| Technical data |
| For single-phase motors, 230 V up to | 3 kW |
| For three-phase motors, 400 V up to | 5,5 kW |
| Load voltage up to | 3AC 230 / 400 V |
| Width | 45 mm |
| Type | BA 9010 |
| Variant |
| Mains / motor voltage | 3AC 230 / 400 V |
| Nominal motor power | 3/5,5 kW |
| Approvals and Markings | UKCA |
The Dold BA9010 3AC230/400V 3/5,5KW is an electronic soft starter for three-phase asynchronous motors. It enables controlled, jerk-free start-up of motors with rated powers up to 5.5 kW at 400 V and up to 3 kW at 230 V. Control is achieved via a single-phase motor drive, where one of the three motor phases is controlled using phase-cut control, allowing current and torque to increase steadily during start-up. This avoids the sudden start-up torque, protecting mechanical drive components and increasing the service life of motors and gearboxes. The device is compliant with IEC/EN 60947-4-2 and suitable for industrial applications where a soft start is required to prevent damage to conveyed goods, drive assemblies, or machinery.
Applications
The BA9010 is used in systems operating three-phase asynchronous motors, particularly in machines with gear, belt, or chain drives. Typical applications include conveyor belts, fans, pumps, compressors, packaging machines, and door drives. It can also be used with single-phase transformers for limiting inrush current. The application is especially beneficial when direct motor switching would cause mechanical wear, noise, or displacement of conveyed goods.
Functions and Equipment in Detail
The device features separate adjustment options for start-up time (0.5 to 5 seconds) and initial torque (0 to 70 %). These parameters can be adjusted according to drive requirements to optimally match the start-up to load conditions. LED indicators show the operating status – green for power supply, yellow for completed soft start. After start-up, the power electronics are bypassed via an internal relay contact to minimize power losses in the device. The width is 45 mm, enabling compact mounting.
Technology Explained Simply
Phase-cut control affects a single motor phase, allowing current in that phase to increase continuously. This results in a smooth rise in motor torque, ensuring a jerk-free start. Control is performed without a neutral conductor, simplifying installation. The device is designed for supply and motor voltages of 3AC 230 V and 400 V, with a voltage range of 60 to 240 V ±10 % at 230 V and 380 to 480 V ±10 % at 400 V. The rated frequency is 50/60 Hz. The maximum switching frequency is 100 operations per hour at 5 times rated current and 5 seconds start-up time. At higher switching frequencies, monitoring of the motor winding temperature is recommended.
Compatibility and Accessories
The BA9010 can be combined with motor brake devices, facilitating integration into existing systems. It is not intended for speed control of drives, and it cannot reduce inrush current in the network. For these functions, other device types such as GC 9012 or GC 9014 are required. The protection rating is IP 20, requiring installation in enclosed switchgear. Installation is on a 35 mm standard DIN rail. The operating temperature range is 0 to +45 °C, and the storage temperature range is -25 to +75 °C. At temperatures above 40 °C or at installation heights above 1000 m, a power reduction of 2 % per degree Celsius or per 100 m is required.
Mounting and Installation
The device is clipped onto a 35 mm standard DIN rail, enabling simple and quick installation. The terminal connections are rated for max. 2 x 2.5 mm² fine-stranded wire. Installation requires no special tools, and the terminal assignment is described in the data sheet. Use of a fast-acting fuse element (semiconductor fuse) is recommended to protect the semiconductor in case of fault. The assignment type is 1 according to IEC 60947-4-1, meaning the device must be replaced after a short-circuit fault.
Operational Advantages
Using the BA9010 extends the service life of motors and mechanical drive components by avoiding high start-up torque. Start-up noise is reduced, and in conveyor systems, it prevents slippage or tipping of conveyed goods. Simple mounting allows easy integration into existing systems. In simple applications, a frequency converter can often be omitted, reducing system costs. Bypassing the power electronics after start-up minimizes power losses and heat generation in the device.
Protection Rating and Operating Conditions
The IP 20 protection rating according to IEC/EN 60529 protects against finger contact and solid foreign objects, but not against water or dust. The device is intended for use in enclosed switchgear. The operating temperature range is 0 to +45 °C, with a required power reduction of 2 % per degree Celsius above 40 °C. Installation at heights above 1000 m also requires power derating. The overvoltage category is III, pollution degree is 2, and installation class is 3. The maximum switching frequency is 100/h at 5 times rated current and 5 seconds start-up time. The re-readiness time is 200 ms.
Approvals and Markings
The device carries the UKCA marking, confirming compliance with applicable European safety and health regulations. Conformity with IEC/EN 60947-4-2 ensures reliability and safety in industrial use. Approvals are documented in the data sheet and correspond to the technical state at the time of issue.