| Technical data |
| 1- / 3-phase | 1 |
| Enclosure design | Distribution board |
| Measuring range | AC 0,175 - 1 A |
| Output contacts | 1 C/O contact |
| Width | 17,5 mm |
| Type | IK 8839 |
| Variant |
| Auxiliary voltage | AC 220 - 240 V |
| Contact equipping | 1 changeover contact |
| Switching point | 1 A max. 20 A |
| Variant | With a fixed operate delay 180 ... 300 ms |
The current monitor IK8839.11/001 from Dold is an industrial monitoring switch designed for functional monitoring of predominantly electro-thermal loads such as heating elements or pipe tracing heaters. The device checks whether operating current is flowing when the load is switched on, and reacts to deviations from the pre-set switching point. It is designed for use in installation distributors and is mounted on a DIN rail. The width is 17.5 mm, enabling compact installation in standard control panels.
Applications
This current monitor is specifically designed for monitoring loads that exhibit a constant current consumption in the range of 0.175 to 1 A. Typical applications include heating systems in industrial processes, food processing, or building automation, where interruption of the heating current can lead to functional failures. The device is designed for continuous operation and functions within a temperature range of -20 °C to +60 °C.
Functions and Features in Detail
The device features a fixed switching point of 1 A, operating with a tolerance of ±15 %. If this value is undershot, the output is activated via a changeover contact. The response delay is 180 to 300 ms, which compensates for short-term current fluctuations and prevents false tripping. The auxiliary voltage is supplied via AC 220–240 V, with a nominal consumption of 2.2 VA (apparent power) and 0.5 W (active power). Two LED indicators signal the operating status: the upper LED lights up when auxiliary voltage is applied, and the lower LED when the output relay is activated.
Technology Explained Simply
The current monitor measures the flowing operating current via inputs i/k and compares it with the set switching point. If the switching point is undershot, the output relay contact (1 changeover) is actuated. The contact configuration allows control of auxiliary relays, signal lamps, or other control elements. The overload capacity is up to 20 A continuously and 150 A for 2 seconds, providing high robustness against short-term current surges. The contact rating is 3 A / AC 230 V for closing contacts and 1 A / AC 230 V for opening contacts according to AC 15.
Compatibility and Accessories
The device is designed for mounting on a DIN rail according to IEC/EN 60715. The connection terminals are rated for conductor cross-sections of 2 x 2.5 mm² (solid) or 2 x 1.5 mm² (stranded wire with ferrule DIN 46228-1/-2/-3/-4). The stripping length is 10 mm, and the tightening torque for the terminals is 0.8 Nm. The switching function complies with IEC/EN 60255-1. The enclosure protection rating is IP 40, and the terminals are rated IP 20.
Mounting and Installation
Mounting is done by securing the device to a DIN rail within the installation distributor. The connection terminals are equipped with flat terminals that allow self-stripping. Cable connections are made at terminals A1/A2 (voltage supply), i/k (current measurement inputs), and 11/12/14 (changeover contacts). The terminals comply with standard EN 50005.
Advantages in Operation
The current monitor provides reliable functional monitoring with a fixed switching point and integrated response delay, which compensates for short-term disturbances. The LED indicators allow for quick visual status checks. The high overload capacity and mechanical life of 20 million operations ensure long service life. The device is designed for use in industrial environments with high electromagnetic compatibility (EMC) stress and meets the requirements for immunity according to IEC/EN 61000-4-2 to -4-6. The operating altitude is limited to below 2000 m, and the relative humidity is up to 93 % at 40 °C.