Dold 0063333, EAN: 4030641633332

Dold 0063333 PH9260.91/020 AC100-240V AC50A semiconductor relay UH=DC4-32V

Dold 0063333 PH9260.91/020 AC100-240V AC50A semiconductor relay UH=DC4-32V

Lieske Part No. 100137
Mfg Part No 0063333
EAN-Code 4030641633332
Manufacturer Dold
Here only 54,02 EUR
64,28 EUR incl. VAT

Further information for Dold 0063333 PH9260.91/020 AC100-240V AC50A semiconductor relay UH=DC4-32V

Technical data
Load current up to125 A
Load voltage up toAC 600 V
Number of poles1-pole
On/Off Input ControlAC/DC, DC
Width45 mm
TypePH 9260
Variant
Control voltageDC 4 - 32 V
Load currentAC 50 A
Load voltageAC 100 - 240 V
Semiconductor output1-pole
VariantSwitching at voltage maximum. Without heat sink
The Dold semiconductor relay PH9260.91/020 AC100-240V AC50A is an AC semiconductor relay / contactor designed for use in industrial applications. It is used for wear-free and noiseless switching of loads such as heaters, motors, valves or lighting systems. The device operates according to the standard IEC/EN 60947-4-3 and is configured as peak voltage switching, making it particularly suitable for switching transformers, as it avoids the high inrush current during switching. The control voltage is DC 4–32 V, while the load voltage is in the range AC 100–240 V and the load current is AC 50 A. The width of 45 mm allows for compact mounting on a DIN rail.

Applications
This semiconductor relay is intended for use in machine building and automation technology, particularly in the plastics and rubber industry, packaging machines, soldering systems or in the food industry. The peak voltage switching variant is especially suitable for applications where high inrush currents must be avoided, such as when switching transformers. Zero-voltage switching is standard, with the peak voltage switching variant representing a special configuration for this purpose.

Functions and Features in Detail
The device features two antiparallel-connected thyristors responsible for the switching function. The DCB technology (Direct-Copper-Bonding process) ensures excellent heat transfer, increasing thermal load capacity. The LED status indicator signals the status of the control input. The box terminals allow for secure and easy connection of wires. The device is delivered without a heatsink, although an optional heatsink for DIN rail mounting is available.

Technology Explained Simply
Switching in the peak voltage switching variant occurs at the maximum voltage point of the sinusoidal mains voltage, minimizing the inrush current. The blocking voltage is 1200 V or 1600 V, and the insulation voltage is 4000 V, ensuring high electrical safety. The maximum load voltage is AC 600 V, and the maximum load current is 125 A (AC-51), with the I²t limit value being 18000 A²s. The junction temperature must not exceed 125 °C. The operating temperature range is –20 °C to 40 °C, and the storage temperature range is –20 °C to 80 °C.

Compatibility and Accessories
The device is designed for industrial environments and complies with the requirements of the standard IEC/EN 60947-4-3. An optional over-temperature protection is available, activated by installing a temperature-limiting switch (e.g. UCHIYA type UP62–100) into a designated pocket on the underside. If the heatsink temperature exceeds the set limit (e.g. 100 °C), the switch opens and protects the device. Additionally, a variant with reduced electromagnetic emission is available, improving electromagnetic compatibility (EMC).

Mounting and Installation
The device is mounted on a DIN rail. The width of 45 mm allows for compact placement. The box terminals are designed for connecting wires. Mounting requires no additional tools, as the terminals can be connected directly. The touch protection class is IP20 at the terminals, and the housing is protected to IP40.

Operational Advantages
The semiconductor relay offers wear-free operation, as there are no mechanical contacts. Switching operations are noiseless, improving the working environment. The high switching capacity (up to 125 A) and robust construction with DCB technology ensure a long service life. The LED indicator allows for easy status monitoring. The peak voltage switching variant reduces the inrush current, increasing the lifespan of both the load and the relay. Compliance with the standard IEC/EN 60947-4-3 ensures safe and reliable operation in industrial installations.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/100137
qrcode für Dold 0063333 PH9260.91/020 AC100-240V AC50A semiconductor relay UH=DC4-32V