| Technical data |
| Diameter | 70 mm, 105 mm |
| For relay type | IL 5882, SL 5882 |
| Type | ND 5019 |
| Variant |
| Variant | 105 mm inner diameter |
The Dold differential current transformer ND5019/105WN1227.053.660 is a component for measuring differential currents in electrical installations. It is specifically designed for use with the differential current monitors IL 5882 and SL 5882 to detect insulation faults in earthed networks at an early stage. The variant with a 105 mm internal diameter allows mounting around conductors with a diameter up to 105 mm, with a 70 mm variant also available. The transformer serves as an external sensor, which in combination with the monitoring device monitors the sum of all currents in an electrical circuit. In a fault-free condition, the sum of currents is zero, so no measurement signal is generated. In the event of an insulation fault, a fault current flows to earth, creating a current difference that is detected by the transformer and transmitted to the monitoring device.
Applications
The differential current transformer ND5019 is used in industrial and installation applications where continuous insulation monitoring is required. It is suitable for installations executed in accordance with DIN 43880 and can be mounted in enclosures or distributors. The application is particularly in earthed networks to ensure preventive fire and system protection. Early detection of insulation degradation enables targeted maintenance without interrupting operations.
Functions and Equipment in Detail
The transformer operates on the principle of differential current measurement. All conductors of the circuit to be monitored (excluding protective earth PE) are passed through the transformer. Measurement is carried out via terminals i and k, which are connected to the differential current monitor IL 5882 or SL 5882. The 105 mm internal diameter version offers flexibility for mounting around larger cables. The construction is designed to detect a broken conductor in the measurement circuit to prevent malfunction. The transformers are suitable for alternating and pulsating direct currents, type A, according to IEC/TR 60755.
Technology Explained Simply
The technology is based on induction of a secondary current in the transformer when a fault current flows through the insulation. The sum of currents in a fault-free system is zero, so no induced current is generated. In the event of a fault, a current difference occurs, which is detected by the transformer. Measurement takes place in the frequency range of 20 to 2000 Hz, covering a wide range of application scenarios. The output is sent to the connected monitoring device, which evaluates the measurement values and triggers a pre-alarm or alarm if a set threshold is exceeded.
Compatibility and Accessories
The differential current transformer ND5019 is specifically developed for use with the differential current monitors IL 5882 and SL 5882. It can be combined with other transformers such as ND 5016 or the hinged current transformer ND 5014, depending on the installation requirements. Mounting is carried out in enclosures with mounting plate and cable duct (SL 5882) or in installation and industrial distributors (IL 5882). The width is 35 mm, and the depth varies depending on the device type (63 mm for IL 5882, 100 mm for SL 5882).
Mounting and Installation
Mounting is done by passing the conductors to be monitored through the transformer. Terminals i and k are connected to the differential current monitor. Installation takes place in enclosures or distributors, with the depth and position of the connection terminals (top or bottom) varying depending on the device type (SL 5882 or IL 5882). The use of sealable transparent covers on the rotary switches of the monitoring device protects against unauthorized adjustment.
Advantages in Operation
The use of the differential current transformer ND5019 enables early detection of insulation faults, increasing the availability of the system. Operation interruption is avoided, as the device only triggers a pre-alarm or alarm without switching off the circuit. The broken conductor detection ensures reliable measurement, and compatibility with various device types offers flexibility in planning and installation. Compliance with the standard IEC/EN 62020 ensures the reliability and safety of the system.
Differential current transformer,
insulation monitoring,
differential current monitor,
IL 5882,
SL 5882,
IEC/EN 62020