Further information for Dold 0053649 voltage relay AC50-500V UH
Technical data
1- / 3-phase
1
Enclosure design
Switch cabinet
Nominal voltage max.
AC 1000 V, DC 900 V
Output contacts
2 C/O contacts
Width
45 mm
Type
BA 9054
Operate delay
Variant
Auxiliary voltage
AC/DC 24 - 80 V
Contact equipping
2 changeover contacts
Measuring range
AC 50 - 500 V
Start up delay
Without
Switching delay
0 - 20 s
Approvals and Markings
UKCA, CCC
Variant
Overvoltage relay. Energized on trip. Time delay at setting value
The Dold voltage relay BA9054/010 is an overvoltage relay of the VARIMETER series, designed for monitoring single-phase DC and AC voltage networks. It is used for continuous monitoring of network voltage to prevent damage caused by voltage spikes or anomalies. The device setting is performed via rotary switches on the front panel, ensuring simple and user-friendly configuration. The relay operates on the operating current principle and is designed for use in industrial and railway applications, where high operational safety and reliability are required.
Applications
The relay is designed for monitoring voltages in the range of AC 50 to 500 V. It can be used both as an overvoltage relay and as an undervoltage relay, with the hysteresis depending on the set threshold value. The galvanic isolation between auxiliary circuit and measurement circuit ensures safe and interference-free measurement. The application is in enclosures, where the device is integrated with a width of 45 mm using standard rail mounting.
Functions and equipment in detail
The device features 2 changeover contacts as output contacts, which switch when the set threshold value is reached. The switching delay is 0 to 20 seconds and is activated when the set value is exceeded. The response delay is also integrated, preventing short-term voltage fluctuations from triggering an unwanted switching operation. The auxiliary voltage is supplied via AC/DC 24 to 80 V, enabling flexible integration into existing control systems.
Technology explained simply
The relay measures the arithmetic mean of the rectified measurement voltage. For AC voltages, the device is calibrated to the RMS value. The setting is performed via rotary switches, allowing both the pickup value and the drop-out value (hysteresis) to be adjusted. The LED indicators signal operational readiness (green LED) and activation of the output relay (yellow LED). The maximum rated voltage is AC 1000 V and DC 900 V, with measurement ranges varying depending on the variant. The maximum permissible continuous voltage for the AC 50–500 V measurement range is 500 V.
Compatibility and accessories
The relay complies with standards IEC/EN 60255-1 and IEC/EN 60947-1. It has UKCA and CCC certifications. The galvanic isolation between auxiliary and measurement circuits enables safe integration into electrical systems. The terminal connections are clearly labeled: A1/A2 for auxiliary voltage, e/f for voltage input, and contacts 11–14 and 21–24 for the two changeover contacts. The measurement frequency can reach up to 5 kHz, suitable for applications with rapid voltage changes.
Mounting and installation
The device is intended for mounting in enclosures and is installed using standard rail mounting (DIN rail). The width is 45 mm, allowing compact placement in existing control systems. The terminal connections are designed for secure connections, with the terminal labeling detailed in the data sheet. Installation requires no additional tools, with electrical connections to be made according to technical specifications.
Advantages in operation
By detecting voltage anomalies early, the relay enables preventive maintenance and prevents failures in electrical systems. The precise and reliable measurement ensures higher operational safety. The LED indicators facilitate diagnostics during operation, as the relay status can be visually monitored. The switching delay prevents false alarms caused by short-term voltage fluctuations, thereby increasing system stability. The high overload capacity of the device ensures robust performance under industrial conditions.