| Technical data |
| 1- / 3-phase | 3 |
| Enclosure design | Distribution board |
| Measuring range max. | 690 V |
| Output contacts | 2 C/O contacts |
| Standard measuring range | 3 AC 380 - 415 V |
| Width | 70 mm |
| Type | IP 9075 |
| Variant |
| Contact equipping | 2 changeover contacts |
| Nominal voltage | AC 380 - 440 V 50 - 400 Hz |
| Variant | Energized / De-energized on trip programmable. Manual reset programmable |
The Dold fuse monitor type IP9075.12/010 AC50...400HZ 380-440V is an industrial monitoring switch for continuous checking of the integrity of up to three load fuses in three-phase networks. The device enables early detection of blown fuses, even when the connected loads are switched off, thus preventing costly damage caused by unintended operating conditions. It is specifically designed for use in installation and industrial distribution systems, with the housing form intended for installation distributors according to DIN 43880.
Applications
The fuse monitor is used in industrial and commercial electrical installations where the reliability of power supply is crucial. Typical applications include monitoring three-phase motors, automatic disconnection in case of failure of one or more phase fuses, and lockout of start-up to prevent damage caused by incomplete phase supply. The devices are designed for networks with a rated voltage of AC 380 to 440 V and a frequency of 50 to 400 Hz, with a maximum measurement range up to 690 V. Standard measurement ranges are 3 AC 380 to 415 V.
Functions and Equipment in Detail
The device features two changeover contacts as output contacts, which are either activated (operating current principle) or deactivated (resting current principle) in case of fault, depending on programming. This setting can be adjusted via programming terminals X3, X4, and X5. Additionally, the memory behavior can be programmed via terminals X1 and X2, where a bridge between X1 and X2 enables automatic reset. Indication is provided by two LEDs: a green LED indicates intact fuses, while a red LED signals a fuse failure.
Technology Explained Simply
The measurement paths of the fuse monitor have an internal resistance in the megohm range, ensuring compliance with touch voltage regulations (internal resistance > 2000 Ohm/V), even if a fuse is missing or defective. The devices comply with IEC/EN 60255-1 and can be used with all common fuse types and sizes. Detection is independent of rotation direction and is reliable even in unbalanced networks, with harmonics, or with regenerative motors. The response time is shorter than that of conventional motor protection switches.
Compatibility and Accessories
The fuse monitor is designed for use in three-phase networks up to 3 AC 690 V and can be combined with various fuse types. The programming terminals X3, X4, and X5 allow selection between operating current and resting current principle, with the maximum cable length for these terminals being 3 m. The devices are available in two housing forms: I-type with 59 mm depth and bottom-mounted terminals, and S-type with 98 mm depth and top-mounted terminals. The housing width is 70 mm.
Mounting and Installation
Mounting is carried out in installation or industrial distributors according to DIN 43880. The terminals are arranged at the bottom, enabling easy integration into existing control systems. Terminals L1, L2, L3 are for connection before the fuses, L1', L2', L3' after the fuses. Programming terminals X1, X2, X3, X4, X5 are intended for setting the operating mode. De-energization requires switching off the upstream main switch.
Operational Advantages
Early detection of fuse failures increases system availability and prevents damage that could result from undetected defects. Programmable functions such as operating current/resting current principle and memory behavior allow flexible adaptation to different requirements. The clear LED indication simplifies diagnosis and maintenance. Reliability in unbalanced networks and with regenerative motors makes the device suitable even for demanding industrial environments.