| Technical data |
| Enclosure design | Switch cabinet |
| Output contacts | 1 C/O contact |
| Time function(s) | Off-delay, with control signal |
| Width | 22,5 mm |
| Type | BC 7933N |
| Variant |
| Contact equipping | 1 changeover contact |
| Nominal voltage | AC 42-48 V / DC 48 V |
| Time range | 0,15 - 3 s |
| Variant | Release delay, with control signal |
The Dold time relay BC7933N.81 is an industrial-grade, delayed-release time relay with control signal, designed for use in enclosures. It features a rated voltage of AC 42–48 V or DC 48 V and allows for an adjustable delay time of 0.15 to 3 seconds. The function is specified according to EN 61812-1, ensuring reliability and interoperability in industrial control systems. The device is designed for continuous operation and is suitable for time-controlled processes in plants, where the output returns delayed after deactivation of the control signal.
Applications
This time relay is used in industrial control systems where a time-delayed reset is required after deactivation of a control signal. Typical applications include control of drives, lighting systems, pumps, or valves, where a controlled shutdown process is necessary. The width of 22.5 mm enables compact mounting in standard DIN-format control panels.
Functions and Equipment in Detail
The device features a changeover contact as output contact, equipped with an AgNi contact material, ensuring high switching life and low contact resistance. The contact position is indicated by a yellow LED, which lights up when the output relay is activated (contacts 15–18 closed). Control is performed via control input B1, which is operated with the rated voltage — a potential-free control contact is not required. The time delay is continuously adjustable and can be varied within the range of 0.15 to 3 seconds.
Technology Explained Simply
The delayed release means that the output contact does not return immediately after deactivation of the control signal, but only after a set delay time. This enables controlled shutdown of loads. The operating voltage at A1–A2 must be continuously present, while the control signal is input via B1/A2. The reset time after completion of the delay is less than 50 ms, ensuring fast repeatability of the function. The time accuracy is ≤ 0.5 % + 10 ms, making the function suitable for precise control applications.
Compatibility and Accessories
The relay is designed for operating voltages in the range of AC 42–48 V and DC 48 V. It is equipped with a control input B1, which is operated with the rated voltage. The terminal clamps allow connection of stranded wires with 2 x 1.5 mm² (with ferrule and plastic sleeve DIN 46228-1/-2/-3/-4) or 2 x 2.5 mm² (with ferrule DIN 46228-1/-2/-3). The switching capacity is up to 3 A at AC 230 V for closing contacts and 1 A for opening contacts according to AC 15. The maximum short-circuit withstand requires a maximum fuse rating of 4 A gG/gL.
Mounting and Installation
The device is mounted in enclosures and is designed for a width of 22.5 mm. The terminals are designed for connection of stranded wires with the specified cross-sections. The operating temperature ranges from -20 °C to +60 °C, and the storage temperature ranges from -25 °C to +70 °C. The relative humidity may reach up to 95 % at 40 °C. The operating altitude is limited to a maximum of 2000 m above sea level.
Advantages in Operation
The time relay offers a high switching life (mechanical 10⁸ switching operations, electrical 1.5 x 10⁵ switching operations at 1 A/AC 230 V) and precise time control. The LED indicator enables visual monitoring of the contact status. The use of a control signal with rated voltage simplifies integration into existing control systems, as no additional potential-free contact is required. The EMC coverage according to IEC/EN 61000-4-2 to -4-6 ensures robust operation in electromagnetically stressed environments.