Further information for Dold 0053641 voltage relay AC25-250V UH
Technical data
1- / 3-phase
1
Enclosure design
Switch cabinet
Nominal voltage max.
AC 1000 V, DC 900 V
Output contacts
2 C/O contacts
Width
45 mm
Type
BA 9054
Operate delay
Variant
Auxiliary voltage
AC/DC 24 - 80 V
Contact equipping
2 changeover contacts
Measuring range
AC 25 - 250 V
Start up delay
Without
Switching delay
0 - 20 s
Approvals and Markings
UKCA, CCC
Variant
Overvoltage relay. Energized on trip. Time delay at setting value
The voltage relay BA 9054/010 from Dold is an industrial voltage monitoring relay for monitoring single-phase DC and AC power networks. It is designed for continuous monitoring of network voltage to prevent damage caused by voltage spikes or fluctuations. The device operates on the principle of operating current and switches when the set threshold value is exceeded. Adjustment is performed via rotary switches on the front of the device, ensuring simple and user-friendly configuration. The switching delay ranges from 0 to 20 seconds and is activated upon reaching the set value. The auxiliary voltage is supplied via AC/DC 24 to 80 V, with the measurement range for AC voltage being AC 25 to 250 V. The devices are designed for use in enclosures and have a width of 45 mm.
Applications
This relay is designed for use in industrial plants and railway applications where reliable voltage monitoring is required. It protects electrical devices from destruction due to overvoltage and enables preventive maintenance by detecting voltage anomalies early. The application is in single-phase systems, and the devices can be used as both overvoltage and undervoltage relays, with hysteresis depending on the set value.
Functions and Equipment in Detail
The device features two changeover contacts as output contacts, which are galvanically isolated from the measurement circuit. LED indicators signal operational readiness (green LED) and activation of the output relay (yellow LED). Measurement is performed using the arithmetic mean of the rectified measurement voltage, with the devices calibrated for sinusoidal AC voltages in RMS value. The response delay is integrated, preventing reactions to short-term voltage spikes. The maximum rated voltage is AC 1000 V and DC 900 V.
Technology Explained Simply
Voltage monitoring is performed via inputs e and f, with the internal resistance varying depending on the measurement range. For the range AC 25 to 250 V, the internal resistance is 2 MΩ, and the maximum permissible continuous voltage is 500 V. The switching delay t_v delays switching after exceeding the threshold value, preventing false alarms caused by short-term voltage fluctuations. The start-up bypass is not present in this variant, meaning the device becomes active immediately upon applying the auxiliary voltage.
Compatibility and Accessories
The relay is compliant with IEC/EN 60255-1 and IEC/EN 60947-1 standards and carries the UKCA and CCC certifications. It is designed for measurement frequencies up to 5 kHz and can be used in systems with high overload capacity. The galvanic isolation between the auxiliary and measurement circuits ensures safe and interference-free signal transmission. The devices are designed for use in enclosures and can be combined with other components of the VARIMETER series.
Mounting and Installation
Mounting is performed in standard enclosures with a width of 45 mm. The connection terminals are clearly labeled: A1 and A2 for auxiliary voltage, e and f for voltage input, and contacts 11, 12, 14 and 21, 22, 24 for the two changeover contacts. Adjustment of threshold values and hysteresis is performed via rotary switches on the front. The devices are designed for use in industrial environments and require no additional mounting aids.
Advantages in Operation
Early detection of voltage anomalies enables preventive maintenance and reduces downtime. The LED indicators facilitate diagnosis and fault localization. Galvanic isolation and high overload capacity increase the reliability of the device. The switching delay prevents unnecessary switching operations during short-term voltage fluctuations, extending the service life of connected devices. The devices are suitable for use in industrial and railway applications where high operational safety is required.