Further information for Dold 0063103 RP 9800.12 voltage/frequency monitor
Technical data
1- / 3-phase
3
Auxiliary voltage
Without
Enclosure design
Distribution board
Output contacts
2 C/O contacts
Width
70 mm
Type
RP 9800
Operate delay
Variant
Contact equipping
2 changeover contacts
Supply voltage
3/N AC 315/182 V
Time delay
90 s
The voltage and frequency monitor RP 9800.12 from Dold is an industrial monitoring regulator for self-generation plants operated on the low-voltage grid. The device ensures safe disconnection of the plant from the public grid in case of unauthorized voltage or frequency values, particularly for plants with a power output exceeding 30 kVA according to VDEW guidelines. It is designed for use in installation distributors and features a width of 70 mm. Monitoring is performed 3-phase against the neutral conductor (N), where voltage values are measured individually on each phase and the maximum value (in case of overvoltage) and minimum value (in case of undervoltage) are evaluated. Frequency measurement is performed 1-phase in phase L1, also referenced to the neutral conductor. The measurement is calibrated to the RMS value, ensuring precise and reliable evaluation.
Applications
This device is primarily designed for monitoring self-generation plants such as combined heat and power plants, photovoltaic systems, or diesel generators connected to the public low-voltage grid. It enables automatic disconnection in case of voltage or frequency deviations to prevent grid damage or hazards. For plants under 30 kVA, it can be used as an alternative to a disconnection point, provided a manual disconnection point is available. The application is in industrial and commercial environments where reliable grid monitoring is required.
Functions and Equipment in Detail
When the set limit values are exceeded or undershot, the relays switch to the rest position, causing the plant to be disconnected from the grid. Reconnection occurs after an adjustable delay of 90 seconds, once the values are again within the permissible range. The limit values are adjusted via detent rotary switches, allowing simple and precise adaptation to specific operating conditions. All set values are simultaneously visible, facilitating control and maintenance. Tamper protection is ensured by a sealable transparent cover.
Technology Explained Simply
Voltage monitoring measures the voltage values of the three phases against the neutral conductor. In case of overvoltage (e.g., above 120% of nominal voltage) or undervoltage (e.g., below 72%), the corresponding relay is triggered. Additionally, an average voltage value over a period of 10 minutes is calculated to detect slow voltage increases that would not be captured by short-term fluctuations. The response delay ensures that short-term fluctuations do not lead to unwanted disconnection.
Compatibility and Accessories
The device is designed for a grid voltage of 3/N AC 315/182 V and requires connection of the neutral conductor for the RP 9800.12 variant. It operates without auxiliary voltage, simplifying installation. Indication is provided via LEDs: a green LED indicates the presence of auxiliary voltage, red LEDs signal voltage or frequency deviations, and yellow LEDs indicate the status of the output relays. Indication of 10-minute average voltage exceedance is shown by flashing of the red LED for voltage. The set values for voltage and frequency deviation are adjustable via rotary switches, with voltage deviation specified as a percentage of nominal voltage (e.g., 108% to 120%) and frequency in Hz (e.g., 50.2 Hz to 52 Hz).
Mounting and Installation
The voltage and frequency monitor is installed in an installation distributor. The width is 70 mm, enabling standard mounting in enclosures. The connection terminals are designed for connecting the three phase conductors and the neutral conductor. For the RP 9800.12 variant, the neutral conductor must be connected. The limit values are adjusted on-site via rotary switches, with the values directly visible. The sealable cover protects against unauthorized changes to the settings.
Advantages in Operation
The high measurement accuracy and separate output relays for voltage and frequency ensure reliable and precise response to grid disturbances. The adjustable reconnection delay of 90 seconds prevents unwanted rapid reconnections. Clear LED indication enables quick error diagnosis. Simple operation via rotary switches and visible set values reduces maintenance effort. The device complies with standards DIN EN 60255-1 and DIN EN 60947-1, ensuring compliance with safety and functional requirements.