| Technical data |
| 1- / 2-channel | 1, 2 |
| Approvals | UL-Recognized |
| Cat. / PL acc. to EN ISO 13849-1 | 4/e |
| Connection | Pluggable screw terminals |
| Output contacts max. | 4 NO contacts |
| SIL CL acc. to IEC/EN 62061 | 3 |
| SIL acc. to IEC/EN 62061 | 3 |
| Thermal current Ith max. | 5 A |
| Width | 22,5 mm |
| Type | BG 5924 |
| Variant |
| Contact equipping | 3 NO contacts, 1 NC contact |
| Nominal voltage | AC 230 V 50/60 Hz |
| Approvals and Markings | TÜV, UKCA, CCC |
The Dold BG5924.48AC230V50/60HZ is a
Not-Aus module of the BG 5924 series, designed for use in
safety-oriented applications in industrial environments. It protects personnel and machinery by safely enabling and interrupting a safety circuit. The device is designed for operation at a nominal voltage of
AC 230 V at 50/60 Hz and features a
width of 22.5 mm, making it suitable for installation in standard rail systems. The contact configuration includes
3 NO contacts and 1 NC contact, with a maximum of
4 NO contacts usable as output contacts. Connections are made via
removable screw terminals, enabling flexible and secure connections. The terminals are rated for wires with a cross-section up to 2.5 mm², and the use of ferrules and plastic collars according to DIN 46228-1/-2/-3/-4 is also possible.
Applications
This module is designed for applications requiring high safety integrity, such as in automation technology, machine controls, or combustion systems. It complies with the requirements of
EN 50156-1, confirming its suitability for use in combustion systems. The device class allows use in systems requiring
Performance Level (PL) e and
Category 4 according to
EN ISO 13849-1. Additionally, the module meets the requirements for
SIL 3 according to
IEC/EN 62061 and
SIL 3 according to
IEC/EN 61508, ensuring reliability in the event of failure. Certifications including
TÜV, UKCA, CCC and recognition by
UL-Recognized highlight its international applicability.
Functions and Features in Detail
The BG5924.48AC230V50/60HZ allows the safety circuit to be started
manually or automatically. Integrated
LED indicators show the operating status and the status of channels 1 and 2, simplifying fault diagnosis. A
short-circuit detection between terminal Y1 and ground provides additional safety by identifying potential faults in the circuit. Galvanic isolation in the circuit increases safety and prevents interference caused by electrical potential differences. The device is designed for
single-channel or dual-channel wiring, allowing flexible integration into various safety architectures.
Technical Explanation
The safety functions of the module are based on a redundant circuit, which maintains the other channel active in case one channel fails, provided the requirements of the respective standard are met. The maximum thermal current rating is
5 A, defining the contact load capacity under normal operating conditions. The width of 22.5 mm allows installation in standard rail systems, facilitating integration into existing control panels. The removable terminal blocks enable quick and secure installation and maintenance without tools.
Compatibility and Accessories
The module is part of the BG 5924 series and can be combined with other devices in this series, particularly with the IP 5924, which has a wider mounting width of 70 mm. The use of accessories such as terminal blocks or special connection cables is possible, provided they comply with the requirements of the respective standards. The mentioned certifications and markings ensure compatibility with various safety standards in Europe and internationally.
Mounting and Installation
Mounting is done in standard rail systems, with the width of 22.5 mm ensuring direct compatibility. The removable screw terminals allow for easy and secure connection of wires. The terminals are rated for wires up to 2.5 mm², and the use of ferrules and plastic collars according to DIN 46228-1/-2/-3/-4 is recommended. Installation must follow the manufacturer’s technical instructions, with correct wiring and adherence to safety regulations being critical.
Operational Advantages
The module offers high safety integrity by meeting the standards PL e / Cat. 4 and SIL 3, making it suitable for critical applications. The integrated LED indicators and short-circuit detection simplify maintenance and fault diagnosis. Galvanic isolation in the circuit increases electromagnetic compatibility and safety. The flexible wiring options (single- or dual-channel) and compact design enable easy integration into existing systems. The certifications TÜV, UKCA, CCC, and UL-Recognized ensure international usability and market access in various regions.