Further information for Dold 0053125 current relay BA9053/010 AC0,5-5A
Technical data
1- / 3-phase
1
Enclosure design
Switch cabinet
Output contacts
2 C/O contacts
Width
45 mm
Type
BA 9053
Operate delay
Variant
Auxiliary voltage
AC 110 V
Contact equipping
2 changeover contacts
Measuring range
AC 0,5 - 5 A
Start up delay
Without
Switching delay
0 - 20 s
Approvals and Markings
UKCA, CCC
Variant
Overcurrent relay. Energized on trip. Time delay at response value
The current relay BA9053/010 from Dold is an overcurrent relay of the VARIMETER series, designed for monitoring single-phase DC and AC power networks. It is used for continuous monitoring of the current consumption of electrical loads, enabling early detection of deviations from the setpoint and thus preventing failures in industrial plants or railway applications. The device setting is adjusted via rotary switches on the front panel, ensuring simple and user-friendly configuration. The device operates on the operating current principle and is designed for use in enclosures, with a width of 45 mm.
Applications
This relay is intended for use in industrial plants and railway applications. It monitors the current consumption of loads to detect overloads or interruptions in current flow. Early fault localization enables preventive maintenance, enhancing operational safety and securing productivity. The application is in single-phase systems, with measurement provided for both DC and AC.
Functions and Equipment in Detail
The device features 2 changeover contacts as output contacts, which are galvanically isolated from the measuring circuit. The auxiliary voltage is AC 110 V, ensuring reliable power supply for the relay. The measuring ranges are fixed at AC 0.5 to 5 A, with the devices calibrated for sinusoidal AC currents in RMS value. Measurement is performed using the arithmetic mean of the rectified measuring current. The setting of the pickup value and hysteresis is adjusted via the rotary switches on the front of the device. The hysteresis depends on the set pickup value.
Technology Explained Simply
The relay operates as an overcurrent relay, but can also be used as an undercurrent relay. The switching delay t v delays switching after exceeding the set threshold. In overcurrent relays, the delay acts after exceeding the set value. The start-up bypass is not available in this variant, meaning no one-time suppression of switching operations during inrush currents occurs. The pickup delay is active, meaning the relay does not switch immediately upon reaching the threshold, but incorporates a delay. The maximum switching delay is 20 seconds. The LED indicators signal operational readiness (green LED) and activation of the output relay (yellow LED).
Compatibility and Accessories
The relay complies with IEC/EN 60255-1 and IEC/EN 60947-1 standards. The certifications UKCA and CCC are valid for this variant. It is designed for use in enclosures and can be integrated into existing control systems. The galvanic isolation between the auxiliary circuit and measuring circuit ensures safe and interference-free signal transmission. The measuring frequency can reach up to 5 kHz, enabling application in dynamic systems.
Mounting and Installation
Mounting is performed in standard enclosures. The width of 45 mm corresponds to DIN format, allowing the device to be installed in standard enclosure modules. The terminal connections are clearly labeled: A1/A2 for auxiliary voltage, i/k for current input, and contacts 11-14 and 21-24 for the two changeover contacts. Installation requires no special tools or additional components; wiring is done directly to the terminals.
Advantages in Operation
Precise and reliable measurement enables high operational safety. The LED indicators facilitate visual monitoring of the operating status. The switching delay prevents unnecessary tripping due to short-term current peaks. Galvanic isolation protects control electronics from interference. Simple adjustment via rotary switches reduces installation time and minimizes error sources. Application in industrial and railway environments demonstrates the device’s robustness and reliability under demanding conditions.