Further information for Dold 0053647 voltage relay AC50-500V UH AC230V
Technical data
1- / 3-phase
1
Enclosure design
Switch cabinet
Nominal voltage max.
AC 1000 V, DC 900 V
Output contacts
2 C/O contacts
Width
45 mm
Type
BA 9054
Operate delay
Variant
Auxiliary voltage
AC 230 V
Contact equipping
2 changeover contacts
Measuring range
AC 50 - 500 V
Start up delay
Without
Switching delay
0 - 20 s
Approvals and Markings
UKCA, CCC
Variant
Overvoltage relay. Energized on trip. Time delay at setting value
The Dold voltage relay BA9054/010 AC50-500V UH AC230V is an industrial-grade overvoltage relay from the VARIMETER series, designed for monitoring single-phase DC and AC voltage networks. It enables early detection of voltage anomalies to prevent damage to electrical installations and enhance operational safety. Device settings are adjusted via rotary switches on the front panel, ensuring simple and user-friendly configuration. The relay operates on the principle of operating current and is designed for use in enclosures, with a width of 45 mm.
Applications
This relay is suitable for voltage monitoring in industrial installations and railway applications. It monitors DC and AC voltages in the range of AC 50 to 500 V. Galvanic isolation between the auxiliary circuit and the measurement circuit ensures safe and interference-free measurement. Typical applications include systems requiring preventive maintenance and rapid fault localization to minimize downtime.
Functions and Equipment in Detail
The device features two changeover contacts as output contacts, which can be used to control external circuits. The switching delay is 0 to 20 seconds and is activated when the set threshold is exceeded. The pickup delay is also integrated, preventing unwanted switching due to short-term voltage fluctuations. The auxiliary voltage is AC 230 V, allowing seamless integration into standard industrial installations. The start-up bypass is not available in this variant.
Technology Explained Simply
The relay measures the arithmetic mean of the rectified measurement voltage. For AC voltages, the device is calibrated to the RMS value, enabling precise measurement even with sinusoidal voltages. Settings are adjusted via rotary switches, allowing manual adjustment of both the pickup value and the hysteresis value. The hysteresis depends on the set value and ensures the relay does not switch uncontrollably due to minor fluctuations around the threshold. LED indicators signal operational readiness (green LED) and activation of the output relay (yellow LED).
Compatibility and Accessories
The relay complies with standards IEC/EN 60255-1 and IEC/EN 60947-1. The maximum permissible continuous voltage is AC 1000 V and DC 900 V. The measurement frequency can reach up to 5 kHz, enabling use in systems with high frequencies. Galvanic isolation between the auxiliary and measurement circuits ensures safe and interference-free operation. The UKCA and CCC certifications are valid for this variant.
Mounting and Installation
The device is designed for mounting in enclosures and is connected via designated terminal clamps. Terminals A1 and A2 supply the auxiliary voltage of AC 230 V, while terminals e and f are designated for the voltage measurement input. The output contacts (11, 12, 14 and 21, 22, 24) enable control of external loads. Mounting is performed in the usual manner within an enclosure, taking into account the width of 45 mm.
Operational Advantages
Precise and reliable voltage monitoring enhances operational safety. Early detection of voltage anomalies enables preventive maintenance, preventing failures and damage to electrical equipment. LED indicators simplify diagnostics, as the operating status and contact position are visually identifiable. The switching delay prevents unwanted switching during short-term voltage fluctuations, increasing system stability. Galvanic isolation between the measurement and auxiliary circuits ensures high safety and immunity to interference.