| Technical data |
| Enclosure design | Switch cabinet |
| Output contacts | 2 NC contacts, 4 NO contacts |
| Time function(s) | Flasher relay, Fleeting on break, Fleeting on make, Impulsgeber, Off-delay, with control signal, On- and Off-delay, On-delay, Pulse extender |
| Width | 52,5 mm |
| Type | SN 7920 |
| Variant |
| Contact equipping | 2 x 2 NO contacts, 2 NC contacts |
| Nominal voltage | AC/DC 24 - 230 V |
| Time range | 0,05 s - 300 h |
| Approvals and Markings | UKCA |
| Variant | To switch high DC-loads with mechanical forcibly guided contacts, different terminal designation (see Circuit Diagram) |
The Dold multifunction relay SN7920/001 AC/DC24-230V 0,05S-300H is an industrial time relay for applications in automation technology, particularly in industrial and railway technology. It enables the control of time-dependent processes with high flexibility through eight different functions, which can be set via a rotary switch. The device design is intended for use in enclosures, with a width of 52.5 mm, allowing compact mounting on DIN rails or via screw fastening. The rated voltage is in the range AC/DC 24 to 230 V, making the relay suitable for various electrical systems.
Applications
The relay is designed for time-controlled processes in industrial plants and railway applications. It is suitable, for example, for delaying switching operations, implementing blinking functions, pulse shaping, or generating short switching pulses. The ability to switch large DC loads is ensured by mechanically interlocked contacts in accordance with IEC 61810-3, guaranteeing reliable switching performance even under high loads. Application areas include, among others, drive technology, lighting control, safety functions, and process automation.
Functions and Equipment in Detail
The device offers eight different time functions, which can be selected via a rotary switch: On-delay (AV), On-wipe function (EW), Delayed pulse generator (IE), Blinking function with pulse start (BI), Off-delay (RV), Pulse shaper (IF), Off-wipe function (AW), and On-delay and Off-delay (AV/RV). The time ranges are adjustable in eight steps from 0.05 seconds to 300 hours. The functions are designed to meet various control requirements, such as delaying the switching on or off of loads, generating pulses, or implementing blinking functions.
Technology Explained Simply
The output contacts consist of two normally open contacts and four normally closed contacts, with the contacts mechanically interlocked to ensure safe and reliable switching performance even under high DC loads. The contacts are organized in two relays (Relay 1 and Relay 2), where Relay 2 can be switched via a rotary switch between timer function, immediate contact via auxiliary voltage (A1/A2), or control input (B1/B2). The time control is performed via a potentiometer, which sets the time ranges through the rotary switch. An adjustment aid enables quick setting of long times by using the LED flash frequency as a reference. The LED indicators signal supply voltage (green LED), the state of the output relay, and the time progression (yellow LEDs). The yellow LED R/t indicates the time progression and contact position, with steady light, blinking (short on, long off), and blinking (long on, short off) indicating different states.
Compatibility and Accessories
The relay is designed for use in enclosures and can be installed either on DIN rails or via screw mounting. The terminal connections are designed for connection to wires, with the terminal designation detailed in the circuit diagram. Control is performed via the auxiliary voltage A1/A2 and the control input B1/B2. The functions are usable independently of voltage type (AC/DC) in the range 24 to 230 V. Conformity is ensured in accordance with IEC/EN 61812-1 and DIN EN 50155, confirming suitability for industrial and railway applications. The UKCA approval is also available.
Mounting and Installation
Mounting is either on a DIN rail or via screw fastening in the enclosure. The width of 52.5 mm allows for compact placement. The terminal connections are clearly labeled, with the terminal designation detailed in the circuit diagram. The function and time range settings are adjusted via rotary switches, with the settings only taking effect when the auxiliary voltage is switched on. Changes to the settings during operation have no effect. The LED indicators support commissioning and maintenance by visually displaying the operating status.
Advantages in Operation
The combination of eight functions in a single device offers high flexibility and reduces the number of required components in control technology. The mechanically interlocked contacts ensure reliable switching performance even under high DC loads. The LED indicators facilitate diagnosis and maintenance, as the operating status and time progression can be visually monitored. The adjustment aid for long times reduces commissioning time. Conformity with IEC/EN 61812-1 and DIN EN 50155 ensures suitability for demanding industrial and railway applications. The UKCA approval confirms compliance with applicable requirements in the United Kingdom.