| Technical data |
| Enclosure design | Switch cabinet |
| Output contacts | 1 C/O contact, 2 x 1 C/O contacts |
| Time function(s) | Cyclic timer, Fleeting on break, Fleeting on make, Fleeting on make and brake, Impulsgeber, Off-delay, with control signal, On- and Off-delay, On-delay, Pulse extender |
| Width | 22,5 mm |
| Type | MK 7830N |
| Variant |
| Contact equipping | 2 changeover contacts |
| Nominal voltage | AC/DC 24 V + AC 230 V |
| Terminal type | screw terminal fixed |
| Time range | 0,02 s - 9999 h |
| Approvals and Markings | UKCA |
The Dold MK7830N.82 AC/DC24V+AC230V is a digital multifunction timer relay for industrial control applications. It combines two independently configurable timer relays in one housing with a width of 22.5 mm, reducing the space requirement in the enclosure. The device is designed for use in enclosures and is suitable for time-controlled processes in automation technology. The rated voltage includes two operating voltages: AC/DC 24 V and AC 230 V, enabling flexible use in various installations.
Applications
This timer relay is designed for applications in industrial automation where time-controlled switching operations are required. It can be used, for example, to control pumps, motors, lighting systems, or in maintenance and service processes, where it can replace multiple different time functions in a single device. The digital setting allows precise timing sequences that can be adapted to specific requirements.
Functions and Equipment in Detail
Each of the two output relays can be configured independently. The available time functions include on-delay, off-delay, on-pulse, off-pulse, impulse generator, clock generator, pulse converter, and combinations thereof. The time ranges are separately adjustable and range from 0.02 seconds to 9999 hours. The functions can be set via an LCD display and buttons. The display alternates between the two relays and shows either the set values or the remaining time, with the latter mode only being activatable if at least one time setting is ≥ 1 second.
Technology Explained Simply
The device operates according to the standard IEC/EN 61812-1, which applies to timer relays in industry. The digital control enables precise and reproducible time control. Each of the two output relays is equipped with a changeover contact, resulting in a total of 2 changeover contacts. The contacts are fitted with fixed screw terminals, ensuring a secure connection. The LED indicator displays the device status: off (no operating voltage), green (operation), orange flashing (configuration), and red (error). In case of an error, the error code (e.g., “Err.1” for checksum error on relay 1) is displayed on the screen.
Compatibility and Accessories
The device is designed for use in enclosures and can be operated with various control signals via the control inputs B1(+) and B2(+). The control inputs are assigned to output relays 1 and 2 respectively. An optional version with plug-in terminal blocks is available, enabling quick replacement of the device. The terminal type is fixed as screw terminal.
Mounting and Installation
The timer relay is mounted in an enclosure. The connection terminals are designed for connection with wires. The supply voltage is supplied via terminals A1 (AC 230 V) and A3 (+) (AC/DC 24 V) as well as A2 (N / -). The control inputs B1(+) and B2(+) are used for signal transmission. Mounting is carried out in the usual manner for enclosure components.
Advantages in Operation
By combining two independently adjustable timer relays in one housing, the space requirement in the enclosure is reduced. The digital setting enables high precision and flexibility in adapting to different requirements. The LED indicator and display facilitate diagnosis and configuration. The device is designed for use in industrial environments and complies with the UKCA approval.