Further information for Dold 0059108 load monitor DC24V
Technical data
1- / 3-phase
1, 3
Enclosure design
Switch cabinet
Measuring range max.
40 A (37 kW)
Output contacts
2 x 1 C/O contacts
Width
45 mm
Type
BH 9097
Operate delay
Variant
Auxiliary voltage
DC 24 V
Contact equipping
2 x 1 changeover contact
Nominal current max
AC 40 A
Nominal voltage
3AC 100 - 760 V
Approvals and Markings
CCC
Variant
3-phase with auxiliary supply. Start up delay time 0 - 30 s
The load monitor BH9097.38/0113AC100-760VAC40A from Dold is an industrial monitoring switch for electrical consumers, particularly for motors with variable load. The device monitors active power and responds to exceeding or falling below adjustable threshold values by activating the output relays. It is designed for use in enclosures and is suitable for single-phase and three-phase installations in the voltage range of 3AC 100 to 760 V. The maximum rated current is 40 A, corresponding to a power of up to 37 kW at 690 V. The auxiliary voltage is DC 24 V, and the device has a width of 45 mm.
Applications
The load monitor is designed for monitoring industrial motors and electrical consumers where continuous load monitoring is required. It serves to detect load anomalies, such as underload or overload, to prevent damage to drives or machines. The application is in industrial plants where operational safety and system availability are of high importance. The automatic range switching enables a wide measurement range without additional current transformers up to 40 A.
Functions and equipment in detail
The device features two output relays, each with a 1-changeover contact, responsible for signaling P1 (underload or overload) and P2 (overload). The threshold values for P1 and P2 can be set via rotary switches as absolute values in watts. The adjustment is made using an absolute scale, allowing for precise calibration. The relays can be operated in either the active current principle (activated in case of fault) or the idle current principle (not activated in case of fault), with configuration done via DIP switches. A test/reset button supports commissioning and serves as an adjustment aid.
Technology explained simply
Measurement is performed based on the principle of active power measurement. The device detects load changes and reacts when the set thresholds are exceeded. An adjustable response delay tv suppresses short-term load fluctuations to avoid false alarms. A common adjustable start-up bypass time ta (0 to 30 seconds) prevents the monitor from tripping during a motor’s start-up phase. The functions are configurable via DIP switches, with options including P1min/P2max (underload and overload monitoring) and P1max/P2max (overload monitoring with pre-warning stage).
Compatibility and accessories
The device is suitable for single-phase and three-phase loads, with three-phase installations requiring symmetrical loading of all phases, as is typical for motor loads. The operating voltage is in the range of 3AC 100 to 760 V, and the auxiliary voltage is DC 24 V. Certification according to IEC/EN 60255-1 ensures compliance with standards for electrical measuring instruments. Indication is provided via LEDs: a green LED indicates mains voltage, while two yellow LEDs signal the status of relays P1 and P2. In fault conditions, the LEDs blink in specific patterns to distinguish between “no measurement” and “reverse power”.
Mounting and installation
The device is designed for mounting in enclosures and has a width of 45 mm. Installation is carried out via the designated connection terminals. The terminal assignment is detailed in the data sheet. Configuration is done via DIP switches and rotary switches, with settings adjustable directly on the device. Commissioning is facilitated by the test/reset button.
Advantages in operation
By enabling early detection of load anomalies, the load monitor allows for preventive maintenance, thereby avoiding costly downtime and damage to drives. Reduced wiring due to integrated functionality reduces installation effort. The clear LED display and adjustable delay times increase reliability and user-friendliness. The device is designed for industrial environments and meets the requirements of standard IEC/EN 60255-1. CCC certification is also available.