Further information for Dold 0053350 current relay BA9053/010 AC2,5-25A
Technical data
1- / 3-phase
1
Enclosure design
Switch cabinet
Output contacts
2 C/O contacts
Width
45 mm
Type
BA 9053
Operate delay
Variant
Auxiliary voltage
AC 230 V
Contact equipping
2 changeover contacts
Measuring range
AC 2,5 - 25 A
Start up delay
Without
Switching delay
0 - 20 s
Approvals and Markings
UKCA, CCC
Variant
Overcurrent relay. Energized on trip. Time delay at response value
The Dold current relay BA9053/010 AC2,5-25A AC230V 0-20S is an overcurrent relay of the VARIMETER series, designed for monitoring single-phase DC and AC power networks. It is used for continuous current monitoring in industrial plants and railway applications, enabling early detection of deviations in current consumption. Device settings are adjusted via rotary switches on the front panel, ensuring simple and user-friendly configuration. The function is based on the operating current principle, where the relay responds when the set current value is exceeded. The switching delay of 0 to 20 seconds allows for controlled response, compensating for short-term current peaks, such as those occurring during motor start-ups. The auxiliary voltage is AC 230 V, and the devices are designed for use in enclosures. The width of 45 mm enables compact mounting in standard control panels.
Applications
This relay is suitable for use in industrial plants, particularly in automation technology and railway operations. It monitors the current draw of electrical consumers, helping to prevent failures caused by overloads or malfunctions. Preventive maintenance is supported by the early detection of anomalies, enhancing operational safety and productivity. Galvanic isolation between the auxiliary circuit and the measurement circuit ensures safe and interference-free signal transmission.
Functions and Equipment in Detail
The device features 2 changeover contacts as output contacts, which can be used to control auxiliary circuits or alarm systems. The measurement range is from AC 2.5 to 25 A, with the devices calibrated for sinusoidal AC currents in RMS value. Measurement is performed using the arithmetic mean of the rectified measurement current. The response delay is integrated, meaning the relay does not switch immediately upon exceeding the set value, but after a defined delay time. The hysteresis depends on the set value and can be adjusted via the front panel switches. LED indicators signal operational readiness (green LED) and activation of the output relay (yellow LED).
Technology Explained Simply
The relay technology is based on an internal shunt resistor that measures the current flow and converts it into a corresponding signal. The auxiliary voltage of AC 230 V powers the device and activates the output contacts. The switching delay t_v delays switching after exceeding the set value, which is useful for transient load peaks. The start-up bypass is not available in this variant, so no special suppression of inrush currents is provided. The devices comply with IEC/EN 60255-1 and IEC/EN 60947-1 standards, ensuring reliability and safety in industrial applications.
Compatibility and Accessories
The relay is designed for use in single-phase systems and can be used as both an overcurrent and undercurrent relay, with hysteresis consideration required for undercurrent applications. Galvanic isolation between the measurement and auxiliary circuits enables safe integration into existing systems. The devices are designed for a maximum measurement frequency of 5 kHz, suitable for applications with rapid signal changes. The UKCA and CCC certifications confirm compliance with applicable safety and quality standards.
Mounting and Installation
Mounting is performed in enclosures with a width of 45 mm. The connection terminals are clearly labeled: A1/A2 for auxiliary voltage, i/k for current input, and contacts 11-14 and 21-24 for the two changeover contacts. Adjustment of the response and hysteresis values is done via rotary switches on the front panel. The devices are designed for maximum overload capacity, with exact values varying depending on the measurement range. The connection terminals are designed for secure and durable connections.
Operational Advantages
Continuous current monitoring enables preventive maintenance, minimizing failures and downtime. The clear LED display facilitates diagnosis and fault localization. The switching delay prevents unnecessary tripping during short-term load peaks. Galvanic isolation ensures high immunity to interference and safety. Compliance with IEC/EN 60255-1 and IEC/EN 60947-1 standards guarantees reliable performance in critical applications. The compact design and simple operation make this relay a practical solution for industrial monitoring systems.