Further information for Dold 0059428 overcurrent relay AC220-240V 10-100A
Technical data
1- / 3-phase
3
Enclosure design
Switch cabinet
Output contacts
2 C/O contacts
Width
70 mm
Type
SP 9270CT
Operate delay
Variant
Auxiliary voltage
AC 220 - 240 V
Contact equipping
2 changeover contacts
Measuring range
10 - 100 A
Time delay
0,1 - 20 s
Variant
3-phase current relay with built in CT. De-energized on trip
The Dold SP9270.12CT is a 3-phase current relay for monitoring currents in alternating and three-phase power systems. It is used for overcurrent monitoring and is employed in industrial installations and enclosures to trigger a response when a set threshold is exceeded. The device operates on the zero-current principle, whereby the output relay is de-energized in the event of a fault, ensuring safe disconnection. The auxiliary voltage is AC 220–240 V, and the measurement ranges are between 10 and 100 A. The time delay is adjustable and ranges from 0.1 to 20 seconds, allowing short-term current surges to be considered or ignored.
Applications
This relay is designed for use in industrial and technical installations where precise current monitoring is required. It is suitable, for example, for protective functions for motors, transformers, or other electrical consumers that must be protected against overload. The galvanic isolation between the auxiliary circuit and the measurement circuit ensures high safety and prevents interference in the control circuit. The 3-phase measurement enables simultaneous monitoring of all three phases, which is crucial for operational safety in three-phase installations.
Functions and Equipment in Detail
The device features 2 changeover contacts as output contacts, which can be used to control auxiliary circuits or alarms. The pickup value is adjustable, allowing the relay to be flexibly adapted to different loads and requirements. The hysteresis is fixed at approximately 4 %, ensuring stable switching behavior during current fluctuations. The LED indicators signal the operating status: a green LED indicates that the current is within acceptable limits, while a red LED lights up in case of overcurrent. The display is directly visible to the operator and enables quick fault detection.
Technology Explained Simply
The SP9270.12CT integrates a current transformer, which makes the monitored current measurable without requiring direct electrical connections to the main circuit. The measurement is performed by passing the conductors through the transformer, thereby inductively detecting the current. The auxiliary voltage is supplied via terminals A1/A2 and powers the relay with the necessary energy for controlling the contacts. The time delay allows short-term load peaks, which are not harmful, to be ignored, while sustained overloads are reliably detected.
Compatibility and Accessories
The device is designed for use in enclosures and corresponds to the enclosure form enclosure. The width is 70 mm, making it suitable for standard enclosure mounting. It is manufactured in accordance with IEC/EN 60 255-1, confirming compliance with international standards for electrical measuring instruments and relays. It can be combined with other devices from the SP-9270 series, especially in configurations requiring 3-phase monitoring. The connection terminals are located at the top, which is typical for the S form factor and facilitates installation in enclosures with mounting plate and cable duct.
Mounting and Installation
Mounting is performed in enclosures with a mounting plate. The connection terminals are positioned at the top, enabling easy wiring. The depth is 100 mm, providing sufficient space for wiring and secure installation. The terminal designation is clearly defined: A1/A2 for auxiliary voltage, i1/k1 to i3/k3 for the measurement circuits of the three phases, and Z1/Z2, Z3/Z4 are used for selecting the measurement range via bridges.
Advantages in Operation
The SP9270.12CT offers reliable and precise current monitoring with adjustable parameters that can be adapted to the specific application. The galvanic isolation between the measurement and auxiliary circuits increases safety. The LED indicators enable quick visual monitoring of the operating status. The adjustable time delay reduces false alarms caused by short-term load peaks. The device is designed for use in industrial environments and complies with applicable standards, ensuring high operational safety.