in the range
AC 100–240 V and the load current is
AC 50 A. The width of
45 mm allows for compact mounting on a DIN rail.
Applications
This semiconductor relay is intended for use in machine building and automation technology, particularly in the plastics and rubber industry, packaging machines, soldering systems or in the food industry. The peak voltage switching variant is especially suitable for applications where high inrush currents must be avoided, such as when switching transformers. Zero-voltage switching is standard, with the peak voltage switching variant representing a special configuration for this purpose.
Functions and Features in Detail
The device features
two antiparallel-connected thyristors responsible for the switching function. The
DCB technology (Direct-Copper-Bonding process) ensures excellent heat transfer, increasing thermal load capacity. The
LED status indicator signals the status of the control input. The
box terminals allow for secure and easy connection of wires. The device is delivered
without a heatsink, although an optional heatsink for DIN rail mounting is available.
Technology Explained Simply
Switching in the peak voltage switching variant occurs at the maximum voltage point of the sinusoidal mains voltage, minimizing the inrush current. The blocking voltage is
1200 V or 1600 V, and the insulation voltage is
4000 V, ensuring high electrical safety. The maximum load voltage is
AC 600 V, and the maximum load current is
125 A (AC-51), with the I²t limit value being
18000 A²s. The junction temperature must not exceed
125 °C. The operating temperature range is
–20 °C to 40 °C, and the storage temperature range is
–20 °C to 80 °C.
Compatibility and Accessories
The device is designed for industrial environments and complies with the requirements of the standard
IEC/EN 60947-4-3. An optional
over-temperature protection is available, activated by installing a temperature-limiting switch (e.g. UCHIYA type UP62–100) into a designated pocket on the underside. If the heatsink temperature exceeds the set limit (e.g. 100 °C), the switch opens and protects the device. Additionally, a variant with
reduced electromagnetic emission is available, improving electromagnetic compatibility (EMC).
Mounting and Installation
The device is mounted on a DIN rail. The width of
45 mm allows for compact placement. The box terminals are designed for connecting wires. Mounting requires no additional tools, as the terminals can be connected directly. The touch protection class is
IP20 at the terminals, and the housing is protected to
IP40.
Operational Advantages
The semiconductor relay offers wear-free operation, as there are no mechanical contacts. Switching operations are noiseless, improving the working environment. The high switching capacity (up to 125 A) and robust construction with DCB technology ensure a long service life. The LED indicator allows for easy status monitoring. The peak voltage switching variant reduces the inrush current, increasing the lifespan of both the load and the relay. Compliance with the standard
IEC/EN 60947-4-3 ensures safe and reliable operation in industrial installations.