Further information for Dold 0053103 current relay AC230V 0-20S
Technical data
1- / 3-phase
1
Enclosure design
Switch cabinet
Output contacts
2 C/O contacts
Width
45 mm
Type
BA 9053
Operate delay
Variant
Auxiliary voltage
AC 230 V
Contact equipping
2 changeover contacts
Measuring range
AC 20 - 200 Ma
Start up delay
Without
Switching delay
0 - 20 s
Approvals and Markings
UKCA, CCC
Variant
Overcurrent relay. Energized on trip. Time delay at response value
The Dold current relay BA9053/010 is an overcurrent relay of the VARIMETER series, designed for monitoring single-phase DC and AC power networks. It is used for continuous monitoring of the current consumption of electrical loads, enabling early detection of deviations from the setpoint and thus preventing failures in industrial plants or railway applications. The device setting is performed via rotary switches on the front panel, ensuring simple and user-friendly configuration. The device operates on the operating current principle and switches when the set current value is exceeded, with an integrated switching delay of 0 to 20 seconds. This delay prevents unwanted tripping during short-term current surges, for example during motor start-up.
Applications
This relay is designed for use in industrial plants and railway applications, where high operational safety and reliability are required. It monitors current flow in single-phase systems and can be used as both an overcurrent and undercurrent relay, with hysteresis dependent on the set value. The galvanic isolation between auxiliary circuit and measuring circuit ensures safe and interference-free measurement. The measurement frequency can reach up to 5 kHz, enabling use in systems with rapid signal changes.
Functions and Equipment in Detail
The device features 2 changeover contacts as output contacts, which can be used to control external circuits. The auxiliary voltage is AC 230 V, allowing operation in standard enclosures. The LED indicator signals operational readiness (green LED) and activation of the output relay (yellow LED). Adjustment is done via a rotary switch, where both the pickup value and the drop-out value can be set using hysteresis. The width is 45 mm, enabling compact installation in standard enclosures.
Technology Explained Simply
The relay measures the arithmetic mean of the rectified measurement current. For AC current, the device is calibrated to the RMS value, enabling accurate measurement even with sinusoidal loads. The switching delay (0–20 s) ensures that the relay only switches after the set time has elapsed once the current exceeds the set value. This prevents false tripping during short-term current surges. The start-up bypass is not available in this variant, so no special suppression of start-up currents is provided. The galvanic isolation between measuring and auxiliary circuits protects against interference and increases safety.
Compatibility and Accessories
The relay is designed for use in single-phase systems and can be combined with other VARIMETER models. The certifications UKCA and CCC confirm compliance with applicable safety and quality standards. The devices are manufactured in accordance with IEC/EN 60255-1 and IEC/EN 60947-1, ensuring reliability and safety in industrial applications.
Mounting and Installation
The device is intended for mounting in enclosures and is connected via the designated terminals (A1/A2 for auxiliary voltage, i/k for current input). Terminals 11–14 and 21–24 serve the two changeover contacts. Mounting is done in standard enclosures with a width of 45 mm. Installation requires no special tools or additional components, as all necessary connections are directly available on the device.
Operational Advantages
By enabling early detection of current deviations, the relay allows for preventive maintenance, avoiding failures and increasing productivity. The clear LED indicator simplifies fault localization, and galvanic isolation increases operational safety. The high overload capacity of the device ensures robust performance even under demanding operating conditions. The adjustability of pickup and drop-out values provides flexibility in adapting to different load profiles.