Dold 0061302, EAN: 4030641613020

Dold 0061302 GF9016 3AC200-480V UH DC24V 22KW soft starter

Dold 0061302 GF9016 3AC200-480V UH DC24V 22KW soft starter

Lieske Part No. 1002137
Mfg Part No 0061302
EAN-Code 4030641613020
Manufacturer Dold
Here only 902,24 EUR
1.073,67 EUR incl. VAT

Further information for Dold 0061302 GF9016 3AC200-480V UH DC24V 22KW soft starter

Technical data
Extra functionsMains monitoring, Temperature monitoring
For three-phase motors, 400 V up to22 kW
Load voltage up to3AC 400 V
Width45 mm, 52,5 mm
TypeGF 9016
Signalling outputYes
Variant
Auxiliary voltageDC 24 V
Mains / motor voltage3AC 200 - 480 V
Nominal motor power22 kW
Approvals and MarkingsUKCA
The Dold GF9016 is an electronic soft-start and soft-stop device for three-phase asynchronous motors. It is designed for controlled operation of motor start-up and shut-down processes with a rated power up to 22 kW. The device variant with auxiliary voltage DC 24 V is designed for supply and motor voltages in the range 3AC 200–480 V. The device complies with the standard IEC/EN 60947-4-2 and is marked with the UKCA approval. The width is 52.5 mm, enabling installation in standard control panels.

Applications
This device is suitable for drives with mechanical loads where a smooth start-up and shut-down are required. Typical application fields include conveyor belts, fans, pumps, compressors, woodworking machines, centrifuges, packaging machines, and door drives. It is particularly advantageous for drives with gear, belt, or chain transmission, as it reduces mechanical stress caused by sudden torque impulses.

Functions and Equipment in Detail
The GF9016 operates on the principle of phase-cut control. Two motor phases are controlled via power semiconductors (thyristors), allowing the current and torque of the motor to increase gradually. This prevents the sudden start-up torque that would occur with direct switching. After start-up, the circuit is bypassed via internal relay contacts to minimize power loss in the device. The soft-stop function extends the natural deceleration time of the drive to avoid jerky stopping. Device functions include mains monitoring and temperature monitoring, contributing to safety and reliability. An alarm output is integrated to indicate faults.

Technology Explained Simply
Control is achieved via an electronic ramp control, which drives the thyristors through an ignition pulse generator. Optionally, a kick-start function can be activated, providing a short pulse at the beginning of start-up to assist the start-up process. The device connection terminals are clearly marked: X1 (output +24 V), X2 (start/stop), X3 (kick-start 0.5 s), X4 (0 V), X5/X6 (alarm output, fault), X7/X8 (alarm output, device bypassed). The green LED indicates the ready-to-operate status, while the yellow LED flashes at a specific frequency during faults, indicating the fault code (e.g., supply voltage fault, overload, electronic fault). W3 wiring is possible, increasing flexibility during installation.

Compatibility and Accessories
The device is designed for 3-phase asynchronous motors operated in the voltage range 3AC 200–480 V. The load voltage is up to 3AC 400 V. The auxiliary voltage is DC 24 V. The device functions are designed for motors up to 22 kW. Control is performed via the designated terminals, with adjustment options for start-up and shut-down time as well as start-up voltage allowing individual adaptation to specific applications.

Mounting and Installation
The device is mounted in standard control panels. The width of 52.5 mm corresponds to the format for motors up to 22 kW. The connection terminals are clearly labeled, simplifying installation. Connections are made to terminals L1, L2, L3 (supply voltage) and T1, T2, T3 (motor voltage). Control is performed via signal terminals X1 to X8. W3 wiring is possible, enabling flexible installation in existing systems.

Advantages in Operation
Smooth start-up and shut-down reduce mechanical wear on motors and drive components, increasing service life. Reduction of start-up currents relieves the supplying network. Simple mounting and clear signaling via LEDs and alarm outputs facilitate maintenance and fault diagnosis. Integrated mains and temperature monitoring increase operational safety. The possibility of W3 wiring expands application options in existing installations.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/1002137
qrcode für Dold 0061302 GF9016 3AC200-480V UH DC24V 22KW soft starter